| Plan Review Notes For Permit 06070122 |
| Permit Number |
06070122 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-07-14 00:00:00 | *** DENIED *** | | | 1) CONDENSER UNIT APPEARS TO CLOSE TO | | | THE PROPERTY LINE, SEE ZONING REVIEW | | | NOTES. | | | | | | 2) PLEASE SUBMIT ENERGY CALCULATIONS | | | SHORT FORM, PER 2004 FBC 13--101.4.1 . | | | | | | 3) PLEASE SUBMITMANUAL J CALCULATIONS, | | | PER 2004 FBC 13-607.1.ABC.1 . | | | | | | 4) ALL INFORMATION, DRAWINGS, | | | SPECIFICATIONS AND ACCOMPANYING DATA | | | SHALL BEAR THE NAME AND SIGNATURE OF THE | | | PERSON RESPONSIBLE FOR THE DESIGN. PER | | | FBC 104.2.1 . (PRINTED NAME). | | | | | | 5) PLEASE SHOW ON MECHANICAL PLANS TOTAL | | | BTU'S AND SENSIBLE BTU'S. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|