2006-07-12 00:00:00DENIED;
 1.SANITARY RISER DIAGRAM; MASTER
 BATHROOM LAVS ARE NOT ON THE SAME WALL.
 A VENT STACK IS NEEDED FOR EACH LAV.
 2.AUTOMATIC CLOTHES WASHER BRANCH DRAIN
 IS REQUIRED TO BE 3", FBC-2004 PLUMBING
 SEC. 406.3. CLEANOUT SHOULD BE LOCATED
 AT 48" ABOVE FINISHED FLOOR FOR SERVICE.
 ON SET OF PLANS MARKED IN RED
 PLUMBING PLAN REVIEW BY;