Plan Review Notes
Plan Review Notes For Permit 06070176
Permit Number 06070176
Review Stop E
Sequence Number 1
Notes
Date Text
2006-07-21 00:00:00*** UNSAT ***
  
 1) NOTE: PLEASE PROVIDE A RISER DIAGRAM
 INCLUDING ALL CONDUCTOR SIZE AND HOW
 THIS PANEL ETC WILL TIE INTO THE
 EXISTING SERVICE.
 PLEASE INDICATE ALL OCP , FEEDERS ETC
 FROM EXISTING.
 PLEASE CLARIFY AND SHOW THE DISCONNECT
 REQUIRED FOR FEEDERS FROM GEN TO HOUSE
 AND BEIGN GROUPED WIHT THE EXISTING
 MAINS/DISCONNECTS.
 PLEASE SHOW AN OVERVIEW FOR LOCATION OF
 ALL EQUIPMENT.
 240.4,310.16,215.5,225.31-225.39
  
 2) NOTE: PLEASE VERIFY HEAT STRIP IN AHU
 AND HOW THE LOAD WILL SHED. PLEASE KNOW,
 IF PART OF UNIT, THEN THE HEAT LOAD AT
 100% WILL BE REQUIRED TO BE FIGURED INTO
 CALCULATIONS.
 220.31
  
 3) NOTE: PLEASE PROVIDE SETBACKS OF GEN
 FOR ALL SIDES FROM PROPERTY , AND ANY
 STRUCTURES.
 PLEASE KNOW, MIN CLEARENCE ON ALL SIDES
 FOR THIS UNIT SHALL BE 3FT PR GREATER OF
 REQUIRED BY MANUFACTURE.
  
 4) NOTE: PLEASE SEE FBC 108.3 ADMIN SECT
 AS THE VALUE FOR THE SCOPE OF WORK SHALL
 INCLUDE ALL LABOR AND MATERIALS EVEN IF
 EQUIPMENT IS OWNER SUPPLIED.
 PLEASE ADJUST.
  
 5) NOTE: PLEASE KNOW ALL PLANS DESIGNS
 ETC SHALL CONTAIN THE PRINTED NAME AND
 THE SIGNATURE OF THE PERSON RESPONSIBLE
 FOR PLANS. MUST STATE, DRAWN BY:,,, ETC
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  