| 2007-10-27 12:19:37 | ** DENIED REVISION ** |
| | |
| | ** PLEASE SEE NOTES FROM PREVIOUS *PROVISO* ARE STILL |
| | IN NEED OF ADDRESSING. PLEASE ALSO SEE THERE ARE NEW |
| | NOTES AS PLANS HAVE BEEN REVISED WITH SOME ITEMS WHICH |
| | ARE NOT CODE COMPLIANT. |
| | |
| | 1) NOTE: PLEASE SEE THE SMOKE ALARMS WHICH WERE TO BE |
| | CORRECTED TO THE EXISTING DWELLING AS WELL WAS NOT |
| | SUBMITTED. |
| | PLEASE SEE FBC R313, NFPA-72 11.5.1.1 |
| | |
| | 2) NOTE: PLEASE SEE THE WATER DISCONNECT IS NOW |
| | MISSING. |
| | 422.31. |
| | |
| | 3) NOTE: PLEASE SEE THE ELECTRICAL PANEL IS NOW BEING |
| | SHOWN IN THE CLOSET ARE WITH THE WASHER AND DRYER AND |
| | ALSO DOES NOT MEET 110.26 FOR MINIMUM WORKING |
| | CLEARANCES PER 110.26. |
| | PLEASE ALSO SEE 240.24D, AND 408.7 |
| | PANEL IS TO BE RELOCATED. |
| | |
| | 4) NOTE: PLEASE SEE THE PANEL SCHEDULE WAS NOT |
| | COMPLETELY REVISED INDICATING ALL NEW CIRCUITS. PLEASE |
| | SEE SOME BRANCH CIRCUITS FOR LIGHTING AND RECEPTACLES |
| | HOWEVER WASHER, DRYER ETC IS THE SAME. |
| | PLEASE SEE IN FACT WASHER CIRCUIT IS MISSING FROM THE |
| | PANEL SCHEDULE. |
| | PLEASE ALSO SEE SMALL APPLIANCE CIRCUIT #32 FOR BRKFST |
| | ROOM IS SHOWN ON LIGHTING CIRCUIT FOR COVERED PATIO. IF |
| | EXISTING OK, IF NEW THIS DOES NOT MEET 210.52B1, |
| | 210.11C1, 220.16 |
| | PLEASE ADJUST PANEL SCHEDULE AS NEEDED. 408.4, 310.16, |
| | 240.4 ETC |
| | FBC 106.3.5.4 |
| | |
| | 5) NOTE: PLEASE ONLY SUBMIT ELECTRICAL PLANS WHICH ARE |
| | BEING REVISED. PLEASE SEE THE TITLE BLOCKS OF PLANS DO |
| | NOT INDICATE THE REVISIONS, CLOUDS AND TRIANGLES WITH |
| | DATES. |
| | PLEASE SEE THE SHEETS CONTAIN ALL OTHER TRADES WHEN |
| | ONLY ELECTRICAL IS NEEDED. |
| | FBC 106.3.1 |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS, PLEASE CALL. |
| | |