| 2006-07-15 00:00:00 | **** UNSAT **** |
| | |
| | ** PLEASE SEE THE FOLLOWING COMMENTS, |
| | AND PLEASE KNOW, IT IS RECOMMENED |
| | ELECTRICLA BE DONE ON A SEPARATE SHEET |
| | AS THE OTHER REVIEWS HAVE BEEN STAMPED |
| | AND PASSED. |
| | |
| | 1) NOTE: PLEASE SHOW ALL CIRCUITING ON |
| | PLANS AND CORRELATE WITH A PANEL |
| | SCHEDULE TO BE SUBMITTED. |
| | PLEASE LIST ALL THE MIN REQUIRED |
| | DEDICATED CIRCUITS PER |
| | 210.52,210.11,220.16 ETC |
| | BATH(S), SM APPL, RANGE, DISH WASHER , |
| | DISP, ETYC. PLEASE SEE 240.4,310.16, FBC |
| | 106.1.2 ADMIN SECT. |
| | |
| | 2) NOTE: PLEASE LIST THE REQUIRED ARC |
| | FAULT FOR NEW SD'S BEING ADDED. 210.12B, |
| | 2002 NEC. |
| | |
| | 3) NOTE: PLEASE SEE SD SEEM TO BE |
| | MISSING OUTSIDE MAST BEDRM.? |
| | R313, NFPA-72 11.5.1.1 |
| | ** PLEASE KNOW, ALL SD'S SHALL BE A MIN |
| | OF 3' FROM ALL BATH AND KITCHEN DOORS |
| | AND IF WITHIN 20' OF COOKING APPLIANCE, |
| | THE SD SHALL BE PHOTO-ELECTRIC |
| | EYE/RESETTING TYPE> |
| | NFPA-72 11.8.3 |
| | |
| | 4) NOTE: PLEASE SEE A NEW JACUZZI TUB IS |
| | NOTED, HOWEVER NO ELECTRICAL IS SHOWN |
| | FOR THIS AND NO GFI PROTECTION IS |
| | INDICATED. |
| | 680.71, 240.4,310.16 ETC. |
| | |
| | 5) NOTE: PLEASE COMPLETE SW LEGS FOR NEW |
| | LTS SHOWN TO VERIFY EGRESS CONTROL FOR |
| | LTS. |
| | 210.70, LS 101 7.8 |
| | |
| | 6) NOTE: PLEASE SEE BATHS SHALL CONTAIN |
| | A "LIGHTING OUTLET" AS REQUIRED PER |
| | 210.70. AN EXHAUST FAN WITH A LT IS NOT |
| | A LIGHTING OUTLET. |
| | 100 |
| | |
| | 7) NOTE: PLEASE SHOW THE LOCATION OF THE |
| | ELECTRICLA PANEL AND IF NEW OR EXISTING. |
| | PLEASE BE SURE TO SEE |
| | 110.26,408.7,240.24 FOR PERMITTED |
| | LOCATIONS AND MIN CLEARENCES REQUIRED. |
| | |
| | 8) NOTE: PLEASE INDICATE THE NEW OR |
| | EXISTING BATH GFI RECEPTS PER 210.52D, |
| | 210.8A |
| | |
| | 9) NOTE: PLEASE INDICATE ALL RECEPTS |
| | SERVING KITCHEN COUNTER SPACE AS GFI/GFI |
| | PROTECTEDPER 210.8A6. |
| | AS SHOWN IS FROM THE 1993 NEC. |
| | |
| | 10) NOTE: PLEASE SEE THAT PLANS REFLECT |
| | THE FOLLOWING CODES AT A MIN. |
| | 2002 NFPA-70, 2002 NFPA-72, |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |
| | |