Plan Review Notes
Plan Review Notes For Permit 06070415
Permit Number 06070415
Review Stop E
Sequence Number 2
Notes
Date Text
2006-11-14 12:19:00***** UNSAT 2ND REVIEW*****
  
 *** PLEASE SEE RISER, PLANS AND EQUIPMENT SUBMITTED HAS
 NOW BEEN COMPLETELY REVISED FROM THE PREVIOUSLY
 REVIEWED WHICH HAS CREATED NEW COMMENTS.
  
 1) NOTE: PLEASE SUBMIT THE PERMIT APPLICATION BACK WITH
 PLANS. COULD NOT LOCATE THE ORIGINAL PERMIT APPLICATION
 IN PERMIT PLANS AND PACKAGE.
 PLEASE REVISE PERMIT APPLICATION TO INCLUDE THE NEW GEN
 AS NOW SUBMITTED. PLEASE ALSO ADJUST VALUE AS REQUIRED
 BY CODE FOR SCOPE OF WORK. THIS VALUE SHALL BE BASED ON
 TABLES AS SET FORTH AND ADOPTED INTO THE CODE FOR FAIR
 MARKET VALUE. FBC 108.3
 105.1, 106.1.2
 FBC ADMINISTRATIVE SECTION AS ADOPTED BY THE CITY OF
 WEST PALM BEACH.
  
 2) NOTE: PLEASE SUBMIT TWO REVISED SITE/SURVEY PLANS
 WHICH INDICATE THE NEW PROPOSED 40KW UNIT. PLEASE
 INDICATE ALL OF THE UPDATED DIMENSIONS AND SET-BACKS.
 THESE WILL BE SENT TO ZONING FOR REVIEW AND STAMPING AT
 THAT TIME. PLEASE SEE THE SITE/SURVEY ORIGINAL
 SUBMITTED AND STAMPED BY ZONING WAS VOIDED AS IT IS NOT
 LONGER VALID BASED ON THE CHANGES MADE TO PLANS.
  
 3) NOTE: PLEASE SUBMIT THE OVER-VIEW OF SAID LOCATION
 OF ALL EQUIPMENT. PLEASE BE SURE THE MANUFACTURE
 SPECIFICATION DATA SUBMITTED INDICATES THE MINIMUM
 REQUIRED DISTANCES AROUND EQUIPMENT AS REQUIRED BY THE
 MANUFACTURE.
 90.7, 110.3
  
 4) NOTE: PLEASE SEE SERVICE IS NOW SHOWING 400A OCP FOR
 THE SERVICE ENTRANCE CONDUCTORS WHICH SEEMED TO BE FOR
 A MUCH SMALLER SERVICE.
 PLEASE SEE PREVIOUS PLANS INDICATED A 200A SERVICE WITH
 2/0'S WHICH WERE TOO SMALL AS THE TABLE IN 310.15B6 CAN
 NOT BE USED. THIS IS NOT A DWELLING.
 PLEASE SEE 240.4, 310.16 AS THE OCP PROVIDED IN THE
 SERVICE SHALL LIMIT THE LOAD AND PROTECT THE SERVICE
 ENTRANCE CONDUCTORS.
 PLEASE KNOW, A MAIN AHEAD OF AN ATS IS OK, AND A SE
 RATED ATS IS NOT REQUIRED. IN THE SCENARIO AS SHOWN THE
 OCP IS NOT PERMITTED AT 400A?S ON 1/0'S.
 PLEASE ALSO SEE RISER SHOWS ONLY 2- HOT-PHASE
 CONDUCTORS AND ONE HIGH LEG FROM THE SE RATED ATS TO
 THE GUTTER INSIDE.
 MISSING THE NEUTRAL, MISSING THE EQUIPMENT GROUNDING
 CONDUCTOR (AFTER THE FIRST MEANS OF DISCONNECT). 250.6,
 250.24, 250.110, 250.122 ETC.
 PLEASE SEE EVEN THE HIGH-LEG DECREASES IN SIZE TO#3
 FROM THE #2 IN RISER.
 PLEASE INDICATE THE OCP IN ALL EXISTING PANELS AND
 EQUIPMENT.
 PLEASE ALSO SEE AS RISER HAS NOW BEEN COMPLETELY
 CHANGED FOR 400A OCP FOR SERVICE; PLEASE SEE 240.21 FOR
 TAPPED CONDUCTORS PERMITTED ETC.
 PLEASE SEE IF THE SEC'S DO ACTUALLY INCREASE, PLEASE BE
 SURE TO SEE 250.66 FOR THE GEC.
 PLEASE KNOW THE GENERATOR MUST CONTAIN A "READILY
 ACCESSIBLE" DISCONNECTING MEANS LOCATED WITHIN SIGHT.
 (50FT) THE DISCONNECTING MEANS MAY NOT EXPOSE ANY
 PERSON TO LIVE PARTS.
 PLEASE VERIFY THIS ON THE EQUIPMENT BEING PURCHASED.
 110.27, 225.31-225.39, 702.8 ETC
  
 5) NOTE: PLEASE SEE SPECS FROM MANUFACTURE ARE HIGH
 LIGHTED AS BOTH 3-POLE AND 4-POLE, WHICH ONE WILL THIS
 BE? PLEASE VERIFY WITH THE MANUFACTURE AS MANY
 GENERATOR MANUFACTURE SHIP THEIR GENERATORS WIRED FOR
 SEPARATELY DERIVED SYSTEMS.
 IF THIS IS GOING TO BE A SD GEN, PLEASE BE SURE TO
 ADJUST GROUNDING OF THE GEN AND THE NEED FOR A 4-POLE
 ATS.
  
 ** PLEASE KNOW, THE RAISED SEAL OVER THE SLAB
 ENGINEERING SHEETS IS IN FACT A RAISED SEAL OVER A
 COLOR PHOTO-COPIED SIGNATURE. SIGNATURE MUST BE
 ORIGINAL WHEN REQUIRED.
 THIS IS IN VIOLATION OF FLORIDA STATUTES 471.025 AND
 FLORIDA ADMINISTRATIVE CODE 61G15-23.002.
 THIS IS ONLY NOTED BY THE ELECTRICAL REVIEW AT THIS
 TIME
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 **PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. **IF
 THERE ARE ANY QUESTIONS, COMMENTSOR IF ANY OF THE
 NOTES TYPEDWHICH ARE UNCLEAR IN ANY WAY, PLEASE DO
 NOT HESITATEIN CONTACTING THIS REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved