| 2006-10-01 00:00:00 | *****UNSAT 2ND REVIEW ******** |
| | |
| | ** PLEASE SEE NOTES FROM PREVIOUS REVIEW |
| | WHICH STILL NEED TO BE ADDRESSED AND |
| | PLEASE SEE NEW COMMENTS BASED ON PLANS |
| | AND SPECS SUBMITTED. |
| | PLEASE SEE NOTES BELOW ARE TAKEN |
| | DIRECTLY FROM PREVIOUS REVIEW. |
| | |
| | 1) NOTE: NO, LOAD CALCULATIONS |
| | SUBMITTED, DO NOT CORRELATE WITH ANY |
| | CALCULATIONS BASED FROM THE NFPA-70 OR |
| | IS PERMITTED IN THE NEC. |
| | ** PLEASE SEE 220.312B AND COMPLETE. |
| | PLEASE SEE THERE IS A MAJOR LOAD BEING |
| | ADDED, HOWEVER THERE HAS BEEN NOT |
| | CONSIDERATION FOR THIS. PLEASE SEE SPECS |
| | FOR TANKLESS WATER HEATER SUBMITTED |
| | WHICH "HIGH-LIGHTS" A 28KW UNIT!!!! THIS |
| | UNITS ALONE PULLS 116A'S. |
| | PLEASE SEE THE LOAD ON THIS UNIT ALONE |
| | AND THE MIN LOADS ON THE EXISTING |
| | DWELLING FAR EXCEED THE RATING OF THE |
| | EXISTING DWELLING'S SERVICE. |
| | PLEASE OBTAIN A QUALIFIED PERSON WHO HAS |
| | ELECTRICAL BACKGROUND TO THESE AS THIS |
| | IS LIFE SAFETY AND FIREHAZARD AND DUE |
| | TO WHAT IS BEING SUBMITTED. |
| | PLEASE SEE NO INFORMATION AND LCOATION |
| | OF UNIT AT THIS TIME IS "NOT" PERMITTED. |
| | ** PLEASE ALSO SEE THERE IS NO NRTL( |
| | NATIONALLY RECOGNIZED TESTING |
| | LABORATORY) SHOWN ON SPECS. PLEASE ALSO |
| | SUBMIT TWO COPIES. |
| | PLEASE SEE NO NEW REVISED PANEL SCHEDULE |
| | WAS SUBMITTED EITHER TO VERIFY THE NEW |
| | CIRCUITS, CONDUCTORS, OCP, LOADS ETC. |
| | 110.3,240.24,110.26,90.7,220.31B, 408.4, |
| | 240.4, 310.16 ETC. |
| | |
| | ** PREVIOUS REVIEW NOTE** |
| | PLEASE SUBMIT COMPLETE LOAD |
| | CALCULATIONS SHOWING ALL EXISTING AND |
| | NEW LOADS. |
| | INDICATE THE SIZE OF THE NEW TANKLESS |
| | WH. PLEASE SEE MANUFACTURES SPECS / CUT |
| | SHEETS FOR MIN CLEARENCES AND LOCATION. |
| | PLEASE SEE CLARIFY WHERE THE MEANS OF |
| | DISCONNECT IS? |
| | PLEASE SEE LOCATION BEING PRIMARILY |
| | STORAGE UNDER LAV AND LOCATION DUE TO |
| | EASILY IGNITIBLE MATERIALS. |
| | PLEASE SUBMIT THE MANUFACTURES SPECS/ |
| | CUT SHEETS FOR THE PROPOSED UNIT. |
| | PLEASE SEE 110.26,422.31,110.3,240.24, |
| | 220.31, 408.4 ETC. |
| | |
| | 2) NOTE: OK. |
| | |
| | 3) NOTE:NO, SAME NOTE, NOTHING SHOWN |
| | OR SUBMITTED. |
| | |
| | ** PREVIOUS REVIEW NOTE **PLEASE SEE |
| | 2004 R313 AS SD'S |
| | ARE REQUIRED INSIDE AND OUTSIDE ALL |
| | EXISTING SLEEPING RMS. PLEASE SEE |
| | NFPA-72 11.5.1.1,11.8.3. |
| | PLEASE SHOW A BASIC LAYOUT OF THE |
| | EXISTING DWELLING AND THE LOCATION OF |
| | THE SD'S. |
| | |
| | 4) NOTE: NO, NOT CLEAR A NEW LOCATION |
| | SEEMS TO BE SHOWN BASED ON SYMBOL OF |
| | WHAT THE WASHER AND DRYER SHOULD BE, |
| | HOWEVER NOTHING IDENTIFING NEW |
| | EQUIPMENT. PLEASE SEE IF NEW STACKABLE |
| | UNIT, PLEASE SHOW, AND PLEASE INDICATE |
| | IN NEW LOADS/PANEL SCHEDULE. |
| | 220.16, 210.11C2, 220.18 |
| | |
| | ** PREVIOUS REVIEW NOTE** |
| | PLEASE SEE PERMIT APPLICATION |
| | MENTIONS CONVERTING EXISTING LAUNDRY RM |
| | TO BATHRM, HOWEVER NEW LANUDRY AREA CAN |
| | NOT BE LOCATED. PLEASE SEE MIN HOUSING |
| | CODE FOR LAUNDRY FACILIES AND PLEASE SEE |
| | NEC FOR MIN LAUNDRY CIRCUITS. |
| | 210.11C2, 220.16 |
| | |
| | |
| | ** NEW NOTE ** |
| | |
| | 1) NOTE: PLEASE SEE ONE SET OF PLANS |
| | HAVE BEEN RETAINED BY THIS OFFICE AND |
| | WILL BE PLACED IN FILE WITH ALL OTHER |
| | PROJECTS REPEATLY BEING SUBMITTED, |
| | SIGNED , DATED AND SEALED BY THIS DESIGN |
| | PROFESSSIONAL.PLEASE SEE NOTICE TO FS |
| | 553.80(2)(B) WITH RESPECT TO REPEAT |
| | COMMENTS FOR PLAN REVIEW IS NOW GIVEN AS |
| | NOTICE. |
| | PLEASE ALSO SEE FS 471.025(3) QUOTED, |
| | "NO LICENSEE SHALL AFFIX OR PERMIT TO |
| | BE AFFIXED HIS OR HER SEAL, NAME, OR |
| | DIGITAL SIGNATURE TO ANY PLAN, |
| | SPECIFICATION, DRAWING, FINAL BID |
| | DOCUMENT, OR OTHER DOCUMENT THAT DEPICTS |
| | WORK WHICH HE OR SHE IS NOT LICENSED TO |
| | PERFORM OR WHICH IS BEYOND HIS OR HER |
| | PROFESSION OR SPECIALTY THEREIN." |
| | THIS IS TAKEN DIRECTLY FROM THE TEXT OUT |
| | OF THE FLORIDA STATUES. |
| | |
| | |
| | |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |