| 2006-08-27 00:00:00 | **** UNSAT2ND REVIEW **** |
| | |
| | ** PLEASE SEE SOME COMMENTS FROM PREVOUS |
| | REVIEW STILL NEED TO BE ADDRESSED ALONG |
| | WITH NEW COMMENTS DUE TO |
| | INFORMATION/CHANGES MADE ON PLANS. |
| | PLEASE SEE NOTE BWLOW ARE TAKEN DIRECTLY |
| | FROM PREVIOUS REVIEW AS NOTED WITH NEW |
| | NOTES ADDED TO BOTTOM. |
| | |
| | ** PLEASE SEE THE FOLLOWING COMMENTS, |
| | AND PLEASE KNOW, IT IS RECOMMENED |
| | ELECTRICAL BE DONE ON A SEPARATE SHEET |
| | AS THE OTHER REVIEWS HAVE BEEN STAMPED |
| | AND PASSED. |
| | |
| | 1) NOTE: NO, PLEASE SEE CIRCUITING IS |
| | NOT YET ON PLANS WHICH CORRELATES WITH |
| | THE PANEL SCHEDULE SUBMITTED. |
| | PLEASE KNOW ALL CIRCUITS SHALL BE |
| | SPECIFIC TO ROOMS AND AREAS.408.4 |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SHOW ALL CIRCUITING ON |
| | PLANS AND CORRELATE WITH A PANEL |
| | SCHEDULE TO BE SUBMITTED. |
| | PLEASE LIST ALL THE MIN REQUIRED |
| | DEDICATED CIRCUITS PER |
| | 210.52,210.11,220.16 ETC |
| | BATH(S), SM APPL, RANGE, DISH WASHER , |
| | DISP, ETYC. PLEASE SEE 240.4,310.16, FBC |
| | 106.1.2 ADMIN SECT. |
| | |
| | 2) NOTE: OK. |
| | |
| | 3) NOTE: OK. |
| | |
| | 4) NOTE: OK, HOWEVER NEW JACUZZI TUB IS |
| | SHOWN ON PLANS WITH GFI, HOWEVER THIS |
| | JACUZZI IS NOT ON PANEL SCHEDULE OR IN |
| | LOAD CALCULATIONS? |
| | 220.31 |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE A NEW JACUZZI TUB IS |
| | NOTED, HOWEVER NO ELECTRICAL IS SHOWN |
| | FOR THIS AND NO GFI PROTECTION IS |
| | INDICATED. |
| | 680.71, 240.4,310.16 ETC. |
| | |
| | 5) NOTE: NO, PLEASE SEE BEDRM. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE COMPLETE SW LEGS FOR NEW |
| | LTS SHOWN TO VERIFY EGRESS CONTROL FOR |
| | LTS. |
| | 210.70, LS 101 7.8 |
| | |
| | 6) NOTE: OK. |
| | |
| | 7) NOTE: OK. |
| | |
| | 8) NOTE: NO, COULD NOT LOCATE ON PANEL |
| | SCHEDULE. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE INDICATE THE NEW OR |
| | EXISTING BATH GFI RECEPTS PER 210.52D, |
| | 210.8A |
| | |
| | 9) NOTE: OK. |
| | |
| | 10) NOTE: NO, PLEASE SEE SAME NOTE. |
| | CODES RELEVANT TO DESIGN/SCOPE AND PLANS |
| | IS REQUIRED ON PLANS. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE THAT PLANS REFLECT |
| | THE FOLLOWING CODES AT A MIN. |
| | 2002 NFPA-70, 2002 NFPA-72, |
| | |
| | ***** NEW NOTE **** |
| | |
| | 11) NOTE: PLEASE COMPLETE PANEL SCHEDULE |
| | WITH ALL OCP FOR BRANCH CIRCUITS ALONG |
| | WITH MIN CONDUCTORS PER 240.4,310.16 |
| | |
| | 12) NOTE: PLEASE SEE ONLY ONE SMALL |
| | APPLIANCE CIRCUIT IS BEING SHOWN IN LOAD |
| | CALCULATIONS. |
| | PLEASE SEE 210.52B1,210.11C1,220.16 |
| | |
| | 13) NOTE: PLEASE SEE |
| | 210.52B1,220.11C1,220.16 FOR MIN |
| | CIRCUITING FOR DINING RM CIRCUIT(S). |
| | PLEASE ADJUST. |
| | |
| | 14) NOTE: PLEASE SEE FBC 106.1.2, PLEASE |
| | BE SURE THE PERSON RESPONSIBLE FOR PLANS |
| | AND DESIGN CLEARLY PRINTS NAME AND SIGNS |
| | PLANS . |
| | |
| | |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |
| | |