| Notes |
| Date |
Text |
| 2006-07-13 00:00:00 | | | | | | | DENIED | | | | | | 1) FLOOR PLAN SHALL SHOW BEDROOM LAYOUT | | | AND WHERE THE 2 DIFFERENT WINDOWS ARE TO | | | BE INSTALLED. BE AWARE THAT THE EGRESS | | | SWING OPEN WINDOWS FROM BOTH NOA'S HAVE | | | A MAXIMUM SIZE LIMITATION OF 37"X50 5/8" | | | IF YOU PLAN TO PUT 2 TOGETHER IN THE 75" | | | OPENING A MULLION WOULD BE NECESSARY AND | | | A PRODUCT APPROVAL WILL BE REQUIRED. | | | | | | 2) PROVIDE ENGINEERED DESIGN FOR INFILL | | | ESPECIALLY WHERE THE NEW WINDOW WILL BE | | | ATTACHED, ALSO DETAIL THE NEW BUCK | | | ATTACHMENT THAT SHALL BE DESIGNED TO | | | TRANSFER THE WIND LOADS PLACED ON THE | | | WINDOW TO THE STRUCTURE PER 1714.5.4.2 | | | FBC | | | | | | BLDG PLAN REVIEW | | | ADRIAN MORSE | | | 561-805-6716 |
|