| Date |
Text |
| 2006-11-14 12:19:00 | ***** UNSAT 2ND REVIEW***** |
| | |
| | *** PLEASE SEE RISER, PLANS AND EQUIPMENT SUBMITTED HAS |
| | NOW BEEN COMPLETELY REVISED FROM THE PREVIOUSLY |
| | REVIEWED WHICH HAS CREATED NEW COMMENTS. |
| | |
| | 1) NOTE: PLEASE SUBMIT THE PERMIT APPLICATION BACK WITH |
| | PLANS. COULD NOT LOCATE THE ORIGINAL PERMIT APPLICATION |
| | IN PERMIT PLANS AND PACKAGE. |
| | PLEASE REVISE PERMIT APPLICATION TO INCLUDE THE NEW GEN |
| | AS NOW SUBMITTED. PLEASE ALSO ADJUST VALUE AS REQUIRED |
| | BY CODE FOR SCOPE OF WORK. THIS VALUE SHALL BE BASED ON |
| | TABLES AS SET FORTH AND ADOPTED INTO THE CODE FOR FAIR |
| | MARKET VALUE. FBC 108.3 |
| | 105.1, 106.1.2 |
| | FBC ADMINISTRATIVE SECTION AS ADOPTED BY THE CITY OF |
| | WEST PALM BEACH. |
| | |
| | 2) NOTE: PLEASE SUBMIT TWO REVISED SITE/SURVEY PLANS |
| | WHICH INDICATE THE NEW PROPOSED 40KW UNIT. PLEASE |
| | INDICATE ALL OF THE UPDATED DIMENSIONS AND SET-BACKS. |
| | THESE WILL BE SENT TO ZONING FOR REVIEW AND STAMPING AT |
| | THAT TIME. PLEASE SEE THE SITE/SURVEY ORIGINAL |
| | SUBMITTED AND STAMPED BY ZONING WAS VOIDED AS IT IS NOT |
| | LONGER VALID BASED ON THE CHANGES MADE TO PLANS. |
| | |
| | 3) NOTE: PLEASE SUBMIT THE OVER-VIEW OF SAID LOCATION |
| | OF ALL EQUIPMENT. PLEASE BE SURE THE MANUFACTURE |
| | SPECIFICATION DATA SUBMITTED INDICATES THE MINIMUM |
| | REQUIRED DISTANCES AROUND EQUIPMENT AS REQUIRED BY THE |
| | MANUFACTURE. |
| | 90.7, 110.3 |
| | |
| | 4) NOTE: PLEASE SEE SERVICE IS NOW SHOWING 400A OCP FOR |
| | THE SERVICE ENTRANCE CONDUCTORS WHICH SEEMED TO BE FOR |
| | A MUCH SMALLER SERVICE. |
| | PLEASE SEE PREVIOUS PLANS INDICATED A 200A SERVICE WITH |
| | 2/0'S WHICH WERE TOO SMALL AS THE TABLE IN 310.15B6 CAN |
| | NOT BE USED. THIS IS NOT A DWELLING. |
| | PLEASE SEE 240.4, 310.16 AS THE OCP PROVIDED IN THE |
| | SERVICE SHALL LIMIT THE LOAD AND PROTECT THE SERVICE |
| | ENTRANCE CONDUCTORS. |
| | PLEASE KNOW, A MAIN AHEAD OF AN ATS IS OK, AND A SE |
| | RATED ATS IS NOT REQUIRED. IN THE SCENARIO AS SHOWN THE |
| | OCP IS NOT PERMITTED AT 400A?S ON 1/0'S. |
| | PLEASE ALSO SEE RISER SHOWS ONLY 2- HOT-PHASE |
| | CONDUCTORS AND ONE HIGH LEG FROM THE SE RATED ATS TO |
| | THE GUTTER INSIDE. |
| | MISSING THE NEUTRAL, MISSING THE EQUIPMENT GROUNDING |
| | CONDUCTOR (AFTER THE FIRST MEANS OF DISCONNECT). 250.6, |
| | 250.24, 250.110, 250.122 ETC. |
| | PLEASE SEE EVEN THE HIGH-LEG DECREASES IN SIZE TO#3 |
| | FROM THE #2 IN RISER. |
| | PLEASE INDICATE THE OCP IN ALL EXISTING PANELS AND |
| | EQUIPMENT. |
| | PLEASE ALSO SEE AS RISER HAS NOW BEEN COMPLETELY |
| | CHANGED FOR 400A OCP FOR SERVICE; PLEASE SEE 240.21 FOR |
| | TAPPED CONDUCTORS PERMITTED ETC. |
| | PLEASE SEE IF THE SEC'S DO ACTUALLY INCREASE, PLEASE BE |
| | SURE TO SEE 250.66 FOR THE GEC. |
| | PLEASE KNOW THE GENERATOR MUST CONTAIN A "READILY |
| | ACCESSIBLE" DISCONNECTING MEANS LOCATED WITHIN SIGHT. |
| | (50FT) THE DISCONNECTING MEANS MAY NOT EXPOSE ANY |
| | PERSON TO LIVE PARTS. |
| | PLEASE VERIFY THIS ON THE EQUIPMENT BEING PURCHASED. |
| | 110.27, 225.31-225.39, 702.8 ETC |
| | |
| | 5) NOTE: PLEASE SEE SPECS FROM MANUFACTURE ARE HIGH |
| | LIGHTED AS BOTH 3-POLE AND 4-POLE, WHICH ONE WILL THIS |
| | BE? PLEASE VERIFY WITH THE MANUFACTURE AS MANY |
| | GENERATOR MANUFACTURE SHIP THEIR GENERATORS WIRED FOR |
| | SEPARATELY DERIVED SYSTEMS. |
| | IF THIS IS GOING TO BE A SD GEN, PLEASE BE SURE TO |
| | ADJUST GROUNDING OF THE GEN AND THE NEED FOR A 4-POLE |
| | ATS. |
| | |
| | ** PLEASE KNOW, THE RAISED SEAL OVER THE SLAB |
| | ENGINEERING SHEETS IS IN FACT A RAISED SEAL OVER A |
| | COLOR PHOTO-COPIED SIGNATURE. SIGNATURE MUST BE |
| | ORIGINAL WHEN REQUIRED. |
| | THIS IS IN VIOLATION OF FLORIDA STATUTES 471.025 AND |
| | FLORIDA ADMINISTRATIVE CODE 61G15-23.002. |
| | THIS IS ONLY NOTED BY THE ELECTRICAL REVIEW AT THIS |
| | TIME |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | **PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. **IF |
| | THERE ARE ANY QUESTIONS, COMMENTSOR IF ANY OF THE |
| | NOTES TYPEDWHICH ARE UNCLEAR IN ANY WAY, PLEASE DO |
| | NOT HESITATEIN CONTACTING THIS REVIEWER. |
| | |
| | |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |