| Plan Review Notes For Permit 06070179 |
| Permit Number |
06070179 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-09-13 00:00:00 | NONCOMPLIANT | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} PROVIDE A RISER DIAGRAM WITH | | | CONDUCTOR AND CONDUIT SIZE AND TYPE, | | | GROUNDING DETAILS, LOAD CALCULATIONS, | | | PANEL SCHEDULES, SERVICE EQUIPMENT AND | | | PANEL LOCATIONS PER 106.3.5.4 FBC. THIS | | | DOCUMENT MUST BE PRODUCED BY THE | | | DESIGNER OF RECORD FOR THE PROJECT, AND | | | SIGNEDAND SEALED BY SAME. | | | | | | 2} THE RECEPTACLE IN THE MASTER BATH | | | MUST COMPLY WITH 210.52(D), WITHIN 3' OF | | | THE BASIN. PLEASE CORRECT ON PLANS. | | | | | | 3} THE WHITE OUT ON THE PLAN IS NOT | | | ACCEPTABLE FOR RECORD RETENTION PER | | | 106.1.3 FBC. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | WILLIAM R. TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561) 805-6718 |
|