Plan Review Notes
Plan Review Notes For Permit 06070391
Permit Number 06070391
Review Stop E
Sequence Number 4
Notes
Date Text
2007-07-16 16:30:44 
  
 **** UNSAT ****
  
 1) NOTE: PLEASE SEE THE PANEL SCHEDULE INDICATES A
 SECOND SMALL APPLIANCE CIRCUIT WHICH IS BEING SHARED
 WITH THE FRIG, HOWEVER THE LOAD IS ONLY SHOWN AT
 450VA.
 PLEASE SEE THE NEW GFI RECEPTACLE ADDED TO KITCHEN
 CONTAINS A CIRCUIT NUMBER WHICH IS CIRCUITED TO THE
 LIGHTS.
 PLEASE SEE 210.52B1 AS THIS IS NOT PERMITTED ON
 LIGHTING CIRCUIT.
 PLEASE SEE THIS IS CIRCUIT A-3.
 PLEASE SEE 210.52B1, 210.11C1, AND 220.16
  
 2) NOTE: PLEASE SEE AS PLANS ARE COMING BACK FOR
 CORRECTIONS, PLEASE CORRECT THE DESIGNATION OF THE
 SMOKE DETECTION DEVICES AS THESE APPEAR TO BE SMOKE
 ALARMS AND NOT SMOKE DETECTORS PER NFPA-72
 DEFINITIONS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]