| 2006-07-08 00:00:00 | |
| | ***** UNSAT ***** |
| | |
| | ** PLEASE KNOW, DUE TO THE EXTENT OF |
| | COMMENTS AND SOME ITEMS NOT COMPLETE AT |
| | THIS TIME, THERE MAY BE COMMENTS OTHER |
| | THAN BELOW ON THE NEXT REVIEW. |
| | |
| | |
| | 1) NOTE: PLEASE SEE 210.52 FOR RECEPT |
| | SPACING. PLEASE SEE MANY LOCATIONS ON |
| | PLANS.2',6',12' RULE. |
| | |
| | 2) NOTE: PLEASE SEE MISSING RECEPTS FOR |
| | KITCHEN ISLAND, FOR ALL ELECTRICAL |
| | APPLIANCES, COUNTERSPACE ETC. PLEASE |
| | COMPLETE. |
| | PLEASE SEE 210.52C1-5, 210.8A6, FBC |
| | ADMIN SECT 106.1.2 |
| | |
| | 3) NOTE: PLEASE KNOW, SD'S SHALL BE |
| | LOCATED WITH IN 3' OF THE PEAK ON A |
| | SLPOED CEILING AND SHALL BE WITHIN 12" |
| | OF THE HIGHEST POINT ON A FLAT CEILING. |
| | NFPA-72 11.8.3 |
| | PLEASE ALSO SEE AREAS WHICH REQUIRE |
| | SD'S IN THE IMMEDIATE VICINITY OUTSIDE |
| | ALL SLEEPING RMS. |
| | 11.5.1.1 |
| | |
| | 4) NOTE: PLEASE CORRELATE PLANS, PANEL |
| | SCHEDULES AND LOAD CALCULATIONS. |
| | PLEASE SEE PLANS, SHOW MORE A/C SYSTEMS |
| | THAN IN PANEL SCHEDULES OR LOAD CALCS. |
| | PLEASE SEE ONLY ONE CU IS SHOWN ON |
| | PLANS, PLEASE SEE 3- AHU'S?? |
| | 106.1.2, 440.11 ETC |
| | |
| | 5) NOTE: PLEASE SEE MISSING GFI RECEPT |
| | PER 210.6 FOR CU'S. |
| | |
| | 6) NOTE PLEASE PROVIDE AIC RATINGS FOR |
| | MAIN(S). 110.9, ONLY SHOWN FOR SUB |
| | PANELS AND THE SERIES RATINGS. |
| | |
| | 7) NOTE: PLEASE VERIFY THE SIZE OF MAIN |
| | AND METER, AS THE 320A OF METER AND THE |
| | LOADS CALCS AFETR DERATINGS, EXCEED |
| | THIS? |
| | PLEASE ADJUST AND INCREASE SIZE OF |
| | EQUIPMENT AS REQUIRED. |
| | 230.70,240 ETC. |
| | |
| | 8) NOTE: PLEASE CORRLEATE PLANS, PANELS, |
| | AND LOAD CALCS. PLEASE SEE PLANS |
| | INDICATE MORE THAN ONE WASHER AND DRYER. |
| | ADJUST AS REQUIRED. |
| | 220.31, 215.5, 310.16, *106.1.2 |
| | |
| | 9) NOTE: PLEASE SEE LOADS SHOWN FOR |
| | WATER HEATER EXCEED BRANCH CIRCUIT |
| | RATING. 9KW? ON 30A BRKR? |
| | 240.4,310.16, 240, 220 ETC |
| | |
| | 10) NOTE: PLEASE SEE LOAD FOR STEAM UNIT |
| | EXCEEDS BRANCH CIRCUIT RATING FOR THE |
| | 1-POLE 40A BRKR. |
| | 240.4,310.16,240.,220 ETC |
| | |
| | 11) NOTE: PLEASE PROVIDE AN ELEVATION OF |
| | ELECTRICAL SERVICE INCORPORATED WITH |
| | STAIRS ON OUTSIDE WALL. |
| | PLEASE SEE 110.26 AND MIN CLEARNECES |
| | REQUIRED BY FPL FOR LOCATION AS SHOWN. |
| | |
| | 12) NOTE: PLEASE SEE MISSING EGRESS |
| | LIGHTING CONTROL REQUIRED FOR OUTSIDE |
| | STAIRS AT LOWER LEVEL. (3-WAY). LS 101 |
| | 7.8, NEC 210.70 |
| | |
| | 13) NOTE: PLEASE SUBMIT AND COMPLETE THE |
| | PANEL SCHEDULES INDICATTING ALL |
| | CIRCUITS, WIRE SIZES, AND OCP FOR EACH. |
| | CIRCUITS SHALL BE SPECIFIC TO RMS AND |
| | AREAS. |
| | 408.4, 240.4, 310.16 ETC. |
| | PLEASE SEE NOTES ABOVE AS MANY ITEMS ON |
| | PLANS, DO NOT MATCH. |
| | |
| | 14) NOTE: PLEASE INDICATE ALL EQUIPMENT |
| | ON PLANS FOR STEAN UNITS, ELEVATOR |
| | EQUIPMENT, DISCONNECTS, LTS, GFI ETC. |
| | UNABLE TO REVIEW LOCATIONS FOR CODE |
| | COMPLIANCE AT THIS TIME. |
| | 110.26,240.4.240.24 ETC |
| | |
| | 15) NOTE: PLEASE SEE 220.3B4. |
| | PLEASE SHOW ALL RECESSED LTS BASED ON |
| | MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT |
| | BE FIGURED IN W/ 3W/PER SQ FT. |
| | PLEASE PROVIDE FIXTURE INFORMATION ON |
| | LEGEND. |
| | |
| | 16) NOTE: PLEASE SEE ENERGY CALCS |
| | SHALLBE SIGNED , DATED AND SEALED. |
| | PLEASE SEE FBC CHAPTER 13 |
| | FS 481.221, 471.023 |
| | |
| | 17) NOTE: PLEASE SUBMIT MANUFACTURES |
| | SPECS/ CUT SHEETS FOR ELEVATOR EQUIPMENT |
| | AND FOR STEAM UNIT EQUIPMENT. ALL SHALL |
| | INDICATE A LISTING FROM A NRTL. |
| | 110.3, 106.1.2* |
| | |
| | 18) NOTE: PLEASE CLARIFY EXTERIOR LTS ON |
| | A 220V CIRCUIT?? |
| | 310.16, 220.,240.4 ETC |
| | |
| | 19) NOTE: PLEASE INDICATE THE DEDICATED |
| | BATH(S) CIRCUIT(S0 PER 210.52D,210.11C3, |
| | MUST BE 20A AND #12. |
| | |
| | 20) NOTE: PLEASE SEE 210.52B1, |
| | 210.11C1,220.16, DINING RM CIRCUIT SHALL |
| | BE INDICATED AS NOTED. |
| | |
| | 21) NOTE: PLEASE SEE PLANS NOTE ARC |
| | FAULT FOR WALL OUTLETS, THIS HAS CHANGED |
| | IN THE 2002 NEC, WHICH WENT INTO EFFECT |
| | 7/1/2003. |
| | ALL OUTLETS" , IN BEDRMS SHALL BE |
| | PROTECTED. , LTS, RECEPTS, FANS, SD'S |
| | ETC. |
| | PLEASE LIST ALL THE ARC FAULT PROTECTED |
| | CIRCUITS ON PANEL SCHEDULE. A NOT IS NOT |
| | SUFFICIENT. |
| | 210.12B, 408.4 |
| | |
| | 22) NOTE: PLEASE SEE 110.26 FOR MIN |
| | CLEARENCES FOR AHU'S AND DISCONNECTS. |
| | |
| | 23) NOTE: PLEASE SEE PLANS SHALL |
| | INDICATE THE 2002 NEC. |
| | |
| | 24) NOTE: PLEASE SEE PLANS ARE NOT |
| | SIGNED, SEALED , OR DO NOT CONTAIN A |
| | TITLE BLOCK FOR PERSON RESPONSIBLE FOR |
| | PLASN AND DESIGN. |
| | PLEASE SEE THAT PLANS SHALL CLEARLY |
| | CONTAIN THE PRINTED NAME AND SIGNATURE |
| | OF THE PERSON RESPONSIBEL FOR PLANS AND |
| | DESIGN. PLEASE SEE 106 FBC AND FS 481, |
| | 471, 468 FOR PERSON PERMITTED TO DO |
| | SCOPE PF WORK AS SHOWN. |
| | |
| | 25) NOTE: ** IMPORTANT** |
| | PLEASE KNOW, ONCE ALL REVIEWS ARE DONE |
| | AND BEFORE RESUBMITTING PLANS. PLEAS BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS FROM SETS AND ONLY INSERT NEW |
| | REVISED SHEETS INTO TWO COMPLETE SETS |
| | FOR REVIEW AND STAMPING. ONLY ONE COPY |
| | OF THE OLD/VOIDED REMOVED SHEETS SHOULD |
| | BE SUBMITTED FOR REFERENCE. |
| | PLEASE KNOW, THIS WILL HELP TO |
| | ALLEAVIATE ANY DELAYS INT THE PROCESSING |
| | OF PROJECT FOR PERMIT. |
| | |
| | |
| | *** PLEASE SEE NOTE AS FIRST MENTIONED. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |