Plan Review Notes
Plan Review Notes For Permit 06070128
Permit Number 06070128
Review Stop E
Sequence Number 2
Notes
Date Text
2006-08-27 00:00:00**** UNSAT2ND REVIEW ****
  
 ** PLEASE SEE SOME COMMENTS FROM PREVOUS
 REVIEW STILL NEED TO BE ADDRESSED ALONG
 WITH NEW COMMENTS DUE TO
 INFORMATION/CHANGES MADE ON PLANS.
 PLEASE SEE NOTE BWLOW ARE TAKEN DIRECTLY
 FROM PREVIOUS REVIEW AS NOTED WITH NEW
 NOTES ADDED TO BOTTOM.
  
 ** PLEASE SEE THE FOLLOWING COMMENTS,
 AND PLEASE KNOW, IT IS RECOMMENED
 ELECTRICAL BE DONE ON A SEPARATE SHEET
 AS THE OTHER REVIEWS HAVE BEEN STAMPED
 AND PASSED.
  
 1) NOTE: NO, PLEASE SEE CIRCUITING IS
 NOT YET ON PLANS WHICH CORRELATES WITH
 THE PANEL SCHEDULE SUBMITTED.
 PLEASE KNOW ALL CIRCUITS SHALL BE
 SPECIFIC TO ROOMS AND AREAS.408.4
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH A PANEL
 SCHEDULE TO BE SUBMITTED.
 PLEASE LIST ALL THE MIN REQUIRED
 DEDICATED CIRCUITS PER
 210.52,210.11,220.16 ETC
 BATH(S), SM APPL, RANGE, DISH WASHER ,
 DISP, ETYC. PLEASE SEE 240.4,310.16, FBC
 106.1.2 ADMIN SECT.
  
 2) NOTE: OK.
  
 3) NOTE: OK.
  
 4) NOTE: OK, HOWEVER NEW JACUZZI TUB IS
 SHOWN ON PLANS WITH GFI, HOWEVER THIS
 JACUZZI IS NOT ON PANEL SCHEDULE OR IN
 LOAD CALCULATIONS?
 220.31
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE A NEW JACUZZI TUB IS
 NOTED, HOWEVER NO ELECTRICAL IS SHOWN
 FOR THIS AND NO GFI PROTECTION IS
 INDICATED.
 680.71, 240.4,310.16 ETC.
  
 5) NOTE: NO, PLEASE SEE BEDRM.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE COMPLETE SW LEGS FOR NEW
 LTS SHOWN TO VERIFY EGRESS CONTROL FOR
 LTS.
 210.70, LS 101 7.8
  
 6) NOTE: OK.
  
 7) NOTE: OK.
  
 8) NOTE: NO, COULD NOT LOCATE ON PANEL
 SCHEDULE.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE INDICATE THE NEW OR
 EXISTING BATH GFI RECEPTS PER 210.52D,
 210.8A
  
 9) NOTE: OK.
  
 10) NOTE: NO, PLEASE SEE SAME NOTE.
 CODES RELEVANT TO DESIGN/SCOPE AND PLANS
 IS REQUIRED ON PLANS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE THAT PLANS REFLECT
 THE FOLLOWING CODES AT A MIN.
 2002 NFPA-70, 2002 NFPA-72,
  
 ***** NEW NOTE ****
  
 11) NOTE: PLEASE COMPLETE PANEL SCHEDULE
 WITH ALL OCP FOR BRANCH CIRCUITS ALONG
 WITH MIN CONDUCTORS PER 240.4,310.16
  
 12) NOTE: PLEASE SEE ONLY ONE SMALL
 APPLIANCE CIRCUIT IS BEING SHOWN IN LOAD
 CALCULATIONS.
 PLEASE SEE 210.52B1,210.11C1,220.16
  
 13) NOTE: PLEASE SEE
 210.52B1,220.11C1,220.16 FOR MIN
 CIRCUITING FOR DINING RM CIRCUIT(S).
 PLEASE ADJUST.
  
 14) NOTE: PLEASE SEE FBC 106.1.2, PLEASE
 BE SURE THE PERSON RESPONSIBLE FOR PLANS
 AND DESIGN CLEARLY PRINTS NAME AND SIGNS
 PLANS .
  
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  
  