Plan Review Notes
Plan Review Notes For Permit 06070422
Permit Number 06070422
Review Stop E
Sequence Number 1
Notes
Date Text
2006-07-20 00:00:00******UNSAT ********
  
 1) NOTE: PLEASE SUBMIT COMPLETE LOAD
 CALCULATIONS SHOWING ALL EXISTING AND
 NEW LOADS.
 INDICATE THE SIZE OF THE NEW TANKLESS
 WH. PLEASE SEE MANUFACTURES SPECS / CUT
 SHEETS FOR MIN CLEARENCES AND LOCATION.
 PLEASE SEE CLARIFY WHERE THE MEANS OF
 DISCONNECT IS?
 PLEASE SEE LOCATION BEING PRIMARILY
 STORAGE UNDER LAV AND LOCATION DUE TO
 EASILY IGNITIBLE MATERIALS.
 PLEASE SUBMIT THE MANUFACTURES SPECS/
 CUT SHEETS FOR THE PROPOSED UNIT.
 PLEASE SEE 11.26,422.31,110.3,240.24,
 220.31, 408.4 ETC.
  
 2) NOTE: PLEASE SEE MISSING RECEPT PER
 210.52 FOR MORE THAN 2' OF WALL SPACE.
  
 3) NOTE: PLEASE SEE 2004 R313 AS SD'S
 ARE REQUIRED INSIDE AND OUTSIDE ALL
 EXISTING SLEEPING RMS. PLEASE SEE
 NFPA-72 11.5.1.1,11.8.3.
 PLEASE SHOW A BASIC LAYOUT OF THE
 EXISTING DWELLING AND THE LOCATION OF
 THE SD'S.
  
 4) NOTE: PLEASE SEE PERMIT APPLICATION
 MENTIONS CONVERTING EXISTING LAUNDRY RM
 TO BATHRM, HOWEVER NEW LANUDRY AREA CAN
 NOT BE LOCATED. PLEASE SEE MIN HOUSING
 CODE FOR LAUNDRY FACILIES AND PLEASE SEE
 NEC FOR MIN LAUNDRY CIRCUITS.
 210.11C2, 220.16
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717