2006-10-20 21:18:45***** UNSAT 4TH REVIEW *******
  
 1) NOTE: PLEASE SEE LIGHTING PERFORMANCE CALCULATIONS
 ARE DONE UNDER THE 2000 IECC??
 PLEASE SEE ALL PREVIOUS NOTES FROM ALL PREVIOUS REVIEWS
 WHICH REQUIRES PERFORMANCE CALCULATIONS TO BE DONE PER
 FBC 2004. PLEASE KNOW, IT IS THE UNDER STANDING OF THIS
 REVIEWER THAT"COMCHECK " WHICH IS BEING USED HAS A
 2004 FBC PERFORMANCE EQUIVALENT OR THERE-ABOUTS WHICH
 SHOULD HAVE EQUAL VALUES ETC.
 PLEASE KNOW, WE CAN NOT ACCEPT UNDER FLORIDA STATUES
 CALCULATIONS, PLANS ETC DONE UNDER CODES WHICH ARE NOT
 ADOPTED UNDER THE FLORIDA BUILDING CODE WHICH IS
 ADOPTED INTO THE FLORIDA STATUES.
 PLEASE SEE ALL ROOMS INCLUDING BATH RMS CONTAINING
 FLOOR TO CEILING HEIGHT PARTITIONS REQUIRE OVER RIDE
 DEVICES AS STATED IN ALL PREVIOUS REVIEWS.
 PLEASE SEE 13-415.1.ABC.1.2
  
 ** PLEASE KNOW, A CALL WAS PLACED TO THE ENGINEER'S
 OFFICE AND A MESSAGE WAS LEF T FOR MR. PATRICAK DAVITT
 AT APPROX 8PMTO CALL THIS OFFICE ASAP.IF THE
 MESSAGE IS OBTAINED BY MR. DAVITT , THIS REVIEWER WILL
 BE IN THE OFFICE BOTH SAT AND SUN ALL DAY FOR
 CONSULTATION.
  
 PLEASE CONTACTTHIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717