| 2006-07-21 00:00:00 | *** UNSAT *** |
| | |
| | 1) NOTE: PLEASE PROVIDE A RISER DIAGRAM |
| | INCLUDING ALL CONDUCTOR SIZE AND HOW |
| | THIS PANEL ETC WILL TIE INTO THE |
| | EXISTING SERVICE. |
| | PLEASE INDICATE ALL OCP , FEEDERS ETC |
| | FROM EXISTING. |
| | PLEASE CLARIFY AND SHOW THE DISCONNECT |
| | REQUIRED FOR FEEDERS FROM GEN TO HOUSE |
| | AND BEIGN GROUPED WIHT THE EXISTING |
| | MAINS/DISCONNECTS. |
| | PLEASE SHOW AN OVERVIEW FOR LOCATION OF |
| | ALL EQUIPMENT. |
| | 240.4,310.16,215.5,225.31-225.39 |
| | |
| | 2) NOTE: PLEASE VERIFY HEAT STRIP IN AHU |
| | AND HOW THE LOAD WILL SHED. PLEASE KNOW, |
| | IF PART OF UNIT, THEN THE HEAT LOAD AT |
| | 100% WILL BE REQUIRED TO BE FIGURED INTO |
| | CALCULATIONS. |
| | 220.31 |
| | |
| | 3) NOTE: PLEASE PROVIDE SETBACKS OF GEN |
| | FOR ALL SIDES FROM PROPERTY , AND ANY |
| | STRUCTURES. |
| | PLEASE KNOW, MIN CLEARENCE ON ALL SIDES |
| | FOR THIS UNIT SHALL BE 3FT PR GREATER OF |
| | REQUIRED BY MANUFACTURE. |
| | |
| | 4) NOTE: PLEASE SEE FBC 108.3 ADMIN SECT |
| | AS THE VALUE FOR THE SCOPE OF WORK SHALL |
| | INCLUDE ALL LABOR AND MATERIALS EVEN IF |
| | EQUIPMENT IS OWNER SUPPLIED. |
| | PLEASE ADJUST. |
| | |
| | 5) NOTE: PLEASE KNOW ALL PLANS DESIGNS |
| | ETC SHALL CONTAIN THE PRINTED NAME AND |
| | THE SIGNATURE OF THE PERSON RESPONSIBLE |
| | FOR PLANS. MUST STATE, DRAWN BY:,,, ETC |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |