| 2007-07-16 16:30:44 | | | | | | | **** UNSAT **** | | | | | | 1) NOTE: PLEASE SEE THE PANEL SCHEDULE INDICATES A | | | SECOND SMALL APPLIANCE CIRCUIT WHICH IS BEING SHARED | | | WITH THE FRIG, HOWEVER THE LOAD IS ONLY SHOWN AT | | | 450VA. | | | PLEASE SEE THE NEW GFI RECEPTACLE ADDED TO KITCHEN | | | CONTAINS A CIRCUIT NUMBER WHICH IS CIRCUITED TO THE | | | LIGHTS. | | | PLEASE SEE 210.52B1 AS THIS IS NOT PERMITTED ON | | | LIGHTING CIRCUIT. | | | PLEASE SEE THIS IS CIRCUIT A-3. | | | PLEASE SEE 210.52B1, 210.11C1, AND 220.16 | | | | | | 2) NOTE: PLEASE SEE AS PLANS ARE COMING BACK FOR | | | CORRECTIONS, PLEASE CORRECT THE DESIGNATION OF THE | | | SMOKE DETECTION DEVICES AS THESE APPEAR TO BE SMOKE | | | ALARMS AND NOT SMOKE DETECTORS PER NFPA-72 | | | DEFINITIONS. | | | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|