Plan Review Notes
Plan Review Notes For Permit 06070127
Permit Number 06070127
Review Stop B
Sequence Number 1
Notes
Date Text
2006-07-28 00:00:00 
 1) THE PRODUCT APPROVALS FOR THE ROOF
 TILES ARE EXPIRED. SUBMIT APPROVED AND
 UP-DATED PRODUCT APPROVALS FOR THE
 ROOFING TILES. SEE
 WWW.FLORIDABUILDING.ORG FOR NEW AND
 UP-DATED PRODUCT APPROVALS.
  
 2) THE CLAIMED VALUATION ON THE PERMIT
 APPLICATION IS LOW. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT
 COST EXCLUDING LAND VALUE. OUR VALUATION
 REFERENCE IS ICC (BVD) MARSHALL-SWIFT
 AND MEANS COST ANALYSIS SERVICES PER
 108.3* FBC.
  
 3) SHOW THE SIZE OF THE EXISTING
 CONCRETE FOOTING AND THE NEW FOOTING IF
 ONE WILL BE INSTALLED.
  
 F.S 489.113 (3)
 (B)A GENERAL, BUILDING, OR RESIDENTIAL
 CONTRACTOR SHALL NOT BE REQUIRED TO
 SUBCONTRACT THE INSTALLATION, OR REPAIR
 MADE UNDER WARRANTY, OF WOOD SHINGLES,
 WOOD SHAKES, OR ASPHALT OR FIBERGLASS
 SHINGLE ROOFING MATERIALS ON A NEW
 BUILDING OF HIS OR HER OWN CONSTRUCTION.
 THEREFORE, A ROOFING CONTRACTOR IS
 REQUIRED TO DO THE TILE ROOF.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER