| Date |
Text |
| 2006-09-26 00:00:00 | |
| | |
| | DENIED |
| | |
| | 1) THE SUBMITTED TRUSS DRAWINGS SHALL BE |
| | SIGNED AND SEALED BY TRUSS MANUFACTURERS |
| | ENGINEER. ALSO ONLY ONE COPY OF THE |
| | LAYOUT WAS PROVIDED AND 2 WILL BE |
| | REQUIRED |
| | |
| | 2) PLEASE BE AWARE THAT SPECIFIC ANCHORS |
| | ARE TO BE LISTED FOR THE TRUSS TIE DOWNS |
| | AT ALL LOCATIONS (WALLS, GIRDERS, |
| | VALLEYS, ETC.) EITHER BY THE TRUSS |
| | MANUFACTURERS DESIGNER OR THE DESIGNER |
| | RESPONSIBLE FOR THE PROJECT |
| | |
| | 3) PRODUCT APPROVALS FOR THE MULLIONS |
| | MISSING THE STATE OF FLORIDA COVERS |
| | SHEETS (FL# 6868) |
| | |
| | 4) SOME PRODUCT APPROVALS WERE NOT |
| | REVIEWED BY THE DESIGN PROFFESIONAL AS |
| | REQUIRED PER 106.3.3 FBC* ( SINGLE HUNG |
| | WINDOWS,MULLIONS,STEEL INSULATED DOOR, |
| | AND STORM PANELS |
| | |
| | 5) PRODUCT APPROVALS WERE SUBMITTED FOR |
| | CASEMENT/SH EGRESS WINDOWS. PLEASE SEE |
| | THAT THE REGULAR SINGLE HUNG SH25 WILL |
| | MEET THE EGRESS REQUIREMENTS BECAUSE IT |
| | IS 63" TALL AND THAT THE CASEMENT/SH |
| | WINDOWS HAVE A MAX HEIGHT OF 50 5/8" |
| | ALSO A PRODUCT APPROVAL WAS SUBMITTED |
| | FOR AN INSWING DOOR THAT IS NOT A FRENCH |
| | DOOR (GLAZED) AS STATED FOR FRONT DOOR |
| | ON THE DRAWINGS. PLEASE MAKE CORRECTIONS |
| | AND REMOVE PRODUCTS THAT ARE INCORRECT |
| | OR NOT USED. SUBMIT REVIEWED AND |
| | APPROVED ALTERNATIVES. |
| | |
| | 6) ALL PERMIT APPLICATION FEES MUST BE |
| | PAID BEFORE FURTHER REVIEWS WILL BE MADE |
| | |
| | BLDG PLAN REVIEW |
| | ADRIAN MORSE |
| | 561-805-6716 |
| | |
| | |
| | |
| | |
| | |
| | |