| 2007-01-10 12:09:56 | ** UNSAT *** | | | | | | 1) NOTE: PLEASE SEE PLANS ARE NOW INCLUDING A NEW TANK | | | LESS WATER HEATER WHICH HAS CREATED NEW COMMENTS. | | | PLEASE SEE THIS CIRCUIT IS BEING SHOWN AS A SINGLE POLE | | | 20AMP CIRCUIT, HOWEVER THE LOAD ON THIS CIRCUIT IS | | | SHOWN AS 3300VA. PLEASE SEE THAT THIS EXCEEDS THE | | | MAXIMUM RATING ON THIS 20AMP SINGLE POLE CIRCUIT. | | | PLEASE VERIFY THE SIZE OF THE CIRCUIT AND THE LOAD AND | | | CORRELATE. | | | 310.16, 240.4, 408.4, 220 ETC. | | | | | | 2) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT | | | SHEETS FOR THE UNIT BEING INSTALLED. PLEASE KNOW THIS | | | DOCUMENTATION MUST CONTAIN THE INFORMATION AND | | | LISTING(S) FROM A NRTL. NATIONALLY RECOGNIZED TESTING | | | LABORATORY. | | | 110.3, 90.7 | | | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|