2006-08-10 00:00:00BUILDING PLAN REVIEW
 PERMIT: 06070415
 ADD: 2140 PALM BCH LAKES BLVD.
 CONT: PERSONALIZED A/C
 TEL: (561) 239-1340
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) ENGINEERING SHEET A-1 BY HILLMAN
 ENGINEERING IS A COPY WITH THE WRONG
 ADDRESS INTHE TITLE BLOCK.
 61G15-23.002(2)FL. ADMIN. CODE. PLANS
 SIGNED & SEALED BY A PROFESSIONAL
 ENGINEER SHALL INCLUDE EITHER THE NAME,
 ADDRESS AND LICENSE NUMBER OF THE
 ENGINEER OR, THE NAME AND LICENSE NUMBER
 OF THE ENGINEER AND THE NAME, ADDRESS
 AND CERTIFICATE OF AUTHORIZATION NUMBER
 OF THE ENGINEERING BUSINESS THROUGH
 WHICH THE ENGINEER IS PRACTICING
 (471.025 F.S. AND 471.023 F.S.).
  
 3) HILLMAN ENGINEERING IS MISSING THEIR
 CERTIFICATE OS AUTHORIZATION:
 61G15-23.002 P. E.- CERTIFICATE OF
 AUTHORIZATION.IF PRACTICING THROUGH A
 DULY AUTHORIZED ENGINEERING BUSINESS,
 ENGINEERS SHALL LEGIBLY INDICATE THEIR
 NAME AND LICENSE NUMBER, AS WELL AS,
 THE NAME, ADDRESS, AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF THE ENGINEERING
 BUSINESS ON EACH SHEET.
  
 4) HILLMAN ENGINEERING PLANS ARE NOT
 SIGNED NOR SEALED, ORIGINALS, BUT
 COPIED.
 PLANS, SPECIFICATIONS, REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 5) PROVIDE ADDITIONAL INFORMATION AS TO
 PREFABRICATED PAD. PROVIDE WEIGHT PER
 SQUARE FOOT.
 1609.1.3 ANCHORAGE AGAINST OVERTURNING,
 UPLIFT AND SLIDING.
 STRUCTURAL MEMBERS AND SYSTEMS AND
 COMPONENTS AND CLADDING IN A BUILDING OR
 STRUCTURE SHALL BE ANCHORED TO RESIST
 WIND-INDUCED OVERTURNING, UPLIFT AND
 SLIDING AND TO PROVIDE CONTINUOUS LOAD
 PATHS FOR THESE FORCES TO THE
 FOUNDATION. WHERE A PORTION OF THE
 RESISTANCE TO THESE FORCES IS PROVIDED
 BY DEAD LOAD, THE DEAD LOAD, INCLUDING
 THE WEIGHT OF SOILS AND FOUNDATIONS,
 SHALL BE TAKEN AS THE MINIMUM DEAD LOAD
 LIKELY TO BE IN PLACE DURING A DESIGN
 WIND EVENT. WHERE THE ALTERNATE BASIC
 LOAD COMBINATIONS OF SECTION 1605.3.2
 ARE USED, ONLY TWO-THIRDS OF THE MINIMUM
 DEAD LOAD LIKELY TO BE IN PLACE DURING A
 DESIGN WIND EVENT SHALL BE USED.
  
  
 GENERATOR SLAB & ANCHOR REQUIREMENT
 PLEASE PROVIDE SIZE OF GENERATOR(WXL),
 PLUS PROVIDE PLANS WITH THE INFORMATION
 DEPICTING HOLD DOWN BRACKETS, TYPE OF
 FASTENER, AND THE MINIMUM EDGE DISTANCE
 THE DEVICE REQUIRES WITHOUT LOAD
 REDUCTION.
 SECOND, PROVIDE INFORMATION ON THE
 SLAB, THICKNESS, WIDTH AND LENGTH, IF
 WIREMESH, FIBER MESH OR IF STEEL REBAR
 WILL BEUSED.
 THE NEW SLAB AND HOLD DOWN DETAILS:
 104.2.1* ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026