Plan Review Notes
Plan Review Notes For Permit 06070319
Permit Number 06070319
Review Stop B
Sequence Number 2
Notes
Date Text
2006-08-11 00:00:00BUILDING REVIEW 2ND CHECKLIST:
  
 1- CONTRACTOR STATES IN PERMIT
 APPLICATION THAT CONCRETE TILE IS TO BE
 PLACED IN WOOD DECK BATTEN SYSTEM. DADE
 COUNTY NOA #02-1205.07 FOR MONIER
 SPANISH 'S' CONCRETE TILE DOESN'T ALLOW
 BATTEN SYSTEM INSTALLATION. SEE PAGE 4
 OF 5 OF NOA. NEED TO PROVIDE PRODUCT
 APPROVAL THAT ALLOWS BATTEN SYSTEM
 APPLICATION OR PROVIDE SOLID DECK
 SYSTEM.
 PROVIDE COMPLETE STRUCTURAL DRAWINGS AND
 SPECIFICATIONS FOR SOLID DECKING UNDER A
 SEPARATE PERMIT FOR STRUCTURAL WORK.
 SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004
 AND SEC. 1609 FBC 2004.
  
 2- SELF ADHERING UNDERLAYMENT (FLORIDA
 PRODUCT APPROVAL FL3732-R1) IS NOT
 ALLOWED. SEE RAS 120 FOR TYPES OF
 UNDERLAYMENTS ALLOWED. SPECIFY WHICH
 UNDERLAYMENT IS GOING TO BE USED.
 ALSO, ACCORDING TO THE ROOF SLOPE THERE
 ARE ROOF TILE NAILING REQUIREMENTS. SEE
 RAS 120 AND PROVIDE NAILING
 SPECIFICATIONS AS REQUIRED.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712