| 2006-07-24 00:00:00 | ** UNSAT ** |
| | |
| | 1) NOTE: PLEASE SPECIFY THE FOLLOWING |
| | CURRENT CODES IN EFFECT. PLEASE KNOW THE |
| | LATEST EDITION OF THE NEC IS NOT YET |
| | ADOPTED BY THE STATE OF FL. |
| | PLEASE LIST THE 2002 NFPA-70 (NEC), 2002 |
| | NFPA-72 AND FBC 2004. |
| | |
| | 2) NOTE: PLEASE SEE FBC CHAPTER 13, |
| | 13-415.1.ABC.1.1 AS NEW BUILD OUT IS IN |
| | A BUILDING GREATER THAN 5K SQ FT, IT |
| | WILL REQUIRE LIGHTING CONTROLS BY ONE |
| | METHOD AS MENTIONED. PLEASE EACH ROOM |
| | SHALL ALSO CONTAIN EITHER SOME TYPE OF |
| | OCCUPANCY SENSOR OR TIMED DEVICE. PLEASE |
| | KNOWIF TIMER TYPE DEVICE IS USED, A |
| | MAX OF 4HR OF OVER RIDE, AND FOR |
| | OCCUPANCY SENSOR TYPE PERMITS A MAX OF |
| | 30 MINS OF OVER RIDE. PLEASE SEE |
| | 13-415.1.ABC.1.2, .1.3. |
| | |
| | 3) NOTE: PLEASE SEE MISSING THE PRINTED |
| | NAME AND PRINTED LICENSE NUMBER OF SAID |
| | ARCHITECT ON TITLE BLOCKS AS REQUIRED |
| | PER FAC 61G1-16.004. |
| | THIS IS REQUIRED FOR ALL TRADES AND FOR |
| | ALL SHEETS WHETHER OR NOT COMMENT IS |
| | MADE BY OTHER REVIEWER(S). |
| | |
| | 4) NOTE: PLEASE CLARIFYTHE CONDUCTORS |
| | SHOWN. PLEASE SEE SYMBOLS SHOWS 3-#0 AND |
| | 3-3#0, IT IS BEING TAKEN THIS IS A |
| | MISPRINT AND THE SYMBOLS ARE MEANING |
| | 3/0?S. PLEASE SEE REDLINED PLANS FOR |
| | LOCATIONS AND ADJUST. |
| | 310.16. |
| | |
| | 5) NOTE: PLEASE SEE 700.12E AS THE |
| | EM/EXT LTS ARE REQUIRED TO BE CIRCUITED |
| | AHEAD OFSWITCHING ON THE LOCAL |
| | LIGHTING BRANCH CIRCUIT IN THE SAME |
| | AREAS. |
| | |
| | 6) NOTE: PLEASE CLARIFY SPECIAL |
| | EQUIPMENT LOAD OF 7500 VAON LOAD |
| | CALCULATIONS AS THIS DOES NOT SEEM TO |
| | CORRELATE WITH AMPERAGES ON PANEL |
| | SCHEDULES. |
| | PLEASE ALSO LIST THIS EQUIPMENT; SOME |
| | NOTED FOR FUTURE HOWEVER PLEASE KNOW |
| | EQUIPMENT MAY AFFECT INSTALLATION |
| | REQUIREMENTS. |
| | PLEASE ALSO SEE THAT WHEN THE NUMBER OF |
| | RECEPTS ARE KNOW THE AMOUNT FIGURED FOR |
| | LOAD CALCULATIONS SHALL BE 180VA PER |
| | RECEPT. |
| | PLEASE ALSO SEE PLANS APPEAR TO SHOW A |
| | REFRIGIERATOR CIRCUITED TO OTHER GENERAL |
| | RECEPT CIRCUIT? PLEASE VERIFY THE AMOUNT |
| | OF VA ON THIS APPLIANCE AND PROVIDE A |
| | DEDICATED CIRCUIT IF OVER 750VA. |
| | 220.3,220.10,220.11,220.13 ETC. |
| | 106.1.2 FBC ADMIN SECT. |
| | |
| | 7) NOTE: PLEASE CLARIFY RISER. IS THIS |
| | 200A METER EXISTING FOR FUTURE USE AND |
| | NOW BEING USED OR IS THIS NEW? PLEASE |
| | LIST THE LOAD ON THE EXISTING SERVICE |
| | ALONG WITH THE NEW LOAD ADDED. |
| | 220,220.35 ETC. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |