2006-07-12 00:00:00BUILDING REVIEW CHECKLIST:
 1- CONTRACTOR TO PROVIDE ALL INFORMATION
 AS REQUIRED BY CITY POLICY FOR
 RE-ROOFING PERMITS. SEE ATTACHED COPY.
 MISSING MEAN ROOF HEIGHT.
  
 2- PROVIDE UPLIFT PRESSURE CALCULATIONS
 IF BUILDING MEAN ROOF HEIGHT IS HIGHER
 THAN 30'-0" TO VERIFY COMPLIANCE OF
 CONCRETE ROOF TILE AS REQUIRED BY SEC.
 1609.7 FBC 2004.
  
 3- UNDERLAYMENT PRODUCT APPROVAL.
 A) NEED TO PROVIDE THE 2004 FLORIDA
 PRODUCT APPROVAL VERSION, NOT 2001.
 B) NEED TO PROVIDE TECHNICAL
 INFORMATION THAT WAS SUBMITTED TO GET
 FLORIDA PRODUCT APPROVAL. GO TO THE DCA
 WEBSITE WWW.FLORIDABUILDING.ORG TO
 DOWMLOAD ALL INFORMATION.
  
 4- PROVIDE COPY OF FLORIDA PRODUCT
 APPROVAL COVER PAGE AS REQUIRED BY CITY
 RE-ROOFING PERMITS FOR MONIER SPANISH
 "S". CONC. ROOF TILE.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER