| Plan Review Notes For Permit 06070395 |
| Permit Number |
06070395 |
|
| Review Stop |
E |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2007-07-16 13:19:04 | ** UNSAT ** | | | | | | 1) NOTE: PLEASE SEE THE SMOKE ALARMS ARE REQUIRED | | | INSIDE AND OUTSIDE BEDROOM/SLEEPING ROOMS. PLEASE SEE | | | LOCATION IS NOT AS SHOWN ON PREVIOUS PLANS. NFPA-72 | | | 11.5.1.1 | | | THESE ARE SMOKE ALARMS NOT SMOKE DETECTORS AS SHOWN. | | | THIS WAS REDLINED ON OTHER UNITS. SEE NFPA-72 | | | DEFINITIONS. | | | | | | 2) NOTE: PLEASE SEE THE CIRCUIT FOR THE SMOKE ALARMS IS | | | SHOWN ON CIRCUIT #8 WHEN PLANS INDICATE #10. PLEASE | | | CORRELATE. | | | | | | 3) NOTE: PLEASE SEE THE PANEL SCHEDULE IS SHOWING THE | | | LOAD FOR WHAT APPEARS TO BE THE SECOND SMALL APPLIANCE | | | CIRCUIT AT 450VA. IS THIS THE FRIG? PLEASE SEE THE | | | PLANS ARE MISSING THE CIRCUIT NUNMBER DESIGNATION ON | | | THE RECEPT IN KITCHEN NEXT TO PANEL. THIS DEVICE HAS | | | TYPICALLY BEEN THE SECOND SMALL APPLIANCE IN OTHER | | | UNITS. | | | 210.52B1, 210.11C1, 220.16 | | | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | 561-805-6717 |
|