| 2006-08-10 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 06070159 |
| | ADD: 610 CLEMATIS ST. |
| | CONT: MICHAEL T. LANG BUILDER |
| | TEL: (561)723-2895 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1STREVIEW |
| | ACTION: DENIED |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 2) FL S S 713.13 |
| | NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT BEFORE A |
| | PERMIT WILL BE ISSUED. NOTE: 713.13(2) |
| | IF THE WORK DESCRIBED IN THE NOTICE OF |
| | COMMENCEMENT IS NOT ACTUALLY COMMENCED |
| | WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. |
| | |
| | 3) SEE PLUMBING REVIEW FOR REQUIRED |
| | INFORMATION IN TITLEBLOCK. |
| | |
| | 4) 110.2* W. P. B. ADMINISTRATIVE CODE, |
| | INFORMATION THAT IS REQUIRED FOR RECORD |
| | KEEPING & FOR CERTIFICATE OF OCCUPANCY: |
| | A) THE EDITION OFTHE CODE UNDER WHICH |
| | THE PERMIT WAS ISSUED. |
| | NOTE: 2004 FBC, EXISTING BUILDING |
| | CODE. LEVEL OF ALTERATION! 2004 |
| | EXISTING BUILDING CODE 2004, 301.5 |
| | 301.5 A DESIGN PROFESSIONAL OR AN |
| | OWNER MUST ELECT ONE OR A COMBINATION OF |
| | LEVELS OF ALTERATION PURSUANT TO SECTION |
| | 303,304 & 305 OF THIS CODE.LEVEL II. |
| | |
| | B) THE TYPE OF CONSTRUCTION AS DEFINED |
| | IN CHAPTER 5, TABLE 503 2004 FBC & |
| | FBC TABLE 601. TYPE IB/ FLOOR 2HR |
| | RATING. |
| | |
| | 5)P4.0 WHERE THE DRAIN PIPE PENETRATES |
| | THE FLOOR ASSEMBLY INTO THE PARKING |
| | GAGARE PLEASE PROVIDE THE FIRE STOPPING |
| | ASSEMBLY, 712.4.1.2 THROUGH-PENETRATION |
| | FIRESTOP SYSTEM. |
| | THROUGH PENETRATIONS SHALL BE PROTECTED |
| | BY AN APPROVED THROUGH-PENETRATION |
| | FIRESTOP SYSTEM INSTALLED AND TESTED IN |
| | ACCORDANCE WITH ASTM E 814 OR UL 1479, |
| | WITH A MINIMUM POSITIVE PRESSURE |
| | DIFFERENTIAL OF 0.01 INCH (2.49 PA) OF |
| | WATER. THE SYSTEM SHALL HAVE AN F RATING |
| | AND A T RATING OF NOT LESS THAN 1 HOUR |
| | BUT NOT LESS THAN THE REQUIRED RATING OF |
| | THE FLOOR PENETRATED. |
| | |
| | 6)P4.0 PROVIDE MANUFACTURERS SPEC FOR |
| | WATERPROOFING OF PLANTERS 1807.3.1 |
| | FLOORS/ 1807.3.2 .WALLS. |
| | 1807.3.1WATERPROOFING SHALL BE |
| | ACCOMPLISHED BY PLACING A MEMBRANE OF |
| | RUBBERIZED ASPHALT, BUTYL RUBBER, OR NOT |
| | LESS THAN 6-MIL [0.006 INCH; (0.152 MM)] |
| | POLYVINYL CHLORIDE WITH JOINTS LAPPED |
| | NOT LESS THAN 6 INCHES (152 MM) OR OTHER |
| | APPROVED MATERIALS UNDER THE SLAB. |
| | JOINTS IN THE MEMBRANE SHALL BE LAPPED |
| | AND SEALED IN ACCORDANCE WITH THE |
| | MANUFACTURER?S INSTALLATION |
| | INSTRUCTIONS. |
| | 1807.3.2 WATERPROOFING SHALL BE APPLIED |
| | FROM THE BOTTOM OF THE WALL TO NOT LESS |
| | THAN 12 INCHES (305 MM) ABOVE THE |
| | MAXIMUM ELEVATION OF THE GROUND-WATER |
| | TABLE. THE REMAINDER OF THE WALL SHALL |
| | BE DAMPPROOFED IN ACCORDANCE WITH |
| | SECTION 1807.2.2 . WATERPROOFING SHALL |
| | CONSIST OF TWO-PLY HOT-MOPPED FELTS, NOT |
| | LESS THAN 6-MIL [0.006 INCH; (0.152 MM)] |
| | POLYVINYL CHLORIDE, 40-MIL [0.040 INCH; |
| | (1.02 MM)] POLYMER-MODIFIED ASPHALT, |
| | 6-MIL [0.006 INCH; (0.152 MM)] |
| | POLYETHYLENE OR OTHER APPROVED METHODS |
| | OR MATERIALS CAPABLE OF BRIDGING |
| | NONSTRUCTURAL CRACKS. JOINTS IN THE |
| | MEMBRANE SHALL BE LAPPED AND SEALED IN |
| | ACCORDANCE WITH THE MANUFACTURER?S |
| | INSTALLATION INSTRUCTIONS. |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |