| 2006-11-01 16:37:21 | ** UNSAT 3RD REVIEW ** |
| | |
| | ** PLEASE SEE THE RISER DIAGRAM HAS NOW BEEN REVISED |
| | WHICH HAS CREATED SOME NEW COMMENTS. |
| | |
| | 1) NOTE: PLEASE SEE RISER IS NOW SHOWING AND "EQUIPMENT |
| | GROUNDING CONDUCTOR" FROM THE METER TO THE FIRST MEANS |
| | OF DISCONNECT WHICH IS NOT PERMITTED. |
| | PLEASE SEE 250.6, 250.24B. |
| | |
| | 2) NOTE: PLEASE SEE NOW A NEW GROUNDING ELECTRODE POINT |
| | IS BEING SHOWN, HOWEVER NOW SIZE OF GEC OR SYSTEM |
| | REQUIRED PER 250.50 IS BEING SHOWN>??? |
| | |
| | 3) NOTE: PLEASE SEE RISER SHOWS WHAT IS TO BE A "RTSE" |
| | , PLEASE SUBMIT THE CORRESPONDING MANUFACTURES SPEC/CUT |
| | SHEET FOR THE RTSE. |
| | |
| | 4) NOTE: PLEASE BE SURE ALL SHEETS CONTAIN THE PRINTED |
| | NAME AND SIGNATUREOF THE PERSON RESPONSIBLE FOR |
| | DESIGN/PLANS ETC. (PLEASE SEE LOAD CALCULATIONS). |
| | FBC 106.1.2 |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |