| Date |
Text |
| 2006-08-27 00:00:00 | **** 3RD REVIEW *** |
| | |
| | 1) NOTE: PLEASE SEE MISSING PANEL |
| | SCHEDULE FOR NEW POOL PANEL SHOWING THE |
| | OCP FOR EACH OF THE NEW BRANCH CIRCUITS |
| | ON RISER/WIRING DIAGRAM SUBMITTED. |
| | 408.4,310.16,240.4 |
| | FBC 106.1.2 |
| | |
| | 2) NOTE: PLEASE SEE PLANS ARE STILL |
| | MISSING THE REQUIRED LICENSURE |
| | INFORMATION REQUIRED PER FS 471.023, AND |
| | FAC 61G15-23.002 |
| | PLEASE KNOW, THIS COMMENT IS NOT FOR THE |
| | LICENSE NUMBER OF THE PE. THIS IS FOR |
| | THE FIRM AS LISTED ON TITLE BLOCK. |
| | THIS OFFICE HAS LEFT MESSAGES FOR THE |
| | RETURNED CALLS FROM THE ENGINEERING FIRM |
| | WITH RESPECT TO THIS COMMENT. |
| | PLEASE CONTACT THE FLORIDA BOARD OF |
| | PROFESSIONAL ENGINEERS AND DEPARTMENT OF |
| | BUSINESS AND PROFESSIONLA REGULATION IF |
| | THERE ARE ANY FURTHER QUESTIONS. |
| | ** PLEASE ALSO SEE NEW SIGNED PLANS ARE |
| | DATED AS THE PREVIOUS PLANS WHICH WERE |
| | DATED ON 7/5/06, HOW IS THE DATE THE |
| | SAME WHEN THE PLANS HAVE BEEN REVISED. |
| | PLEASE SEE FS 471.025 AND FAC AS NOED |
| | ABOVE AS THE ENGINEER OF RECORD IS |
| | REQUIRED TO DATE THE PLANS EACH TIME |
| | THEY ARE BEING SIGNED/REVISED. |
| | PLEASE KNOW, TWO SETS OF PLANS, ONE |
| | ORIGINAL AND ONE REVISED IS BEING |
| | RETAINED BY THIS OFFICE FOR POSSIBLE |
| | REVIEW FROM THE FBPE'S AND LEGAL COUNSEL |
| | TO THE BOARD. |
| | |
| | |
| | ** PLEASE SUBMIT TWO COMPLETE SETS OF |
| | REVISED PLANS, PLEASE BE SURE TO ADDRESS |
| | ALL COMMENTS ABOVE. |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |
| | |