| Plan Review Notes For Permit 06070176 |
| Permit Number |
06070176 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-09-17 00:00:00 | *** UNSAT *** | | | | | | ** PLEASE SEE SOME NOTES FROM PREVIOUS | | | REVIEW STILL NEED TO BE ADDRESSED. | | | | | | 1) NOTE: PLEASE SEE MISSING DISCONNECT | | | FOR THE FEEDERS COMING FROM THE | | | GENERARATOR WHICH IS REQUIRED WITHIN | | | CLOSE PROXIMITY OF THE EXISTING MAIN. | | | 225-31, 225.3- | | | PLEASE PROVIDE AN OVERVIEW OF HOUSE AND | | | LOCATION OF THE SERVICE IN COMPARISON OF | | | THE GEN, AND NEW DISOCNNECT REQUIRED. | | | | | | 2) NOTE: PLEASE SEE MISSING EQUIPMENT | | | GROUNDING CONDUCTOR FROM EXISTING MAIN | | | PANEL TO NEW SUB PANEL. | | | 250.110,250.122. | | | | | | 3) NOTE: PLEASE VERIFY, THE RISER SEEMS | | | TO SHOW THE LV AND HV CONDUCTORS BEING | | | INSTALLED IN THE SAME CONDUIT FROM | | | GENERATOR.? | | | THIS IS ONLY FOR CLARIFICATION. | | | | | | 4) NOTE: PLEASE BE SURE TO PRINT NAME | | | AND SIGN ALL PLANS/DESIGNS/LOAD | | | CALCULATIONS BEING DONE AND CERTIFIED BY | | | THE CONTRACTOR. | | | PLEASE SEE HEAT LOAD OS BEING SHOWN AS | | | 5KW. | | | | | | ALL SHEETS EXCEPT MANUFACTURES/SPEC/CUT | | | SHEETS ARE TO BE SIGNED. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-805-6717 | | | [email protected] |
|