2006-08-11 00:00:00BUILDING PLAN REVIEW
 PERMIT: 06070445
 ADD: 2015 OKEECHOBEE BLVD.
 CONT: BOCA DEVEL. & CONST.
 TEL: (561)391-6227
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 EX FBC CODE= 2004 EXISTING FLORIDA
 BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS
 NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 3) ARCHITECT STEVEN L. COHEN AR0006819
 IS WORKING WITH A DELINGUENT LICENSE,
 EXPIRED 02/28/05.
 WWW.MYFLORIDA.COM/LICENSING
  
 4) PLANS INDICATE THAT A SOILS
 INVESTIGATION IS TO BE COMPLETED.
 FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 WHERE THE BEARING CAPACITY OF THE SOIL
 IS NOT DEFINITLY KNOWN OR IS IN QUESTION
 THE BUILDING OFFICIAL MAY REQUIRE EXPLOR
 ATIONS, TEST OR OTHER ADEQUATE PROOF AS
 TO THE PERMISSIBLE SAFE BEARING
 CAPACITY. REQUIRED TEST AND RECOMMENDA-
 TIONS SUBMITTED TO VERIFY BEARING CAPA-
 CITY SHALL BE CERTIFIED BY A GEOTECH-
 NICALREPORT FROM A DESIGN PROFESSIONAL
 PROPERLY LICENSED IN THE STATE OF
 FLORIDA.
  
 5) A1.1.4 PLANS INDICATE THE USE OF ROOF
 SHORING DRAWINGS AND CALCULATIONS TO BE
 SEALED BY ENGINEER. PLEASE PROVIDE THESE
 SHORING PLANS.
  
 6) PLEASE PROVIDE SOME CLARITY ON AN
 ISSUE. SHEET A1.2 NORTH WALL OF THE
 PROJECT THERE APPEARS TO BE NEW
 EXTENSIONS (LOADING DOCKS) IN BAYS 1&2.
 A2.1 CLEARLY INDICATES THE NEW WORK TO
 BE COMPLETED, BUT NO VISIBLE PROPERTY
 LINES. ALTA/ACSM LAND TITLE SURVEY
 DATED 4/08/05 INDICATES ONE LARGE LOT,
 WHERE AS THE SURVEY COMPLETED BY WALLACE
 DATED 1/25/06 CLEARLY INDICATES TWO LOTS
 WITH A 20' DEDICATED ALLEY WITH A 20'
 INGRESS/ EGRESS EASEMENT.
 PLEASE INDICATE WHERE THE PROPERTY LINE
 IS LOCATED ON THE ARCHITECTURAL SHEETS
 TO SEE IF THE NEW EXTENTIONS CREATE
 TABLE 601 & TABLE 704.8 ISSUES.
  
 7) INTALKING WITH VINCE NOEL IN
 ENGINEERING ( CITY SURVEYOR) THIS NEW
 PROPERTY WILL ALSO NEED TO BE TIED TO
 THE PROPERTY TO THE SOUTH WHICH THE
 BUILDING SITS ON TO CREATE ONE PROPERTY
 SO THE NEW ADDITIONS DO NOT CROSS
 PROPERTY LINES AND PROVIDES THE REQUIRED
 AREA BY TABLE 704.8 FOR OPENINGS.
  
 8) THE OTHER ISSUE VINCE NOEL BROUGHT UP
 IS THE REROUTING OF ALL UTILITIES THAT
 NOW WILL NEED TO FOLLOW THE NEWLY
 CREATED INGRESS/ EGRESS EASEMENT.
 PERMITS NEED TO BE OBTAINED FOR THIS
 WORK.
  
 9) NOTE:8-14-06I SPOKE WITH HAROLD
 PISKURA THE MANAAGER OF THE RESIDENT
 INSPECTOR PROGRAM TO SEE IF A RESIDENT
 INSPECTOR WOULD BE NEEDED FOR THIS
 PROJECT. HAROLD INDICATED THAT A
 RESIDENT INSPECTOR "WOULDN"T" BE
 REQUIRED.
  
 10) ENERGY FORMS: EXISTING BUILDING CODE
 708.1 MINIMUM REQUIREMENTS. ALTERATIONS
 SUBJECT TO THIS CHARTER SHALL COMPLY
 WITH THE REQUIREMEENTS OF CHAPTER 13 OF
 THE FBC, BUILDING.
 13-101.1.6
 SHELL BUILDINGS.
 NONRESIDENTIAL BUILDINGS THAT ARE
 PERMITTED PRIOR TO DESIGN COMPLETION OR
 WHICH WILL BE FINISHED IN SECTIONS AT A
 TIME AFTER CONSTRUCTION OF THE SHELL
 SHALL COMPLY WITH EITHER METHOD B OR C
 OF SUBCHAPTER 13-4 OF THE CODE PRIOR TO
 GRANTING OF A PERMIT TO BUILD. ALL
 ASSUMPTIONS MADE ABOUT FEATURES NOT
 INSTALLED UNTIL LATER THAT ARE NOT ON
 THE BUILDING PLANS SHALL BE LISTED AND
 APPENDED TO THE COMPLIANCE FORM
 SUBMITTED TO THE BUILDING DEPARTMENT.
 UNLESS THE BUILDING IS COMPLETED AS PER
 ALL ASSUMPTIONS MADE IN THE ORIGINAL
 CODE COMPLIANCE SUBMITTAL, A REVISED
 CODE SUBMITTAL(S) USING METHODS A, B OR
 C SHALL BE SUBMITTED WHEN COMPLETION OF
 THE BUILDING (OR PART OF THE BUILDING)
 IS PERMITTED.
  
 11)A1.1 CODE ANALYSIS INDICATES THIS
 IS A LEVEL 3 ALTERATION. 707.5.1 AN
 ENGINEERING EVALUATION AND ANYLSIS THAT ESTABLISHES THE
 STRUCTURAL ADEQUACY OF
 THE ALTERED STRUCTURE SHALL BE PREPARED
 BY A REGISTERED ARCHITECT OR ENGINEER
 AND SUBMITTED TO THE BUILDING OFFICIAL.
 THE EVALUATION AND ANYLISIS SHALL
 DEMONSTRATE THAT THE ALTERED BUILDING OR
 STRUCTURE COMPLIES WITH THE FLORIDA
 BUILDING CODE, BUILDING FOR WIND
 LOADING.
 THE REPORT SUBMITTED WAS CALCULATED
 UNDER THE ASCE 7-98 WHEREAS THE 2004 FBC
 IS UNDER THE ASCE 7-02.
  
 12)A1.1 CODE ANALYSIS, INDICATES THIS
 EXISTING BUILDING IS TO COMPLY WITH
 LEVEL 3 ALTERATIONS, IT IS ALSOREQUIRED
 TO COMPLY WITH EXISTING BUILDING CODE
 FOR ADDITIONS CHAPTER 9. PROVIDE
 COMPLIANCE WITH 902.2 AREA LIMITATIONS.
 IF AREA INCREASES ARE TAKEN PROVIDE THE CALULATIONS.
  
 13A) A1.3 SITE PLAN DETAIL A8.1.1DETAIL
 NUMBER 3, PLANS DO NOT PROVIDE THE WIDTH
 OF THE CURB CUT.
  
 13B) A1.3 SITE PLAN DETAIL A8.1.2
 DETAIL# 2 ON THAT SHEET, NO SUCH DETAIL.
  
  
 13C) THE CROSS WALKS THAT LEAD FROM THE
 DEISABLED PARKING SPACE TO THE STORES
 DOES NOT LEAD TO THE STORE FRONTS WHERE
 THE COVERED ENTRY IS LOCATED BUT TO A
 SIDEWALK WITH A MUCH SMALLER CANOPY AND
 A FURTHER DISTANCE TO THE STORE FRONT.
 11-2.2 EQUIVALENT FACILITATION.
  
 14A) A1.2 SITE PLAN INDICATES THE NEW
 CURB CUTS ACCESS AISLES, NEW LANDSCAPE
 AND NEW LANDSCAPED ISLAND. EX FBC 706
 A BUILDING, FACILITY OR ELEMENT THAT IS
 ALTERED SHALL COMPLY WITH CHAPTER 11 OF
 THE FBC, BUILDING.
 11-4.6.2(1) ALL PARKING SPACES MUST
 BE LOCATED ON AN ACCESSIBLE ROUTE NO
 LESS THAN 44 INCHES (1118 MM)WIDE SO
 THAT USERS WILL NOT BE COMPELLED TO WALK
 OR WHEEL BEHIND PARKED VEHICLES
 THIS PLAN DOES NOT PROVIDE THE
 DISABLED ACCESS TO THE SSTORES WITHOUT
 TRAVELING BEHIND SOMEONE ELSES PARKED
 VEHICLE.
 NOTE, 11-4.1.6(2) DUTY TO PROVIDE AN
 ACCESSIBLE PATH OF TRAVEL TO ALTERED
 AREAS SHALL BE DEEMED DISPROPORTIONATE
 TO THE OVERALL ALTERATION WHEN THE COST
 EXCEEDS 20 % OF THE COST OF THE ALTERA-
 TION TO THE PRIMARY FUNCTION AREA.
 (A)(I) AN ACCESSIBLE ENTRANCE
 (II) AN ACCESSIBLE ROUTE
 (III) AT LEAST ONE ACCESSIBLE REST-
 ROOM FOR EACH SEX OR A SINGLE
 UNISEX RESTROOM
 (IIII) ACCESSIBLE TELEPHONE
 (IV) ELEMENTS SUCH AS PARKING, STOR-
 AGE OR ALARMS.
 PLEASE PROVIDE AN ALYSIS OF MONIES
 SPENT TO MEET THE 20% OF CONTRACT VALUE.
  
 14B) THE SECOND ISSUE IS THE CROSS WALKS
 AND HANDICAPPED ACCESS
 AISLES,11-4.6.2(1) SO THAT NO USER WILL
 NOT BE COMPELLED TO WALK OR WHEEL BEHIND
 PARKED VEHICLES.
 A1.1.3 THE DEMO PLAN DOESN'T
 INDICATE THE SITE AS IS NOW.
 11-4.1.6(1)
 GENERAL. ALTERATIONS TO EXISTING
 BUILDINGS AND FACILITIES SHALL COMPLY
 WITH THE FOLLOWING:
 (A)NO ALTERATION SHALL BE
 UNDERTAKEN WHICH DECREASES OR HAS THE
 EFFECT OF DECREASING ACCESSIBILITY OR
 USABILITY OF A BUILDING OR FACILITY
 BELOW THE REQUIREMENTS FOR NEW
 CONSTRUCTION AT THE TIME OF ALTERATION.
 (B)IF EXISTING ELEMENTS, SPACES, OR
 COMMON AREAS ARE ALTERED, THEN EACH SUCH
 ALTERED ELEMENT, SPACE, FEATURE, OR AREA
 SHALL COMPLY WITH THE APPLICABLE
 PROVISIONS OF SECTION 11-4.1.1 TO
 SECTION 11-4.1.3 , MINIMUM REQUIREMENTS
 FOR NEW CONSTRUCTION. IF THE APPLICABLE
 PROVISION FOR NEW CONSTRUCTION REQUIRES
 THAT AN ELEMENT, SPACE, OR COMMON AREA
 BE ON AN ACCESSIBLE ROUTE, THE ALTERED
 ELEMENT, SPACE, OR COMMON AREA IS NOT
 REQUIRED TO BE ON AN ACCESSIBLE ROUTE
 EXCEPT AS PROVIDED IN SECTION 11-4.1.6
 (2), ALTERATIONS TO AN AREA CONTAINING A
 PRIMARY FUNCTION.
  
 14C) PLEASE PROVIDE THE AMOUNT OF
 PARKINGSPACES THAT ARE REQUIRED FOR
 EACH OF THE OUT BUILDINGS, AND HOW MANY
 DISABLED SPACES ARE REQUIRED BY
 11-4.1.2(5).
  
 15) A1.3 PLANS INDICATE THE USE OF
 BOLLARDS IN FRONT OF THE STORES BUT NO
 DEMINSION IS PROVIDES FOR CENTER TO
 CENTER?1010.5 RAMPS THAT ARE PART OF A
 REQUIRED MEANS OF EGRESS SHALL NOT BE
 LESS THAN 44 INCHES (1118 MM) WIDE.
  
 16) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) STOREFRONT SYSTEMS/ MULLIONS
 B) GLAZED SWING DOORS
 C) EXTERIOR METAL SWING DOORS
 D)ROLL UP DOORS
 E)LOUVERS
 F) ROOF ASSEMBLIES
 G) PREMANUFACTURED METAL A/C STANDS
 H) METAL BAHAMA SHUTTERS SEE NOTE!
  
 17) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 18) W P B ADMINISTRTIVE CODE 106.3.3*
 PRODUCT APPROVALS. THOSE PRODUCTS WHICH
 ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 19) METAL BAHAMA SHUTTERS- TO BE
 INSTALLED IN THE FIXED OPEN POSITION,
 SHUTTERS WILL REQUIRE ENGINEERING IN THE
 OPEN POSITION. THIS SYSTEM WILL NOT
 REQUIRE FL COVERSHEET.
  
 20) THE SERIES A8 DRAWINGS SHOW A SERIES
 OF EXTERIOR BLOCK COLUMNS AND THE OTHER
 TWO SIDES OF THE BLOCK COLUMNS BEING
 CLAD IN PLYWOOD, WIRELATH AND STUCCO.
 THE PLANS DEPICTUSE OF 3/4" EXTERIOR
 GRADE PLYWOOD.
  
 20A) SECTION 603 PROVIDES THE
 COMBUSTIBLES THAT ARE ALLOWED IN A TYPE
 II BUILDING. SEE 603.1(1)1.2) NONBEARING
 EXTERIOR WALLS WHERE NO FIRE RESISTANCE
 RATING IS REQUIRED DOES ALLOW FIRE
 RETARDANT TREATED WOOD, NOT JUST
 PLYWOOD.
  
 20B) PLANS DO NOT INDICATE WHAT TYPE OF
 FINISH TO BE APPLIED TO SHEATHING,
 ASSUMED STUCCO? PROVIDE A WATER
 RESISTANCE BARRIER.1404.2
 WATER-RESISTIVE BARRIER.
 A MINIMUM OF ONE LAYER OF NO. 15 ASPHALT
 FELT, COMPLYING WITH ASTM D 226 FOR TYPE
 1 FELT, SHALL BE ATTACHED TO THE
 SHEATHING, WITH FLASHING AS DESCRIBED IN
 SECTION 1405.3 , IN SUCH A MANNER AS TO
 PROVIDE A CONTINUOUS WATER-RESISTIVE
 BARRIER BEHIND THE EXTERIOR WALL VENEER.
  
  
 20C) THE METAL STUDS INDICATE 2X6 BUT
 NOT WHAT GAUGE?
  
 20D) A8.1.4 PORTACO CEILING INDICATES
 USE OF 2X6 NO GAUGE OF STUD? IS THERE TO
 BE STIFF BACKS? WHAT DEFLECTION IS BEING CONSIDERED
 INTO THE DESIGN?
  
 20E) THE PLANS INDICATE ONLY 5/8" SMOOTH
 STUCCO OVER PAPERBACK METAL LATH. THE
 WEIGHT OF THE EXPANDED METAL LATH HASN'T
 BEEN PROVIDED, NOR THE TYPE OF FASTENERS
 NOR THE LENGTH OF THE FASTENERS. SEE
 ASTM C-1063.
  
 20F) PLANS DO NOT PROVIDE WHAT TYPE OF
 FASTENER WILL BE USED TO HOLD THE STEEL
 PLATES TO THE WALL FOR THE STUCCO
 CEILING.
  
 20G) THE PORTACO ROOF SECTION DOES ALSO
 INDICATE THE USE OF 3/4" PLYWOOD. NO
 MENTION OF FIRE RETARDANT TREATED
 PLYWOOD.SEE TABLE 601 NOTE3, ITEM 3.
 NOTE THE PRODUCT APPROVAL FOR THE ROOF
 WILL NEED TO MATCH THE MATERIALS FOR THE
 ROOFING DECK.
  
 21) A8.1.5 BED BATH & BEYOND PORTACO
 INDICATES 2 SECTIONS ONE DETAIL# 3/
 A8.1.5 THE OTHER IS DETAIL# 7/ A8.3
  
 21A) DETAIL3/ A8.1.5 IS A CUT SECTION OF
 THE PORTICO'S NORTH/ SOUTH WALLS
 INDICATING 2X6 STEEL STUD CONSTRUCTION.
  
  
 21B) THE FRONT AND END DETAILS
 (EAST-WEST WALLS) ARE MISLABELED.IF
 DETAILS 2 & 3 OF A8.3 ARE USED THE
 CORRECT CORNICE PROJECTION IS VIEWED,
 BUT THE DETAILS INDICATE BLOCK
 CONSTRUCTION NOT STEEL STUD.
  
 21C) IF STEEL STUDS ARE TO BE USED FOR
 EITHER WALL OR ROOF FRAMING PROVIDE THE
 GAUGE OF STUD, FLANGE WIDTH AND STYLE OF
  
 PRODUCT TO BE USED.
  
 22) A8.1.6 COMP USA PORTACO INDICATES BY
 ELEVATION 25'-10 START OF NEW WORK BUT
 CROSS HATCHING SHOWING NEW WORK IS AT A
 LOWER LEVEL? PROVIDE ADDITIONAL
 INFORMATION. 106.1.2*.
  
 23) SHEET A8.2 DETAIL# 1 INDICATES USE
 OF 3/4" EXTERIOR GRADE PRESSURE TREATED
 PLYWOOD NO MENTION OF FIRE RETARDANT
 TREATED PLYWOOD.TABLE 601,
 FOOTNOTE(C)(2)
  
 24) A8.2 SAME DETAIL# 1 INDICATES THE
 USE OF EXPANDED WIRE MESH AND STUCCO, NO
 MENTION OF PAPERBACK MESH, TYPE OF MESH,
 WEIGHT OF MESH NOR SPACING OF FURRING
 ABOVE? SEE ASTM C-1063.
  
 25) A8.4 EXIT PASSAGEWAY DETAIL:
  
 25A) DISCREPANCY THE ACTUAL DETAIL
 INDICATES USE OF 3 5/8" STEEL STUDS
 SPANING A HEIGHT OF 25'-4" NO CENTERS
 WHEREAS THE 1 HR RATED UL-U465 DETAIL
 INDICATES 5 5/8" STEEL STUDS AT 24" O.C.
 NO HEIGHT LIMITATION IS PROVIDED.
  
 25B) TABLE 2508.1 PROVIDES THE STANDARD
 FOR NON-LOAD BEARING WALLS WITH GYPSUM
 BOARD APPLICATION ASTM C-754. SEE
 5.3.1.2 STUD HEIGHTS SHALL BE BASED ON
 DESIGN CRITERIAOF A MINIMUM 5 PSF LOAD
 AND A MINIMUM OF L/120 DEFLECTION.
 APPENDIX A PROVIDES THE LIMITATIONS ON A
  
 3 5/8" STUD @ 24" O.C., L/120 AND A 5
 PSF:MAXIMUM HEIGTH OF 11'-7".
 THIS TABLE ONLY GOES TO A 4" STUD
 WIDTH.
 USING THE ICC - ICBO ER REPORT 4943
 THERE ARE NO TABLES FOR A 5 5/8" STEEL
 STUD , THERE ARE TABLE FOR 6" STUDS.
 USING THE DEFLECTION L/120, 5PSF @ 24" O.C.THICKNESS OF
 27 WHICH IS 22 GAUGE
 THE MAXIMUM HEIGHT IS 21'-11",
 USINGTHE SAME CRITERIA 6" STUD,
 L/120,5PSF, @ 16" O.C. THICKNESS27/ 22
 GAUGE , THE MAXIMUM HEIGTH OF 26'-10".
 USING THE SAME CRITERIA AND
 CHANGING THE CENTERS TO 12" O.C. THE
 MAXIMUM STUD HEIGHT OF 31'-0".
 PLEASE CORRECT PLANS.
  
 26) A10.2 PLANS INDICATE THE USE OF
 STANDING SEAM METAL ROOFING ON VAARIOUS
 CURVED CANOPIES.
  
 26A) ON DETAILS 5&9 WHERE THE CANOPY HAS
 A CONCAVE CURVE, AT THE BOTTOM OF THE
 CURVE, RAIN WATER WILL BUILD UP UNDER
 THE STANDING SEAM, WHAT STOPS THE WATER
 FROM LEAKING THROUGH? THERE IS NO DRAIN
 IN EACH BAY? ADITIONAL INFORMATION REQUIRED.106.1.2*
  
 26B) ON THE CONCAVE SIDE OF THE CANCOPY
 WHAT STOPS THE STANDING METAL SEAM FROM
  
 WRAPPING? ADDITIONAL INFORMATION REQUIRED.106.1.2*.
  
 26C) PLANS INDICATE THE USSE OF 3/4"
 PLYWOOD NO MENTION OF FIRE RETARDANT
 TREATED WOOD DECK, TABLE 601 FOOTNOTE
 (C)(2).
  
 26D)PLANS INDICATE THE USE OF FOAM
 BANDS, SEE A8.1.6 COMP USA HEIGHT OF 45'-0",S-3ALSO
 SHOWS A HEIGHT OF 43'-8".
 NO FOAM ABOVE 40'-0".
 1406.2.2 ARCHITECTURAL TRIM.
 IN BUILDINGS OF TYPE I, II, III AND IV CONSTRUCTION
 THAT DO NOT EXCEED THREE
 STORIES OR 40 FEET (12 192 MM) IN HEIGHT
 ABOVE GRADE PLANE, EXTERIOR WALL
 COVERINGS SHALL BE PERMITTED TO BE
 CONSTRUCTED OF WOOD WHERE PERMITTED BY
 SECTION 1405.4 OR OTHER EQUIVALENT
 COMBUSTIBLE MATERIAL. COMBUSTIBLE
 EXTERIOR WALL COVERINGS, OTHER THAN
 FIRE-RETARDANT-TREATED WOOD COMPLYING
 WITH SECTION 2303.2 FOR EXTERIOR
 INSTALLATION, SHALL NOT EXCEED 10
 PERCENT OF AN EXTERIOR WALL SURFACE AREA
 WHERE THE FIRE SEPARATION DISTANCE IS 5
 FEET (1524 MM) OR LESS. ARCHITECTURAL
 TRIM THAT EXCEEDS 40 FEET (12 192 MM) IN
 HEIGHT ABOVE GRADE PLANE SHALL BE
 CONSTRUCTED OF APPROVED NONCOMBUSTIBLE
 MATERIALS AND SHALL BE SECURED TO THE
 WALL WITH METAL OR OTHER APPROVED
 NONCOMBUSTIBLE BRACKETS.
  
 27) S3 DETAIL# 3 PLANS INDICATE THE TIE
 IN OF NEW STEEL STUD WALL OVER THE TOP
 OF EXISTING BLOCK WALL. IT APPEARS THAT
 NOT ONLY A STEEL BOTTOM PLATE BUT A 2X
 PLATE IS ALSO INSTALLED. IS THIS PLATE
 SEGMENTED BETWEEN THE STUDS? THE SECOND
 ISSUE IS THE PLANS INDICATE THAT THE
 TAPCON TO BE USED IS A 1/4"X2 1/2" ONLY
 PROVIDING NOT MORE THAN ONE INCH INTO
 THE CONCRETE, WHICH SHEET OF
 CALCULATIONS PROVIDES THIS INFORMATION?
  
 28) BEFORE A PERMIT TO CONSTRUCT, MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 BUILDING PLAN REVIEW