| 2006-08-23 00:00:00 | **** UNSAT 2ND REVIEW **** |
| | |
| | ** PLEASE SEE SOME COMMENTS FROM |
| | PREVIOUS REVIEW AND SOME NEW COMMENTS |
| | DUE TO CHANGES IN PLANS. |
| | COMMENTS BELOW ARE TAKEN DIRECTLY FROM |
| | PREVIOUS REVIEW AND THEN NEW COMMENTS |
| | ARE ADDED TO BOTTOM. |
| | |
| | |
| | ***** UNSAT ***** |
| | |
| | ** PLEASE KNOW, DUE TO THE EXTENT OF |
| | COMMENTS AND SOME ITEMS NOT COMPLETE AT |
| | THIS TIME, THERE MAY BE COMMENTS OTHER |
| | THAN BELOW ON THE NEXT REVIEW. |
| | |
| | |
| | 1) NOTE: OK. |
| | |
| | 2) NOTE: OK. |
| | |
| | 3) NOTE: OK. |
| | |
| | 4) NOTE: NO, PLEASE SEE SOME ITEMS WERE |
| | ADDED AND SOME WERE CORRECTED, HOWEVER |
| | PLEASE SEE LOAD CALCULATIONS. PLEASE |
| | KNOW, THE LARGER OF THE TWO LOADS OF AN |
| | A/C CU AND AHU SHOULD BE FIGURED INTO |
| | THE LOAD CALCULATIONS. PLEASE SEE CU'S |
| | WITH LOADS LESS THAN HEAT BEING SHOWN. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE CORRELATE PLANS, PANEL |
| | SCHEDULES AND LOAD CALCULATIONS. |
| | PLEASE SEE PLANS, SHOW MORE A/C SYSTEMS |
| | THAN IN PANEL SCHEDULES OR LOAD CALCS. |
| | PLEASE SEE ONLY ONE CU IS SHOWN ON |
| | PLANS, PLEASE SEE 3- AHU'S?? |
| | 106.1.2, 440.11 ETC |
| | |
| | 5) NOTE: OK. |
| | |
| | 6) NOTE OK. |
| | |
| | 7) NOTE: OK, HOWEVER SEE NEW NOTES A |
| | COMPLETELY NEW RISER WAS SUBMITTED. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE VERIFY THE SIZE OF MAIN |
| | AND METER, AS THE 320A OF METER AND THE |
| | LOADS CALCS AFTER DERATINGS, EXCEED |
| | THIS? |
| | PLEASE ADJUST AND INCREASE SIZE OF |
| | EQUIPMENT AS REQUIRED. |
| | 230.70,240 ETC. |
| | |
| | 8) NOTE: OK, HOWEVER SEE NOTE PERTAINING |
| | TO A/C LOADS. |
| | |
| | 9) NOTE: OK. |
| | |
| | 10) NOTE: OK. |
| | |
| | 11) NOTE: OK, STAIRS REMOVED. |
| | |
| | 12) NOTE: OK, STAIRS REMOVED. |
| | |
| | 13) NOTE: NO, PLEASE SEE SPECIFIC ROOMS |
| | AND AREAS ARE NOT LISTED ON PLANS. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SUBMIT AND COMPLETE THE |
| | PANEL SCHEDULES INDICATING ALL |
| | CIRCUITS, WIRE SIZES, AND OCP FOR EACH. |
| | CIRCUITS SHALL BE SPECIFIC TO RMS AND |
| | AREAS. |
| | 408.4, 240.4, 310.16 ETC. |
| | PLEASE SEE NOTES ABOVE AS MANY ITEMS ON |
| | PLANS, DO NOT MATCH. |
| | |
| | 14) NOTE: NO, PLANS ONLY PROVIDE NOTES |
| | FOR WHERE THESE ARE GOING TO BE. NO |
| | DISCONNECTS, CLEARANCES, ACCESS IS BEING |
| | SHOWN. PLEASE SEE CODES BELOW AS |
| | CLEARANCES ETC CAN NOT BE VERIFIED. |
| | PLEASE SEE 240.24D ETC. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE INDICATE ALL EQUIPMENT |
| | ON PLANS FOR STEAM UNITS, ELEVATOR |
| | EQUIPMENT, DISCONNECTS, LT'S, GFI ETC. |
| | UNABLE TO REVIEW LOCATIONS FOR CODE |
| | COMPLIANCE AT THIS TIME. |
| | 110.26,240.4.240.24 ETC |
| | |
| | 15) NOTE: OK. |
| | |
| | 16) NOTE: OK. |
| | |
| | 17) NOTE: NO, THESE COULD NOT BE LOCATED |
| | ON PLANS OR SUBMITTED IN PACKAGES. |
| | NEED TO VERIFY MIN CLEARANCES ETC. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SUBMIT MANUFACTURES |
| | SPECS/ CUT SHEETS FOR ELEVATOR EQUIPMENT |
| | AND FOR STEAM UNIT EQUIPMENT. ALL SHALL |
| | INDICATE A LISTING FROM A NRTL. |
| | 110.3, 106.1.2* |
| | |
| | 18) NOTE: OK. |
| | |
| | 19) NOTE: OK. |
| | |
| | 20) NOTE:NO, PLEASE SEE A DINING RM |
| | CIRCUIT WAS ADDED ON PANEL SCHEDULE |
| | WHICH IS OK, HOWEVER IF THIS IS A |
| | DEDICATED CIRCUIT, THEN PLEASE SEE |
| | 210.11C1, 220.16 FOR MIN VA TO BE |
| | FIGURED FOR THIS CIRCUIT. |
| | 7-SM APPL CIRCUITS ARE LISTED ON PANEL |
| | SCHEDULE AND 7- SHOWN IN LOAD CALCS. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE 210.52B1, |
| | 210.11C1,220.16, DINING RM CIRCUIT SHALL |
| | BE INDICATED AS NOTED. |
| | |
| | 21) NOTE: OK. |
| | |
| | 22) NOTE:NO, PLEASE SEE DISCONNECT FOR |
| | CU OUTSIDE NOW, HAS BEEN MOVED BEHIND |
| | UNIT. THIS WAS SHOWN W/ CORRECT |
| | CLEARANCES ON PREVIOUS PLANS. |
| | PLEASE CLARIFY THE DISC'S FOR AHU'S. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE 110.26 FOR MIN |
| | CLEARANCES FOR AHU'S AND DISCONNECTS. |
| | |
| | 23) NOTE: OK. |
| | |
| | 24) NOTE: OK, PLEASE BE SURE ANY REVISED |
| | PLANS ARE ALSO SIGNED, ETC. |
| | |
| | 25) NOTE: OK, PLEASE BE SURE TO DO THE |
| | SAME WHEN RESUBMITTING. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | ** IMPORTANT** |
| | PLEASE KNOW, ONCE ALL REVIEWS ARE DONE |
| | AND BEFORE RESUBMITTING PLANS. PLEAS BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS FROM SETS AND ONLY INSERT NEW |
| | REVISED SHEETS INTO TWO COMPLETE SETS |
| | FOR REVIEW AND STAMPING. ONLY ONE COPY |
| | OF THE OLD/VOIDED REMOVED SHEETS SHOULD |
| | BE SUBMITTED FOR REFERENCE. |
| | PLEASE KNOW, THIS WILL HELP TO |
| | ALLEVIATE ANY DELAYS INT THE PROCESSING |
| | OF PROJECT FOR PERMIT. |
| | |
| | ***** NEW NOTES ****** |
| | |
| | 26 ) NOTE: PLEASE SEE RISER DIAGRAM HAS |
| | NOW BEEN COMPLETELY REVISED. |
| | PLEASE SEE PLANS DO NOT SHOW THE |
| | LOCATION OF THIS NEW 400A MAIN. PLEASE |
| | SEE ALL MCB'S ARE BEING SHOWN AS BEING |
| | TAPPED FROM THIS ONE MAIN. PLEASE VERIFY |
| | TAPPED CONDUCTORS RULE W/ 240.21 |
| | DEPENDING ON WHERE MAIN IS LOCATED. |
| | (VERIFY THE LUGS AVAILABLE FOR THREE |
| | CONDUCTORS, ONLY NOTED) |
| | |
| | 27) NOTE: PLEASE SEE ITEMS WHICH ARE NOW |
| | HAND WRITTEN ON RISER AND PLANS WHICH IS |
| | NOT PERMITTED. THESE ITEMS SHOULD BE |
| | PRINTED WHEN PLANS ARE RE-PRINTED. |
| | FBC ADMIN SECT 106.1 |
| | |
| | 28) NOTE: PLEASE SEE NOW THAT RISER HAS |
| | BEEN REVISED, PLEASE SEE MISSING |
| | "EQUIPMENT GROUNDING CONDUCTORS" FROM |
| | THE MAIN TO THE SUB-PANELS. |
| | PLEASE SEE 250.24B, 250.110, AND TABLES |
| | IN 250.122 FOR SIZING. |
| | |
| | 29) NOTE: PLEASE SEE MISSING CONNECTIONS |
| | FOR GROUNDING ELECTRODE SYSTEM TO BE |
| | COLD WATER PIPE (IF METAL), NEW FOOTER |
| | STEEL AND ANY OTHER SYSTEMS BEING |
| | PROVIDED. PLEASE SHOW ON RISER. |
| | 250.50 |
| | THIS WAS NOT IN PREVIOUS REVIEW NOTES |
| | |
| | 30) NOTE: PLEASE SEE POOL PUMP AND POOL |
| | HEATER SHOULD BE NOTED AS (FUTURE) SINCE |
| | THESE ARE NOT SHOWN ON PLANS AND POOL IS |
| | NOT PERMITTED AT THIS TIME. |
| | |
| | 31) NOTE: PLEASE SEEFS 553.80(2)(B) |
| | WITH RESPECT TO REPEAT COMMENTS. |
| | THIS IS ONLY A NOTICE. |
| | |
| | |
| | *** PLEASE SEE NOTE AS FIRST MENTIONED. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |