Plan Review Notes
Plan Review Notes For Permit 06070179
Permit Number 06070179
Review Stop E
Sequence Number 2
Notes
Date Text
2006-09-13 00:00:00NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PROVIDE A RISER DIAGRAM WITH
 CONDUCTOR AND CONDUIT SIZE AND TYPE,
 GROUNDING DETAILS, LOAD CALCULATIONS,
 PANEL SCHEDULES, SERVICE EQUIPMENT AND
 PANEL LOCATIONS PER 106.3.5.4 FBC. THIS
 DOCUMENT MUST BE PRODUCED BY THE
 DESIGNER OF RECORD FOR THE PROJECT, AND
 SIGNEDAND SEALED BY SAME.
  
 2} THE RECEPTACLE IN THE MASTER BATH
 MUST COMPLY WITH 210.52(D), WITHIN 3' OF
 THE BASIN. PLEASE CORRECT ON PLANS.
  
 3} THE WHITE OUT ON THE PLAN IS NOT
 ACCEPTABLE FOR RECORD RETENTION PER
 106.1.3 FBC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  