Plan Review Notes
Plan Review Notes For Permit 06070443
Permit Number 06070443
Review Stop E
Sequence Number 2
Notes
Date Text
2006-08-11 00:00:00********* UNSAT2ND REVIEW ***********
  
  
 ** PLEASE SEE SOME NOTE FROM PREVIOUS
 RENIEW WHICH STILL NEED TO BE ADDRESS.
 NOTES BELOW ARE TAKEN DIRECTLY FROM THE
 PERVIOUS REVIEW.
  
 ** PLEASE KNOW, PLANS SHALL BE SPECIFIC
 TO EACH SITE AND DESIGN.
  
 1) NOTE: NO, NOTHING SUBMITTED , SAME
 COMMENT APPLIES.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SUBMIT COMPLETE LOAD
 CALCULATIONS FOR ALL EXISTING LOADS AND
 NEW LOADS ADDED.
 PLEASE INDICATE THE SIZE OF THE EXISTING
 SERVICE.
 220.31B,215.5, FBC ADMIN SECT 106.1.2
  
 2) NOTE: NO, SAME COMMENT. RISER AND
 CALCULATIONS SUBMNITTED ARE NOT FROM THE
 NEC/NFPA-70. PLEASE SEE 2002 NEC FOR
 LOAD CALCULATIONS ETC
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE PLANS INDICATE A NEW
 PANEL, HOWEVER NO INFORMATION ON FEEDERS
 AND OCP FROM SERVICE PANEL.
 240.4,310.16,215.5 ETC
  
 3) NOTE: NO, SAME NOTE. RISER /CALCS
 SUBMITTED ARE NOT DONE TOMIN STANDARDS
 FROM THE NEC. 2002 220
 PLEASE SEE NEW NOTES ALSO.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE PROVIDE A PANEL SCHEDULE
 FOR THE NEW PROPOSED PANEL SHOWING ALL
 CONDUCTOR SIZES, OCP, ETC.
 408.4,106.1.2, 106.3.5.1.2
  
 4) NOTE: NO. PLEASE SEE HAND DRAWN
 CHNAGES MADE TO PLASN WHICH ARE SIGNED,
 DATED AND SEALED BY AND ENGINEER IS NOT
 PERMITTED UNDER FLORIDA STATUES 471.025,
 FLORIDA ADMINSITRATIVE CODE 61G15-23.002
 PLEASE ADDRESS COMMENT ON COMPELTE NEW
 SHEETS, AS THE PLANS SUBMITTED HAVE BEEN
 "VOIDED" INCLUDING SHEETS STAMPED BY THE
 PLUMBING REVIEWER.
  
 **PREVIOUS REVIEW NOTE **
 PLEASE SEE WIRING DIAGRAM DOES
 NOT INCLUDE THE HEAT PUMP? WIRE SIZES?
 CONDUIT? ETC.
 PLEASE COMPLETE WIRING DIAGRAM.
 106.1.2
  
 5) NOTE: NO, VALUE WAS SHOWN ON
 APPLICATION TO $22K, HOWEVER VALUE STILL
 SEEMS LOW, AN ADJUSTMENT MAY BE DONE PER
 MARSHALL'S & SWIFT GUIDE FOR FAIR MARKET
 VALUE.
 PLEASE PROVIDE A SIGNED CONTRACT FOR ALL
 SCOPE OF WORK INCLUDED ON APPLICATION.
 FBC 108.3
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE KNOW, VALUE ON PERMIT
 APPLICATION IS VERY LOW FOR A POOL OF
 THIS SIZE. PLEASE ADJUST VALUE OR PLEASE
 KNOW ONE WILL BE ASSESSED BY THIS OFFICE
 BASED ON THE "MARSHALL'S / SWIFT" GUIDE
 AS ADOPTED INTO THE FBC PER 108.3
  
 ** WHEN REQ'D**
 6) NOTE: PLEASE SEE FAC 61G17 AND FS
 421.025, PLEASE SEE THAT THE SURVEY
 SHALL CONTAIN THE RAISED SEAL AND THE
 ORIGINAL SIGNATURE AND DATE.
  
 ** NEW NOTES **
  
 7) NOTE: PLEASE SEE MISSING INFORMATION
 ON TITLE BLOCKS AS REQUIRED UNDER FAC
 61G15-23.002 AND FS 471.023.
 THIS COMMENT WAS NOT MADE ON PREVIOUS
 REVIEW , HOWEVER IS REQUIRED.
 A)MISSING THE PRINTED NAME AND LICENSE #
 OF SAID ENGINEER.
 B)MISSING THE CERTIFICATE OF
 AUTHORIZATION NUMBER FOR FIRM AS LISTED.
  
 8) NOTE: PLEASE SEE FS 553.80(2)(B) WITH
 RESPECT TO DESIGN PROFESSIONALS AND
 REPEAT CODE COMPLIANCE COMMENTS.
 THIS IS ONLY A NOTICE GIVEN AT THIS
 TIME.
  
 9) NOTE: PLEASE KNOW, ANY ADDTIONAL
 INFORMATION SUCH AS LOAD CALCULATIONS ,
 ETC WHEN NOT DONE BY THE ENGINEER OF
 RECORD, MUST CONTAIN THE PRINTED NAME
 AND SIGNATURE OF THE PERSON RESPONSIBLE
 FOR SAID PLANS. FCB 106.1.2
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  