Plan Review Notes
Plan Review Notes For Permit 06070070
Permit Number 06070070
Review Stop B
Sequence Number 1
Notes
Date Text
2006-07-18 00:00:00 
  
 DENIED
  
 1) PER 1019.1.2 PENETRATIONS.FBC
 PENETRATIONS INTO AND OPENINGS THROUGH
 AN EXIT ENCLOSURE ARE PROHIBITED EXCEPT
 FOR REQUIRED EXIT DOORS, EQUIPMENT AND
 DUCTWORK NECESSARY FOR INDEPENDENT
 PRESSURIZATION, SPRINKLER PIPING,
 STANDPIPES, ELECTRICAL RACEWAY FOR FIRE
 DEPARTMENT COMMUNICATION AND ELECTRICAL
 RACEWAY SERVING THE EXIT ENCLOSURE AND
 TERMINATING AT A STEEL BOX NOT EXCEEDING
 16 SQUARE INCHES (0.010 M 2 ). SUCH
 PENETRATIONS SHALL BE PROTECTED IN
 ACCORDANCE WITH SECTION 712 . THERE
 SHALL BE NO PENETRATIONS OR
 COMMUNICATION OPENINGS, WHETHER
 PROTECTED OR NOT, BETWEEN ADJACENT EXIT
 ENCLOSURES.
  
 2) PERMIT NUMBER 06060243 WAS ISSUED FOR
 THE REMOVAL OF ALL PIPINNG FROM
 STAIRWELLS
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716