| 2006-08-08 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 06070002 |
| | ADD: 1601 FORUM PLACE |
| | CONT: PASS INTERNATIONAL |
| | TEL: (954)496-3133 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 2) 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION |
| | THAT IS REQUIRED FOR RECORD |
| | KEEPING & FOR CERTIFICATE OF OCCUPANCY: |
| | A) THE EDITION OFTHE CODE UNDER WHICH |
| | THE PERMIT WAS ISSUED. |
| | B) THE USE AND OCCUPANCY, IN ACCORDANCE |
| | WITH THE PROVISIONS OF CHAPTER 3. |
| | C) THE TYPE OF CONSTRUCTION AS DEFINED |
| | IN CHAPTER 6, TABLE 601. |
| | D) THE DESIGN OCCUPANT LOAD, SEE 1004. |
| | E) IF AN AUTOMATIC SPRINKLER SYSTEM IS |
| | PROVIDED, WHETHER THE SPRINKLER SYSTEM |
| | IS REQUIRED. |
| | F) ANY SPECIAL STIPULATIONS & CONDITIONS |
| | OF THE BUILDING PERMIT. |
| | |
| | 3) PLANS INDICATE THE USE OF FIRE |
| | RETARDANT TREATED PLYWOOD AS BACKING FOR |
| | THE EXPANDED METAL WIRE LATH. TABLE 601 |
| | FOOTNOTE (C-2). |
| | 2. IN TYPE I AND II CONSTRUCTION, |
| | FIRE-RETARDANT-TREATED WOOD SHALL BE |
| | ALLOWED IN BUILDINGS INCLUDING GIRDERS |
| | AND TRUSSES AS PART OF THE ROOF |
| | CONSTRUCTION WHEN THE BUILDING IS: |
| | I. TWO STORIES OR LESS IN HEIGHT; |
| | II. TYPE II CONSTRUCTION OVER TWO |
| | STORIES; OR |
| | III. TYPE I CONSTRUCTION OVER TWO |
| | STORIES AND THE VERTICAL DISTANCE FROM |
| | THE UPPER FLOOR TO THE ROOF IS 20 FEET |
| | OR MORE. |
| | THE ABOVE FOOTNOTE IS THE ONLY AREAS |
| | THAT PLYWOOD COULD BE USED IN ROOF |
| | CONSTRUCTION. |
| | |
| | 4) THE OTHER ISSUE WITH PLYWOOD IS |
| | CONSIDERED SOLID BACKING AND FOR WIRE |
| | LATH SPACED 1/4" OFF THE FACE OF THE |
| | PLYWOOD TO ALLOW THE STUCCO TO KEY. SEE |
| | ASTM C-1063.WE WILL NEED TO KNOW THE |
| | WWEIGHT OF THE WIRE LATH TO BE USED, |
| | WHAT TYPE OF FRAMING WIL BEUSED TO |
| | SUPPORT THE WIRE LATH. |
| | |
| | 5) DISCREPANCY THE PERMIT APPLICATION |
| | INDICATES ONLY 614 SQ FT OF BREEZEWAY IS |
| | TO BE REPAIRED. WHEREAS THE PLANS IN THE |
| | KEY PLAN 2,432 OF NEW CEILING AND 3,475 |
| | OF NEW GROUND SURFACE ? PLEASE UPDATE |
| | THE PERMIT APPLICATION AND VALUE OF |
| | PROJECT OR THE CITY WILL USE MARSHAL & |
| | SWIFT TO CALCULATE THE VALUE OF THE |
| | PROJECT. |
| | |
| | 6) WILL THERE BE NEW ROOF DECKS |
| | REQUIRING ROOFING PERMITS? |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | |
| | |