| Date |
Text |
| 2006-07-26 00:00:00 | ** UNSAT ** |
| | |
| | 1) NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING |
| | INSTALLED. |
| | 110.9,FBC 106.1.2 |
| | |
| | 2) NOTE: PLEASE PROVIDE AN OVERVIEW OF |
| | THE EQUIPMENT AND LOCATIONS. NEED TO |
| | VERIFY GROUPING OF DISCONNECTS ETC. |
| | PLEASE VERIFY IF THE NEW 125A SUB PANEL |
| | CONTAINS AND MCB AND IS GROUPED WITH THE |
| | OTHER NEW 200A DISCONNECT. |
| | 225.31-225.39, 230.72 |
| | |
| | 3) NOTE: PLEASE PROVIDE THE MINIMUM |
| | DISTANCES FROM BUILDING IN WHICH THE |
| | GENERATOR IS BEING INSTALLED. PLEASE |
| | KNOW AS OF THE DATED INFORMATION |
| | OBTAINED BY THIS OFFICE ALL LIQUID |
| | COOLED UNITS ARE RECOMMENED TO CONTAIN A |
| | 5' MIN CLEARENCE AROUND UNIT. PLEASE SEE |
| | MECH COMMENTS FOR CLEARENCES FROM |
| | OPENINGS TO BUIDLING. |
| | PLEASE KNOW, IF MANUFACTURES SPEC/CUT |
| | SHEETS INDICATE A LESSER MIN CLEARENCE |
| | PLEASE SUBMIT AND HIGHLIGHT. |
| | 110.3,90.7 |
| | |
| | 4) NOTE: PLEASE SUBMIT MANUFACTURES |
| | SPEC/CUT SHEETS FOR THE ATS FOR REVIEW. |
| | 110.3,90.7 |
| | |
| | 5) NOTE: PLEASE SEE THAT LOAD |
| | CALCULATIONS CONTAIN THE PRINTED NAME |
| | AND SIGNATURE OF THE PERSON RESPONSIBLE |
| | FOR SAID PLANS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |