| Date |
Text |
| 2006-07-18 00:00:00 | ******** UNSAT ********* |
| | |
| | 1) NOTE: PLEASE SEE THE LIGHTING LAYOUT |
| | WHICH WAS PROVIDED SEPARATELY NEEDS TO |
| | CONTAIN CIRCUITING, CONTROLS AND |
| | CORRELATE WITH THE SUBMITTED PANEL |
| | SCHEDULE ON PLANS. IN FACT THE |
| | ELECTRICLA LAYOUT SHOWN FOR COOLER |
| | SHOULD BE PROVIDED BY THE DESIGN |
| | PROFESSIONAL WHICH HAD DRAWN THE PLANS |
| | FOR THE INSTALLATION OF COOLER AND ALL |
| | OTHER ELECTRICAL WORK IN THIS SCOPE PF |
| | WORK FOR THIS PERMIT FOR SPACE. |
| | PLEASE KNOW, AS SCOPE OF WORK IS |
| | PERMITTED AND DONE UNDER THE SAME |
| | PERMIT. ONE DESIGN PROFESSIONAL SHOULD |
| | BE RESPOSIBLE FOR DESIGN AND |
| | CONNECTIONS, ETC ARE COMBINED. |
| | 106.1.2 ADMIN SECT. PLEASE BE SURE TO |
| | SEE 700.12E FOR CIRCUITIGN OF EM/EXT LTS |
| | TO THE LOCAL LIGHTING BRANCH CIRCUIT IN |
| | ANY ONE AREA. PLEASE KNOW, FAILURE OF |
| | ONE OCP, CIRCUIT SHOULD NOT LEAVE IN ONE |
| | AREA IN TOTAL DARKNESS. |
| | LS 101 7.8, 7.9 |
| | |
| | 2) NOTE: PLEASE SEE RESPONSE LTR FROM |
| | ARCHITECT'S OFFICE MENTIONS THE 2000 LS |
| | CODE. PLEASE KNOW, WE ARE CURRENTLY |
| | UNDER THE 2003 101. |
| | |
| | 3) NOTE: PLEASE SEE THAT THE SPECS ON EM |
| | LTS ARE OK, HOWEVERTHERE IS A QUESTION |
| | ON THE EM/EXT COMBO UNITWHERE THE |
| | LISTING FOR THIS FIXTURE PERMITS THE |
| | INSTALLATION IN THE COOLER/DAMP/POSSIBLE |
| | WET LOCATION.? COULD NOT LOCATE ANY |
| | INFORMATION ON SPECS SUBMITTED WHICH |
| | LENDS TO THIS? |
| | PLEASE ALSO SEE THE UNIT IS SHOWN AS A |
| | COMBO UNIT WHICH IS FINE, HOWEVER PLANS |
| | SHOULD INDICATE THIS. |
| | 110.3, FBC 106.1.2 ADMIN SECT. |
| | |
| | 4) NOTE: PLEASE KNOW, IF ALL OTHER |
| | ELECTRICAL MECHANICAL WORK IS INLCUDED |
| | IN THE PERMIT/SCOPE, THEN PLEASE KNOW, |
| | VALUATION FOR PERMIT SHALL INCLUDE ALL |
| | LABOR AND MATERIALS WHETHER OR NOT ANY |
| | OF THE EQUIPMENT IS OWNER SUPPLIED. |
| | FBC 108.3 |
| | |
| | THE EXTENSIVE RESPONSE LTR IS |
| | APPRECIATED FOR CLARIFICATION OF OTHER |
| | ITEMS. |
| | |
| | IF THERE ARE ANY QUESTIONS ON NOTE #1, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS REVIEWER. |
| | |
| | ** PLEASE BE SURE TO SEE ANY POSSIBLE |
| | COMMENTS FROM OTHER TRADES WHICH MAY |
| | AFFECT THE ELECTRICAL PLANS, DESIGN ETC. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |