Plan Review Notes
Plan Review Notes For Permit 06070443
Permit Number 06070443
Review Stop E
Sequence Number 1
Notes
Date Text
2006-07-20 00:00:00********* UNSAT ***********
  
 ** PLEASE KNOW, PLANS SHALL BE SPECIFIC
 TO EACH SITE AND DESIGN.
  
 1) NOTE: PLEASE SUBMIT COMPLETE LOAD
 CALCULATIONS FOR ALL EXISTING LOADS AND
 NEW LOADS ADDED.
 PLEASE INDICATE THE SIZE OF THE EXISTING
 SERVICE.
 220.31B,215.5, FBC ADMIN SECT 106.1.2
  
 2) NOTE: PLEASE SEE PLANS INDICATE A NEW
 PANEL, HOWEVER NO INFORMATION ON FEEDERS
 AND OCP FROM SERVICE PANEL.
 240.4,310.16,215.5 ETC
  
 3) NOTE: PLEASE PROVIDE A PANEL SCHEDULE
 FOR THE NEW PROPOSED PANEL SHWOING ALL
 CONDUCTOR SIZES, OCP, ETC.
 408.4,106.1.2, 106.3.5.1.2
  
 4) NOTE: PLEASE SEE WIRING DIAGRAM DOES
 NOT INCLUDE THE HEAT PUMP? WIRE SIZES?
 CONDUIT? ETC.
 PLEASE COMPLETE WIRING DIAGRAM.
 106.1.2
  
 5) NOTE: PLEASE KNOW, VALUE ON PERMIT
 APPLICATION IS VERY LOW FOR A POOL OF
 THIS SIZE. PLEASE ADJUST VVALUE OR PLEAS
 KNOW ONE WILL BE ASSESSED BY THIS OFFICE
 BASED ON THE "MARSHALL'S / SWIFT" GUIDE
 AS ADOPTED INTO THE FBC PER 108.3
  
 ** WHEN REQ'D**
 6) NOTE: PLEASE SEE FAC 61G17 AND FS
 421.025, PLEASE SEE THAT THE SURVEY
 SHALL CONTAIN THE RAISED SEAL AND THE
 ORIGINAL SIGNATURE AND DATE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  