| Plan Review Notes For Permit 06070045 |
| Permit Number |
06070045 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-07-07 00:00:00 | *** DENIED *** | | | 1) PLEASE SUBMITMANUAL J CALCULATIONS, | | | PER 2004 FBC 13-607.1.ABC.1 . | | | | | | 2) NEED TO SUBMIT TWO SETS OF PLANS AND | | | TWO COPIES OF ALL DOCUMENTS. ALL | | | INFORMATION, DRAWINGS,SPECIFICATIONS AND | | | ACCOMPANYING DATA SHELL BEAR THE NAME | | | AND SIGNATURE OF THE PERSON RESPONSIBLE | | | FOR THE DESIGN. PER 2004 WPB(A) FBC | | | 106.1 . | | | | | | 3) PLANS NEED THE ARCHITECT'S SEAL ON | | | THEM, AS HIS NAME AND INFORMATION IS IN | | | THE TITLE BLOCK, PER FAC 61G1-16.003 . | | | | | | 4) SHOW ON MECHANICAL PLANS THE TOTAL | | | AND SENSIBLE BTU'S FOR EACH SYSTEM. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|