| Date |
Text |
| 2006-12-07 08:41:09 | DENIED 4TH TIME |
| | REFERENCE: FBC-2004 FUEL GAS |
| | |
| | THE FOLLOWING CORRECTIONS ARE STILL REQUIRED FOR GAS |
| | PLAN REVIEW FROMPERVIOUS GAS PLAN REVIEW COMMENTS |
| | DATED 7/26/06, 9/12/06 AND11/06/06. |
| | A PERMIT FOR THE GENERATOR CAN NOT BE ISSUED UNTIL THE |
| | FOLLOWING CORRECTIONS ARE MADE TO MEET CODE |
| | COMPLIANCE. |
| | |
| | 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. |
| | NOTE: THE RESUBMITTED DRAWINGS STILL ONLY INDICATES THE |
| | MEASUREMENTS OF THE UNDERGROUND PE PIPING. RECORDS |
| | INDICATE EXISTING GAS AT SAID ADDRESS PLEASE INDICATE |
| | THE EXISTING GAS ON RESUBMITTED DRAWING.PLEASE |
| | REFERENCE THE ATTACHED PERMIT INFORMATION INDICATING |
| | GAS AT SAID ADDRESS. PLEASE INDICATE THE CUT SECTION |
| | MEASUREMENTS OF ALL PIPING, UNDERGROUND, ABOVE GROUND |
| | AND EXISTING. |
| | |
| | 2. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE BEING USED. |
| | NOTE: THE RESUBMITTED DRAWINGS STILL ONLY INDICATES THE |
| | UNDERGROUND PIPING MATERIAL AND SIZE. WHAT IS THE SIZE |
| | AND MATERIAL TYPE OF THE ABOVE GROUND AND EXISTING |
| | PIPING. |
| | |
| | 3. (OK) |
| | |
| | 4. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.6.1 AND TABLES 402.4(1) THRU |
| | 402.4(33). |
| | NOTE: RECORDS INDICATE EXISTING GAS TO A 40 GAL. NAT. |
| | GAS WATER HEATER. THE BTU LOAD TO THAT WATER HEATER |
| | MUST BE INDICATED ON THE DRAWING. THE BTU LOAD OF |
| | 343,000 INDICATED FOR THE GENERATOR ON THE RESUBMITTED |
| | GAS ISOMETRIC IS STILL WRONG. THE CORRECT BTU LOAD IS |
| | 437,000 PER THE SUBMITTED GENERATOR MANUFACTURE CUT |
| | SHEETS. PLEASE CORRECT THIS ON THE RESUBMITTAL. |
| | |
| | 5. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). |
| | NOTE: THE EXISTING GAS SYSTEM NEEDS TO BE INDICATED ON |
| | THE RESUBMITTED DRAWINGS WITH ITS MEASUREMENTS. |
| | |
| | 6. (OK) |
| | |
| | 7. (OK) |
| | |
| | 8. (OK) |
| | |
| | **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| | PLEASE REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED AND PROVIDE ONE COPY |
| | OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| | ONLY. NOTE: ONLY ONE CORRECTED DRAWING |
| | IN RED INK FOR REFERENCE FOR |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |