Plan Review Notes
Plan Review Notes For Permit 06070160
Permit Number 06070160
Review Stop B
Sequence Number 1
Notes
Date Text
2006-07-12 00:00:00BUILDING REVIEW CHECKLIST:
 1- STRUCTURAL DRAWINGS:
 A) PROVIDE COMPLETE ENGINEERING
 PACKAGE ADDRESSING ALL STRUCTURAL WORK
 TO BE PERFORMED ON THE SPECIFIC
 BUILDING. INFORMATION SUBMITTED DOESN'T
 ADDRESS THIS ISSUE. IT'S GENERAL
 INFORMATION AND APPLIES TO CONDO UNITS,
 NOT TO THE POOL HOUSE.
 B) REVISEADDRESS OF BUILDING.
 C) ALL ENGINEERING INFORMATION TO BE
 SIGNED AND SEALED AS REQUIRED BY CHAPTER
 471 FLORIDA STATUTES AND FLORIDA
 ADMINISTRATIVE CODE.
 D) SECOND PAGE IS MISSING THE TITLE
 BLOCK AND ADDRESS OF JOB.
 E) CONNECTOR SIMPSON H2.5A SPECIFIED ON
 DETAIL #1 IS A WOOD TO WOOD CONNECTOR.
 NEED TO SPECIFY WOOD TO MASONRY
 CONNECTOR. REVISE AS REQUIRED.
 F) DETAIL #1: SPECIFY CONNECTORS FOR
 NEW (2)2X12 BEAM.
 G) SPECIFY HOW ARE NEW 2X4 SCABS
 ATTACHED TO BOTTOM OF TRUSS CHORDS?
 H) SPECIFY SIZE OF STEEL ANGLES AND
 NUMBER OF BOLTS.
 I) SPECIFY NEW SOFFITS.
 J) DETAIL #5: SPECIFY ALL CONNECTORS.
 K) DETAIL #4: SPECIFY SPACING FOR HEX
 HEAD BOLTS ALONG THE BEAM.
  
 2- A) PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL FOR ALL STRUCTURAL CONNECTORS
 SPECIFIED ON DETAILS.
 B) DESIGNER OF RECORD TO REVIEW AND
 APPROVE ALL PRODUCT APPROVALS PRIOR TO
 SUBMITTAL.
  
 3- CONTRACTOR TO PROVIDE ALL INFORMATION
 AS REQUIRED BY CITY POLICY FOR
 RE-ROOFING PERMITS. SEE ATTACHED COPY.
 MISSING MEAN ROOF HEIGHT.
  
 4- PROVIDE UPLIFT PRESSURE CALCULATIONS
 IF BUILDING MEAN ROOF HEIGHT IS HIGHER
 THAN 30'-0" TO VERIFY COMPLIANCE OF
 CONCRETE ROOF TILE AS REQUIRED BY SEC.
 1609.7 FBC 2004.
  
 5- A) REQUIRES TWO DIFFERENT PERMITS.
 ONE FOR ROOF STRUCTURAL REPAIRS AND THE
 OTHER FOR ROOFING.
 B) BRAKE DOWN VALUATION FOR ROOFING AND
 FOR STRUCTURAL REPAIRS FOR PROPER PERMIT
 VALUATION.
  
 6- UNDERLAYMENT PRODUCT APPROVAL.
 A) NEED TO PROVIDE THE 2004 FLORIDA
 PRODUCT APPROVAL VERSION, NOT 2001.
 B) NEED TO PROVIDE TECHNICAL
 INFORMATION THAT WAS SUBMITTED TO GET
 FLORIDA PRODUCT APPROVAL. GO TO THE DCA
 WEBSITE WWW.FLORIDABUILDING.ORG TO
 DOWMLOAD ALL INFORMATION.
  
 7- PROVIDE COPY OF FLORIDA PRODUCT
 APPROVAL COVER PAGE AS REQUIRED BY CITY
 RE-ROOFING PERMITS FOR MONIER SPANISH
 "S". CONC. ROOF TILE.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712