| Date |
Text |
| 2006-07-21 00:00:00 | *** UNSAT *** |
| | |
| | 1) NOTE: PLEASE SEE ADDRESS IS FOR |
| | "OKEECHOBEE RD" PLEASE KNOW, LEGALLY |
| | THERE IS NOT 'OLD " OKEECHOBEE IN THE |
| | CITY OF WEST PALM BEACH. |
| | PLEASE PLACE ADDRESS ON PLANS. |
| | 1259 OKEECHOBEE RD. |
| | |
| | 2) NOTE: PLEASE SEE RISER DIAGRAM SHOWN A |
| | SE RATED ATS , HOWEVER PLEASE SEE SPEC |
| | SUBMITTED ARE HIGH LIGHTED FOR A NON-SSE |
| | RATED ATS.? |
| | PLEASE CLARIFY. |
| | PLEASE ALSO CLARIFY OF THE EXISTING MAIN |
| | SHOWN ON RISER IS NEXT TO OR GROUPED IN |
| | CLOSE PROXIMITY TO NEW ATS/ SE RATED |
| | MAIN. |
| | 230.72,225.34 |
| | 110.3,90.7 |
| | |
| | 3) NOTE: PLEASE SEE AN "EQUIPMENT |
| | GROUNDING CONDUCTOR IS BEING SHOWN FROM |
| | METER TO THE FIRST MEANS OF DISCONNET, |
| | HOWEVER PER 250.6,250.24, ONLY AFTER THE |
| | FIRST MEANS OF DISCONNECT, DOES AN |
| | EQUIPMENT GROUNDING CONDUCTOR GET |
| | INSTALLED. |
| | |
| | 4) NOTE: PLEASE KNOW, AS PER INFORMATION |
| | OBTAINED BY THE OFFICE, THE MIN |
| | CLEARENCES FOR THESE TYPE OF GEN SHOULD |
| | BE 5' FROM ALL WALLS BLDGS ETC. PLEASE |
| | KNOW, IF INFORMATION IS NOT THE SAME |
| | PLEASE PROVIDE SPECIFIC DISTANCES |
| | REQUIRED BY MANUFACTURE. |
| | |
| | 5) NOTE: PLEASE VERIFY AIC RATINGS. |
| | 702.6,110.9 ETC. |
| | |
| | 6) NOTE: PLEASE SEE THAT SURVEY/ SITE |
| | PLAN SHALL NOT CONTAIN HANDWRITTEN, PEN |
| | OR PENCILED PLANS. |
| | PLEASE REPRINT AND COPY IF NEEDED. |
| | FBC 106.1.2,1.3 |
| | |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |