| Date |
Text |
| 2006-07-12 00:00:00 | *** DENIED *** |
| | 1) OPEN FLOOR DRAINS CAN NOT BE IN A |
| | MECHANICAL ROOM THAT IS AN OPEN PLENUM, |
| | PER 2004 FBC/P 901.2, FBC/M 601.3, AND |
| | ASHARE 8.4.1.11 . |
| | |
| | 2) PLANS THAT HAVE AN ENGINEER'S SEAL ON |
| | THEM MUST ALSO HAVE THE ENGINEER'S |
| | PRINTED NAME, ADDRESS, AND LICENSE |
| | NUMBER ON EACH SHEET, PER FAC |
| | 61G15-23.002 . |
| | |
| | 3) PLEASE HAVE JOB ADDRESS ADDED TO |
| | TITLE BLOCK, PER 2004 FBC 106.1.1 . |
| | |
| | 4) PLEASE SHOW SIZE OF ALL RETURN AIR |
| | TRANSFER DUCTS, SEE NOTE #5 (A). |
| | |
| | 5) BALANCED RETURN AIR. |
| | THIS MAY BE ACHIEVED BY. |
| | (A)TRANSFER DUCTS MAY ACHIEVE THIS BY |
| | INCREASING THE RETURN TRANSFER ONE AND |
| | ONE HALF TIMES THE CROSS SECTIONAL AREA |
| | (SQUARE INCHES) OF THE SUPPLY DUCT |
| | ENTERING THE ROOM OR SPACE IT'S SERVING |
| | AND THE DOOR HAVING AT LEAST AN |
| | UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE |
| | PROPER RETURN AIR BALANCE. |
| | (B)TRANSFER GRILLES SHALL USE 50 |
| | SQUARE INCHES (OF GRILLE AREA) TO 100 |
| | CFM (OF SUPPLY AIR) FOR SIZING |
| | THROUGH-THE-WALL TRANSFER GRILLES AND |
| | USING AN UNRESTRICTED 1-INCH |
| | UNDERCUTTING OF DOORS TO ACHIEVE PROPER |
| | RETURN AIR BALANCE |
| | (C)HABITABLE ROOMS ONLY SHALL BE |
| | REQUIRED TO MEET THESE REQUIREMENTS FOR |
| | PROPER BALANCED RETURN AIR EXCLUDING |
| | BATHROOMS, CLOSETS, STORAGE ROOMS AND |
| | LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY |
| | AIR INTO THE MASTER SUITE SHALL BE |
| | INCLUDED. PER 2004 FBC/R M1602.4 . |
| | |
| | MECHANICAL PLAN REVIEW BY; |
| | TOM GORDON (561) 805-6729. |