| Plan Review Notes For Permit 06070059 |
| Permit Number |
06070059 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-07-16 00:00:00 | ****** UNSAT ********** | | | | | | 1) NOTE: PLEASE INDICATE THIS SIZE OF | | | THE EXISTING DISCONNECT SHOWN ON RISER | | | FEEDING THE 125 MLO PANEL. UNABLE TO | | | VERIFY CONDUCTORS, OPC ETC. | | | 240.4,215.5,310.16 | | | | | | 2) NOTE: PLEASE PROVIDE PANEL SCHEDULE | | | FOR BRANCH CIRCUITS, OCP FOR EACH | | | CIRCUIT BEING TAKEN TO 2ND FLR J-BOX. | | | PLEASE ALSO KNOW, DERATING FOR THESE | | | BRANCH CIRUITS WILL BE REQUIRED FOR | | | AMBIENT AIR TEMPS ON OUTSIDE WALL. | | | 310.16 | | | PLEASE ALSO SEE THE NUMBER OF CIRCUITS | | | IS NOT CLEAR AS THE PRINT OF THE SHEET | | | SEEMS TO CUT THIS OFF. | | | | | | 3) NOTE: PLEASE KNOW, ALL PLANS SHALL | | | BEAR THE PRINTED NAME AND THE SIGNATURE | | | OF THE PERSON RESPONSIBLE FOR | | | PLANS/DESIGN. | | | FBC ADMIN SECT 106.1.2 | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|