| Date |
Text |
| 2006-07-21 00:00:00 | ******* UNSAT ********* |
| | |
| | 1) NOTE: PLEASE CORRELATE PLANS, RISER |
| | AND PANEL SCHEDULES. |
| | PLEASE SEE PLANS SHOWS PANEL R-8, P* AND |
| | SEE RISER SHOWS L8A, R8B, AND PANEL |
| | SCHEDULE SHOW P8B L8A. |
| | 106.1.2 FBC |
| | |
| | 2) NOTE: PLEASE SEE TRANSFORMER FOR |
| | EXISTING PANEL NOTED ABOVE COULD NOT BE |
| | LOCATED. |
| | IF EXISTING, PLEASE ALSO IDENTIFY ON |
| | TRANSFORMER SCHEDULE (EVEN IF EXISTING |
| | ). |
| | 106.1.2 FBC, 90.7 |
| | |
| | 3) NOTE: PLEASE SEE 240.21 408.16 AS A |
| | NOTED ON TRANSFORMER SCHEDULE MENTIONS |
| | FOR THE MAINS ON THE PANELS ON THE |
| | SECONDARY SIDE OF TRANSFORMER TO BE THE DISCONNECTING |
| | MENAS, HOWEVER PLEASE SEE |
| | PANELS AS TWO ARE SHOWN AS MLO> |
| | |
| | 4) NOTE: PLEASE SEE THAT PLANS REFLECT |
| | THE FOLLOWING CODES AT A MIN. |
| | 2002 NFPA-70, 2002 NFPA-72, 2003 |
| | NFPA-101 |
| | |
| | 5) NOTE: PLEASE HAVE ENGINEER SIGN PLANS |
| | WITHHIS RECOGNIZED SIGNATURE AND THAT |
| | OF WHICH IS ONFILE WITH THE CITY OF |
| | WEST PALM BEACH. |
| | |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND BEFORE |
| | RESUBMITTING PLANS. PLEASE BE SURE TO |
| | COMPLETELY REMOVED ANY OLD/VOIDED SHEETS |
| | AND ONLY INSERT NEW REVISED SHEETS INTO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | PLEASE ONLY SUBMIT ONE SET OF THE OLD |
| | VOIDED SHEETS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |