Plan Review Notes For Permit 06070445
Permit Number 06070445
Review Stop E
Sequence Number 1
Notes
Date Text
2006-08-08 00:00:00REVIEW IN PRORGESS
 ****UNSAT ****
  
 1) NOTE: PLEASE SUBMIT WIND LOADING
 CALCULATIONS FOR NEW LT POLES. IF THESE
 ARE NOT GOING TO BE UNDER THIS PERMIT,
 THEN THE CALCULATIONS MAY NE SUBMITTED
 WITH A SEPARATE PERMIT APPLICATION FEES
 AND PLANS AT A LATER DATE.
 FBC 106.1.2
  
 2) NOTE: PLEASE BE SURE THE PLANS
 REFLECT THE FOLLOWING CODES AT A
 MINIMUM.
 2002 NFPA-70, 2002 NFPA-72, 2003
 NFPA-101.
 2004 FBC.
  
 3) NOTE: PLEASE SEE AUTOMATIC LIGHTING
 CONTROLS FOR SHUTTING OFF OF LIGHTING IS
 REQUIRED PER FBC CHAPTER 13
 13-415.1.ABC.1.1, .1.2
  
 4) NOTE: PLEASE SEE BLDG REVIEW AND
 POSSIBLE FIRE REVIEW COMMENTS FOR DOOR
 SWING OF ADJACENT TENANT SPACE TO BAY
 #2.
 PLEASE SEE DOOR SWING MAY BE REQUIRED TO
 BE CHANGED IF NOT 180 DEGREE SWING. IF
 DOOR SWING CHANGES, SWITCH LOCATION MAY
 BE IN NEED OF ADJUSTMENT.
 THIS IS ONLY BEING NOTED AS THIS LOOKS
 AS THOUGH IT MAY HAVE AN AFFECT ON
 ELECTRICAL PLANS.
  
 5) NOTE: PLEASE PLACE NOTE ON PLANS
 WHICH STATES "PANIC HARDWARE" WILL BE
 REQUIREDON MAIN ELECTRICLA ROOM DOOR.
 110.26, 90.4
  
 6) NOTE: PLEASE CORRELATE RISER DIAGRAM
 WITH PANELS SHOWN ON ELECTRICAL ROOM
 LAYOUT. PLEASE SEE "H" AND H1" SHOWN,
 AND RISER SHOWS "H" AND "L".
 FBC 106.1.2
  
 7) NOTE: PLEASE INDICATE OR NOTE A
 "FLOATING NEUTRAL" FOR HOUSE METER AS
 THIS IS AFTER THE FIRST MEANS OF
 DISCONNECT.
 PLEASE SEE 250.6,250.24B.
  
 8) NOTE: PLEASE PROVIDE A NOTE FOR MSB
 AS THIS EQUIPMENT SHALL CONTAIN NOR MORE
 THAN 6 SPACES FOR MAINS. (THIS WOULD
 INCLUDE SP SPACES) . AS SHOWN IS THERE
 PERMANANT DEADFRONT WHICH PROHIBITS
 ADDTIONAL BRKRS?
 230.70
  
 9) NOTE: PLEASE SEE RISER SHOWS AN
 EQUIPMENT GROUNDING COUNDUCTOR BEFORE
 THE FIRST MEANS OF DISCONNECT FROM FPL.
 PLEASE SEE 250.6,250.24B AS "EQUIPMENT
 GROUNDING CONDUCTORS" ARE ONLY INSTALLED
 AFTER THE FIRST MEANS OF DISCONNECT.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
2006-08-07 00:00:00IN ELEC FOR REVIEW.