Plan Review Notes
Plan Review Notes For Permit 06070422
Permit Number 06070422
Review Stop E
Sequence Number 4
Notes
Date Text
2007-07-12 09:55:57*** PROVISO ***
  
 1) NOTE: PLEASE SEE PANEL SCHEDULE SHOWS ALL CIRCUITS
 AS NEW. PLEASE REVISE TO INDICATE WHICH ARE NEW AND
 WHICH ARE EXISTING?
 408.4
  
 2) NOTE: PLEASE SEE THE SMOKE DEVICES AS INDICATE FOR
 NEW AND EXISTING DWELLING SHOULD BE INDICATED AS SA FOR
 SMOKE ALARMS.
 PLEASE SEE NFPA-72 DEFINITIONS AND 11.5.1.1.1
  
 3) NOTE: PLEASE SEE ONE OR MORE OF THE SMALL APPLIANCE
 CIRCUITS SHALL BE SHOWN AND FIGURED AT 1500 VA FOR
 EACH. ONLY TWO ARE SHOWN ON LOAD CALCULATIONSYET
 THREE ARE SHOWN ON PANEL SCHEDULE.
 210.52B1, 220.16
  
 ** PLEASE REVISED THE ABOVE INFORMATION ON AN
 ELECTRICAL PLAN/SHEET AND SUBMIT WITH ANY OTHER
 POSSIBLE REVISIONS BEFORE ROUGH ELECTRICAL INSPECTION.
 THE REVISED PLANS MUST BE ON-SITE FOR ROUGH ELECTRICAL
 INSPECTION.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  