| 2006-08-08 00:00:00 | REVIEW IN PRORGESS |
| | ****UNSAT **** |
| | |
| | 1) NOTE: PLEASE SUBMIT WIND LOADING |
| | CALCULATIONS FOR NEW LT POLES. IF THESE |
| | ARE NOT GOING TO BE UNDER THIS PERMIT, |
| | THEN THE CALCULATIONS MAY NE SUBMITTED |
| | WITH A SEPARATE PERMIT APPLICATION FEES |
| | AND PLANS AT A LATER DATE. |
| | FBC 106.1.2 |
| | |
| | 2) NOTE: PLEASE BE SURE THE PLANS |
| | REFLECT THE FOLLOWING CODES AT A |
| | MINIMUM. |
| | 2002 NFPA-70, 2002 NFPA-72, 2003 |
| | NFPA-101. |
| | 2004 FBC. |
| | |
| | 3) NOTE: PLEASE SEE AUTOMATIC LIGHTING |
| | CONTROLS FOR SHUTTING OFF OF LIGHTING IS |
| | REQUIRED PER FBC CHAPTER 13 |
| | 13-415.1.ABC.1.1, .1.2 |
| | |
| | 4) NOTE: PLEASE SEE BLDG REVIEW AND |
| | POSSIBLE FIRE REVIEW COMMENTS FOR DOOR |
| | SWING OF ADJACENT TENANT SPACE TO BAY |
| | #2. |
| | PLEASE SEE DOOR SWING MAY BE REQUIRED TO |
| | BE CHANGED IF NOT 180 DEGREE SWING. IF |
| | DOOR SWING CHANGES, SWITCH LOCATION MAY |
| | BE IN NEED OF ADJUSTMENT. |
| | THIS IS ONLY BEING NOTED AS THIS LOOKS |
| | AS THOUGH IT MAY HAVE AN AFFECT ON |
| | ELECTRICAL PLANS. |
| | |
| | 5) NOTE: PLEASE PLACE NOTE ON PLANS |
| | WHICH STATES "PANIC HARDWARE" WILL BE |
| | REQUIREDON MAIN ELECTRICLA ROOM DOOR. |
| | 110.26, 90.4 |
| | |
| | 6) NOTE: PLEASE CORRELATE RISER DIAGRAM |
| | WITH PANELS SHOWN ON ELECTRICAL ROOM |
| | LAYOUT. PLEASE SEE "H" AND H1" SHOWN, |
| | AND RISER SHOWS "H" AND "L". |
| | FBC 106.1.2 |
| | |
| | 7) NOTE: PLEASE INDICATE OR NOTE A |
| | "FLOATING NEUTRAL" FOR HOUSE METER AS |
| | THIS IS AFTER THE FIRST MEANS OF |
| | DISCONNECT. |
| | PLEASE SEE 250.6,250.24B. |
| | |
| | 8) NOTE: PLEASE PROVIDE A NOTE FOR MSB |
| | AS THIS EQUIPMENT SHALL CONTAIN NOR MORE |
| | THAN 6 SPACES FOR MAINS. (THIS WOULD |
| | INCLUDE SP SPACES) . AS SHOWN IS THERE |
| | PERMANANT DEADFRONT WHICH PROHIBITS |
| | ADDTIONAL BRKRS? |
| | 230.70 |
| | |
| | 9) NOTE: PLEASE SEE RISER SHOWS AN |
| | EQUIPMENT GROUNDING COUNDUCTOR BEFORE |
| | THE FIRST MEANS OF DISCONNECT FROM FPL. |
| | PLEASE SEE 250.6,250.24B AS "EQUIPMENT |
| | GROUNDING CONDUCTORS" ARE ONLY INSTALLED |
| | AFTER THE FIRST MEANS OF DISCONNECT. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| 2006-08-07 00:00:00 | IN ELEC FOR REVIEW. |