Plan Review Notes
Plan Review Notes For Permit 06070079
Permit Number 06070079
Review Stop E
Sequence Number 2
Notes
Date Text
2006-08-07 00:00:00***** UNSAT ******
  
 1) NOTE: NO, PLEASE SEE RISER WAS NOT
 REVISED TO SHOW CONDUITS, PLEASE SEE ONE
 CONDUIT FROM THE METERCAN SEEM TO SHOW
 RUNNING THROUGH ONE ATS TO GET TO THE
 OTHER? PLEASE SEE PREVIOUS NOTES WITH
 REPECT TO USING THIS ATS AS A RACEWAY
 FOR SEC'S.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE RISER DOES NOT
 INDICATE THE CONDUITS FROM THE ATS'S TO
 THE EXISTING PANELS. MAY NOT RUN FEEDERS
 BACK THROUGH METER CAN.
 230.7, 408 ETC.
 MAY NOT HAVE LINE AND LOAD IN THE SAME
 RACEWAY OR ENCLOSURE.
 PLEASE KNOW, RISER WILL SUBSTANTIALLY
 CHANGE FROM SUBMITTED PLANS.
  
 2) NOTE:NO, PLEASE SEE A LAYOUT WAS
 PROIVIDED, HOWEVER PLEASE SEE MISSING
 DISCONNECTING MEANS FOR FEEDERS FROM
 GENERATOR. PLEASE SEE THIS DISCONNECT
 DOES NOT REQUIRE OCP, ONLY A DISCONNECT
 RATED FOR THE LOAD SERVED AND GROUPED
 WIHT THE EXISTING (NEW) MAINS. PLEASE
 SEE THIS MAY BE PALCED ON FEEDER CONDUIT
 BEFORE THE ATS OR TWO DISCOONECTS WOULD
 BE REQUIRED AFTER THE ATS GOING INTO
 HOUSE. A 200A RATED DISCONNECT SEEMS THE
 BEST OPTION, HOWEVER ONLY A SUGGESTION.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE PROVIDE A LAYOUT FOR ALL
 SERVICE EQUIPMENT. PLEASE PROVIDE
 DISCONNECTING MEANS FOR THE FEEDER
 COMING FROM GEN. THIS NEED ONLY BE
 DISCONECT, DOES NOT REQUIRE OCP. THIS
 MAY BE ONE ON THE LINE SIDE OF ATS'S
 FROM GEN OR TWO DISCONNECTS ON THE LOAD
 SIDE OF THE ATS'S.PLEASE KNOW, IF THE
 EXISTING MCB PANELS ARE OUTSIDE GROUPED
 WITH THE NEW SE RATED ATS'S THEN A THE
 DISCONNECTING MEANS NOTED ABOVE WOULD
 NOT BE REQUIRED. (( PLEASE KNOW, THE
 BRKR ON GEN UNIT IS NOT ACCEPTABLE FOR
 THE REQUIRED MEANS OF DISCONNECT.
 ** THE SE RATED ATS'S ONLY DISCONNECT
 THE POWER FROM THE NORMAL/FPL SIDE.
 225.31-225.39,110.27 ETC.
  
 3) NOTE: NO, THIS INCLUDES LOAD
 CALCULATIONS SUBMITTED.
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE KNOW, ALL PLANS SHALL
 BEAR THE PRINTED NAME AND THE SIGNATURE
 OF THE PERSON RESPONSIBLE FOR
 PLANS/DESIGN.
 FBC ADMIN SECT 106.1.2
  
 4) NOTE:OK, HOWEVER PLANS ARE BEING
 ROUTED TO ZONING FOR VERIFICATION OF SET
 BACK.
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE KNOW, THE GEN WILL BE
 REQUIRED TO BE LOCATED A MIN OF 5' FROM
 THE DWELLING AND ANY OTHER SURROUNDING
 STRUCTURAL ELEMENTS.
 PLEASE KNOW, AS PER LETTER OBTAINED FROM
 GENERAC, THE MIN RECOMMENDED CLEARENCES
 FOR LIQUID COOLED UNITS IS 5FT.
 PLEASE SEE THAT MANUFACTURE SPECS
 SUBMITTED INDICATED THE MIN CLEARENCE.
 110.3,
 ** PLEASE KNOW, THE SITE PLAN WHICH WAS
 STAMPED BY ZONING WILL NEED TO BE
 REVISED IF UNIT IS 5FT FROM DWELLING.
  
 ** NEW NOTE **
 5) NOTE: PLEASE SEE TWO SMALL APPL
 CIRCUITS ARE BEING INDICATED, HOWEVER
 SHOWS 3500 VA. PLEASE SEE 220.16 (1500VA
 EACH).
 PLEASE ALSO SEE 220.18 AS THE MIN VA TO
 BE FIGURED FOR ELEC DRYERS ARE 5000VA
 PLEASE ADJUST CALCULATIONS.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]