| Date |
Text |
| 2006-11-14 16:21:24 | **** UNSAT ***** |
| | |
| | **PLEASE SEE RISER(S) HAVE NOW BEEN COMPLETELY REVISED |
| | FROM ORIGINAL STAMPED PLANS. PLEASE SEE NEW COMMENTS |
| | BELOW BASED ON RISERS NOW SUBMITTED. |
| | |
| | |
| | 1) NOTE: PLEASE SEE SEC?S ARE NOW BEING SHOWN AS #1?S |
| | WITH 200A OCP WHICH IS NOT PERMITTED. |
| | PLEASE SEE 240.4, 310.16 230.70, 240.20 ETC. |
| | |
| | 2) NOTE: PLEASE SEE 200A BREAKERS FEEDING 150A RATED |
| | PANELS WHICH ARE ALSO NOT PERMITTED. |
| | PLEASE SEE THE NEC 230, 240, 408 ETC |
| | |
| | 3) NOTE: PLEASE SEE RISER WHICH INDICATES AN EQUIPMENT |
| | GROUNDING CONDUCTOR FROM THE METER TO THE FIRST MEANS |
| | OF DISCONNECT WHICH IS NOT PERMITTED. |
| | PLEASE SEE 250.6, 250.24B. |
| | |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | **PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. |
| | **IF THERE ARE ANY QUESTIONS, COMMENTSOR IF ANY OF |
| | THE NOTES TYPEDWHICH ARE UNCLEAR IN ANY WAY, PLEASE |
| | DO NOT HESITATEIN CONTACTING THIS REVIEWER. |
| | |
| | |
| | |
| | |