Date Text
2006-10-01 00:00:00*****UNSAT 2ND REVIEW ********
  
 ** PLEASE SEE NOTES FROM PREVIOUS REVIEW
 WHICH STILL NEED TO BE ADDRESSED AND
 PLEASE SEE NEW COMMENTS BASED ON PLANS
 AND SPECS SUBMITTED.
 PLEASE SEE NOTES BELOW ARE TAKEN
 DIRECTLY FROM PREVIOUS REVIEW.
  
 1) NOTE: NO, LOAD CALCULATIONS
 SUBMITTED, DO NOT CORRELATE WITH ANY
 CALCULATIONS BASED FROM THE NFPA-70 OR
 IS PERMITTED IN THE NEC.
 ** PLEASE SEE 220.312B AND COMPLETE.
 PLEASE SEE THERE IS A MAJOR LOAD BEING
 ADDED, HOWEVER THERE HAS BEEN NOT
 CONSIDERATION FOR THIS. PLEASE SEE SPECS
 FOR TANKLESS WATER HEATER SUBMITTED
 WHICH "HIGH-LIGHTS" A 28KW UNIT!!!! THIS
 UNITS ALONE PULLS 116A'S.
 PLEASE SEE THE LOAD ON THIS UNIT ALONE
 AND THE MIN LOADS ON THE EXISTING
 DWELLING FAR EXCEED THE RATING OF THE
 EXISTING DWELLING'S SERVICE.
 PLEASE OBTAIN A QUALIFIED PERSON WHO HAS
 ELECTRICAL BACKGROUND TO THESE AS THIS
 IS LIFE SAFETY AND FIREHAZARD AND DUE
 TO WHAT IS BEING SUBMITTED.
 PLEASE SEE NO INFORMATION AND LCOATION
 OF UNIT AT THIS TIME IS "NOT" PERMITTED.
 ** PLEASE ALSO SEE THERE IS NO NRTL(
 NATIONALLY RECOGNIZED TESTING
 LABORATORY) SHOWN ON SPECS. PLEASE ALSO
 SUBMIT TWO COPIES.
 PLEASE SEE NO NEW REVISED PANEL SCHEDULE
 WAS SUBMITTED EITHER TO VERIFY THE NEW
 CIRCUITS, CONDUCTORS, OCP, LOADS ETC.
 110.3,240.24,110.26,90.7,220.31B, 408.4,
 240.4, 310.16 ETC.
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE SUBMIT COMPLETE LOAD
 CALCULATIONS SHOWING ALL EXISTING AND
 NEW LOADS.
 INDICATE THE SIZE OF THE NEW TANKLESS
 WH. PLEASE SEE MANUFACTURES SPECS / CUT
 SHEETS FOR MIN CLEARENCES AND LOCATION.
 PLEASE SEE CLARIFY WHERE THE MEANS OF
 DISCONNECT IS?
 PLEASE SEE LOCATION BEING PRIMARILY
 STORAGE UNDER LAV AND LOCATION DUE TO
 EASILY IGNITIBLE MATERIALS.
 PLEASE SUBMIT THE MANUFACTURES SPECS/
 CUT SHEETS FOR THE PROPOSED UNIT.
 PLEASE SEE 110.26,422.31,110.3,240.24,
 220.31, 408.4 ETC.
  
 2) NOTE: OK.
  
 3) NOTE:NO, SAME NOTE, NOTHING SHOWN
 OR SUBMITTED.
  
 ** PREVIOUS REVIEW NOTE **PLEASE SEE
 2004 R313 AS SD'S
 ARE REQUIRED INSIDE AND OUTSIDE ALL
 EXISTING SLEEPING RMS. PLEASE SEE
 NFPA-72 11.5.1.1,11.8.3.
 PLEASE SHOW A BASIC LAYOUT OF THE
 EXISTING DWELLING AND THE LOCATION OF
 THE SD'S.
  
 4) NOTE: NO, NOT CLEAR A NEW LOCATION
 SEEMS TO BE SHOWN BASED ON SYMBOL OF
 WHAT THE WASHER AND DRYER SHOULD BE,
 HOWEVER NOTHING IDENTIFING NEW
 EQUIPMENT. PLEASE SEE IF NEW STACKABLE
 UNIT, PLEASE SHOW, AND PLEASE INDICATE
 IN NEW LOADS/PANEL SCHEDULE.
 220.16, 210.11C2, 220.18
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE SEE PERMIT APPLICATION
 MENTIONS CONVERTING EXISTING LAUNDRY RM
 TO BATHRM, HOWEVER NEW LANUDRY AREA CAN
 NOT BE LOCATED. PLEASE SEE MIN HOUSING
 CODE FOR LAUNDRY FACILIES AND PLEASE SEE
 NEC FOR MIN LAUNDRY CIRCUITS.
 210.11C2, 220.16
  
  
 ** NEW NOTE **
  
 1) NOTE: PLEASE SEE ONE SET OF PLANS
 HAVE BEEN RETAINED BY THIS OFFICE AND
 WILL BE PLACED IN FILE WITH ALL OTHER
 PROJECTS REPEATLY BEING SUBMITTED,
 SIGNED , DATED AND SEALED BY THIS DESIGN
 PROFESSSIONAL.PLEASE SEE NOTICE TO FS
 553.80(2)(B) WITH RESPECT TO REPEAT
 COMMENTS FOR PLAN REVIEW IS NOW GIVEN AS
 NOTICE.
 PLEASE ALSO SEE FS 471.025(3) QUOTED,
 "NO LICENSEE SHALL AFFIX OR PERMIT TO
 BE AFFIXED HIS OR HER SEAL, NAME, OR
 DIGITAL SIGNATURE TO ANY PLAN,
 SPECIFICATION, DRAWING, FINAL BID
 DOCUMENT, OR OTHER DOCUMENT THAT DEPICTS
 WORK WHICH HE OR SHE IS NOT LICENSED TO
 PERFORM OR WHICH IS BEYOND HIS OR HER
 PROFESSION OR SPECIALTY THEREIN."
 THIS IS TAKEN DIRECTLY FROM THE TEXT OUT
 OF THE FLORIDA STATUES.
  
  
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  