Plan Review Notes
Plan Review Notes For Permit 06070422
Permit Number 06070422
Review Stop E
Sequence Number 3
Notes
Date Text
2006-11-30 07:43:58*** UNSAT ***
  
 *** PLEASE SEE NOTES FROM PREVIOUS REVIEWS WHICH STILL
 NEED TO BE ADDRESSED.
  
  
 1) NOTE: PLEASE SEE NO PANEL SCHEDULE WAS SUBMITTED FOR
 CIRCUITING AS REQUESTED ON BOTH PREVIOUS REVIEWS. THIS
 WOULD INDICATE THE CIRCUITS (NEW) AND EXISTING, THE
 BRANCH CIRCUIT , ALONG WITH THE OVER CURRENT PROTECTION
 AND CONDUCTOR SIZES.
 310.16,240.4,408.4 ETC
 FBC 106.1.2, 106.3.5.4 ADMIN SECTION.
  
  
 2) NOTE: PLEASE SEE NOW LOAD CALCULATIONS ARE BEING
 SUBMITTED FOR THE FIRST TIME FOR REVIEW. PLEASE SEE
 THESE NOTE VERIFY A 200A SERVICE, YET THE RISER SHOWS
 AN EXISTING 150A SERVICE? WHICH IS IT?
 PLEASE ALSO SEE THERE ARE 2/0?S BEING SHOWN FROM RISER
 TO MAIN PANEL.(EXISTING)??
 PLEASE KNOW THIS IS THE RESPONSIBILITY OF THE DESIGNER
 OF RECORD TO OBTAIN THIS INFORMATION AND PLACE THIS
 INFORMATION ON PLANS ACCURATELY.
 FBC 106.1.2 ADMIN SECTION.
 NEC 230.70, 310.16, 240.4 ETC.
  
 4) NOTE: PLEASE KNOW AS NOTED ON PREVIOUS2ND REVIEW
 WITH RESPECT TO REPEAT CODE COMPLIANT COMMENTS TO THE
 DESIGN PROFESSIONAL, A FEE OF $312.00 BASED ON 4X THE
 FEE FOR THE PORTION THE FEE ATTRIBUTED TO PLAN REVIEW
 HAS BEEN ASSESSED AS REQUIRED UNDER FS 553.80(2)(B).
 THIS FEE SHALL BE PAID BEFORE NEXT RESUBMISSION OF
 PLANS.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
 ** TO DATE NO CONTACT HAS BEEN MADE TO THIS OFFICE TO
 GO OVER SAID COMMENTS OR ANY QUESTIONS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]