| Plan Review Notes For Permit 06070321 |
| Permit Number |
06070321 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-08-11 00:00:00 | BUILDING REVIEW 2ND CHECKLIST: | | | | | | 1- CONTRACTOR STATES IN PERMIT | | | APPLICATION THAT CONCRETE TILE IS TO BE | | | PLACED IN WOOD DECK BATTEN SYSTEM. DADE | | | COUNTY NOA #02-1205.07 FOR MONIER | | | SPANISH 'S' CONCRETE TILE DOESN'T ALLOW | | | BATTEN SYSTEM INSTALLATION. SEE PAGE 4 | | | OF 5 OF NOA. NEED TO PROVIDE PRODUCT | | | APPROVAL THAT ALLOWS BATTEN SYSTEM | | | APPLICATION OR PROVIDE SOLID DECK | | | SYSTEM. | | | PROVIDE COMPLETE STRUCTURAL DRAWINGS AND | | | SPECIFICATIONS FOR SOLID DECKING UNDER A | | | SEPARATE PERMIT FOR STRUCTURAL WORK. | | | SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004 | | | AND SEC. 1609 FBC 2004. | | | | | | 2- SELF ADHERING UNDERLAYMENT (FLORIDA | | | PRODUCT APPROVAL FL3732-R1) IS NOT | | | ALLOWED. SEE RAS 120 FOR TYPES OF | | | UNDERLAYMENTS ALLOWED. SPECIFY WHICH | | | UNDERLAYMENT IS GOING TO BE USED. | | | ALSO, ACCORDING TO THE ROOF SLOPE THERE | | | ARE ROOF TILE NAILING REQUIREMENTS. SEE | | | RAS 120 AND PROVIDE NAILING | | | SPECIFICATIONS AS REQUIRED. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|