Plan Review Notes
Plan Review Notes For Permit 06070422
Permit Number 06070422
Review Stop E
Sequence Number 5
Notes
Date Text
2007-10-27 12:19:37** DENIED REVISION **
  
 ** PLEASE SEE NOTES FROM PREVIOUS *PROVISO* ARE STILL
 IN NEED OF ADDRESSING. PLEASE ALSO SEE THERE ARE NEW
 NOTES AS PLANS HAVE BEEN REVISED WITH SOME ITEMS WHICH
 ARE NOT CODE COMPLIANT.
  
 1) NOTE: PLEASE SEE THE SMOKE ALARMS WHICH WERE TO BE
 CORRECTED TO THE EXISTING DWELLING AS WELL WAS NOT
 SUBMITTED.
 PLEASE SEE FBC R313, NFPA-72 11.5.1.1
  
 2) NOTE: PLEASE SEE THE WATER DISCONNECT IS NOW
 MISSING.
 422.31.
  
 3) NOTE: PLEASE SEE THE ELECTRICAL PANEL IS NOW BEING
 SHOWN IN THE CLOSET ARE WITH THE WASHER AND DRYER AND
 ALSO DOES NOT MEET 110.26 FOR MINIMUM WORKING
 CLEARANCES PER 110.26.
 PLEASE ALSO SEE 240.24D, AND 408.7
 PANEL IS TO BE RELOCATED.
  
 4) NOTE: PLEASE SEE THE PANEL SCHEDULE WAS NOT
 COMPLETELY REVISED INDICATING ALL NEW CIRCUITS. PLEASE
 SEE SOME BRANCH CIRCUITS FOR LIGHTING AND RECEPTACLES
 HOWEVER WASHER, DRYER ETC IS THE SAME.
 PLEASE SEE IN FACT WASHER CIRCUIT IS MISSING FROM THE
 PANEL SCHEDULE.
 PLEASE ALSO SEE SMALL APPLIANCE CIRCUIT #32 FOR BRKFST
 ROOM IS SHOWN ON LIGHTING CIRCUIT FOR COVERED PATIO. IF
 EXISTING OK, IF NEW THIS DOES NOT MEET 210.52B1,
 210.11C1, 220.16
 PLEASE ADJUST PANEL SCHEDULE AS NEEDED. 408.4, 310.16,
 240.4 ETC
 FBC 106.3.5.4
  
 5) NOTE: PLEASE ONLY SUBMIT ELECTRICAL PLANS WHICH ARE
 BEING REVISED. PLEASE SEE THE TITLE BLOCKS OF PLANS DO
 NOT INDICATE THE REVISIONS, CLOUDS AND TRIANGLES WITH
 DATES.
 PLEASE SEE THE SHEETS CONTAIN ALL OTHER TRADES WHEN
 ONLY ELECTRICAL IS NEEDED.
 FBC 106.3.1
  
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  