Plan Review Notes
Plan Review Notes For Permit 06061761
Permit Number 06061761
Review Stop E
Sequence Number 3
Notes
Date Text
2006-09-21 00:00:00****** UNSAT 3RD REVIEW *******
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW STILL NEED TO BE ADDRESSED.
 PLEASE SEE NOTES BELOW AS THEY ARE TAKEN
 DIRECTLY FROM PREVIOUS REVIEW.
 PLEASE SEE NEW NOTES BELOW PREVIOUS
 NOTES.
  
  
 1) NOTE: OK.
 PLEASE SURE TO REPLACE ANY SHEETS AS
 NEEDED BASED ON THIS REVIEW OF NOTES.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE KNOW, ONCE ALL REVIEWS
 ARE DONE AND BEFORE RSUBMITTING PLANS
 ALL OLD/VOIDED SHEETS SHALL BE
 COMPLETELY REMOVED FROM SETS AND ONLY
 THE NEW REVISED SHEETS SHALL BE INSERTED
 INTO TWO COMPLETE SETS FOR REVIEW AND
 STAMPING. ONLY ONE SET OF THE OLD/VOIDED
 REMOVED SHEETS SHOULD BE SUBMITTED AS
 REFERENCE.
 106.1 ADMIN SECT FBC.
  
 2) NOTE: NO, 3RD REQUEST, PLEASE SEE
 SOME NUMBER OF "F97-000003792" IS NOW
 BEING PLACED ON PLANS FOR THE
 CERTIFICATE OF AUTHORIZATION NUMBER AS
 REQUIRED. PLEASE SEE THIS NUMER IS NO
 SUCH NUMBER AS LISTED WITH THE STATE OF
 FLORIDA'S DEPARTMENT OF BUSINESS AND
 PROFESSIONAL REGULATION. PLEASE KNOW,
 EVEN ENTERING IN JUST 3792 , COMES UP AS
 A "NULL AND VOID" FOR AN INTERIOR
 DESIGNER. PLEASE SEE A SERCH FOR ANY
 NAME LISTED UNDER "LITTLE" CAME UP WITH
 A COMPANY LOCATED IN NORTH CAROLINA,
 WHICH IS "INC". THESE SHEETS IN WHICH I
 HAVE PRINTED OUT FROM THE STATE ARE
 BEING ATTACHED TO MY COMMENTS.
 PLEASE STILL SEE THE MISSING "PRINTED"
 LICENSE NUMBER FOR THE ARCHITECT ON
 TITLE BLOCKS WHICH GOES ALONG WITH THE
 PINTED NAME WHICH WAS DONE.
 ENGINEERING FIRM WAS CORRECTED.
  
 ** PREVIOUS REVIEW NOTE, REVIEW #2**
  
 NO, PLEASE SEE TITLE BLOCKS FOR
 ARCHITECTURAL FIRM IS STILL MISSING THE
 REQUIRED FIRM LICENSE NUMBER WHICH IS
 ALSO KNOWN AS THE "CERITIFICATE OF
 AUTHORIZATION NUMBER".
 PLEASE ALSO SEE THE MISSING 'PRINTED
 NAME AND LICENSE NUMBER FOR THE
 ARCHITECT. 61G1-16.004, FS 481.219
  
 ** THIS IS REQUIRED FOR ALL TRADES AND
 FOR ALL SHEETS WHETHER OR NOT COMMENT IS
 MADE BY OTHER REVIEWER(S).
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MISSING INFORMATION
 REQUIRED ON TITLE BLOCKS FOR
 ARCHITECTURAL FIRM AS REQUIRED UNDER
 FLORIDA ADMINISTRATIVE CODE 61G1-16.004
 AND FLORIDA STATUES 481.219
 PLEASE SEE MISSING CERTIFICATE OF
 AUTHORIZATION NUMBER, PRINTED NAME AND
 PRINTED LICENSE NUMBER FOR SAID
 ARCHITECT ALSO.
 PLEASE KNOW, THIS IS REQUIRED ON ALL
 PLANS AND FOR ALL SHEETS CONTAINING THIS
 TITLE BLOCK WHETHER OR NOT COMMENT IS
 MADE BY OTHER REVIEWER(S).
  
 3) NOTE: OK.
  
 4) NOTE:NO, PLEASE SEE SOME NEC
 ARTICLES IN NOTES ON E-4 ARE STILL BEING
 SHOWN FROM THE 1996 CODE.
 THIS COULD BE REDLINED, HOWEVER PLEASE
 CORRECT OR REMOVE. THIS IS BEING
 REDLINED WHERE ON PLANS.
  
 ** PREVIOUS REVIEW NOTE **
 OK, HOWEVER PLEASE SEE SOME
 CODE ARTICLE NUMBERS AS SHOWN IN NOTES
 ETC ARE NOT FROM THE CURRENT NEC, 2002.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE THAT ALL THE CURRENT
 CODES ARE REFLECTED AS ADOPTED BY THE
 STATE OF FLORIDA. PLEASE SEE THE
 FOLLOWING SHALL BE INDICATED ON PLANS.
 PLEASE ALSO SEE SOME CODES REFLECTED ON
 PLANS ARE FROM THE "1996" NEC.
 PLEASE REF; 2002 NFPA-70, 2002 NFPA-72,
 2003 NFPA-101, AND 2004 FBC.
  
 5) NOTE: OK, HOWEVER NOW THE MAIN
 DISCONNECT FROM LANDLOARD GUTTER IS
 BEING SHOWN IN FRONT OF THE METER.
 (LINESIDE). PLEASE SEE THESE NEED
 REVERSING.
  
 ** PREVIOUS REVIEW NOTE, REVIEW #2**
 NO, PLEASE SEE THE RESPONSE FOR
 THE SERVICE IS NOTED, HOWEVER PLEASE
 KNOW THIS IS A NEW TENAT SPACE BEING
 DERIVED FROM THE EXISTING MAIN SERVICE
 TO THE BUILDING. THE INFORMATION FOR THE
 EXISTING METER AND MAIN ETC IS "NOT" ON
 PREVIOUS PLANS AS THIS IS A NEW SPACE
 BEING CREATED.
 PLEASE COMPLETE RISER INCLUDING
 INFORMATION FOR NEW METER WITH "FLOATING
 NEUTRAL", SIZE, AND MAINETC.
 PLEASE KNOW, THE RISER AS SHOWN SHOWS
 SERVICE TO THIS SPACE AS BEING
 UN-METERED FROM THE LAND LORDS MAIN
 PANEL, YET THIS IS NOT HOW SERVICE IS AT
 BUILDING OR HOW NEW SERVICE IS PROVIDED.
 PLEASE SEE MISSING METERING FOR SPACE
 ETC.
 PLEASE SEE OTHER COMMENTS BELOW WITH
 RESPECT TO LOADS AND AIC RATINGS.
 230.70,230.72, 240.4,310.16 ETC.
  
 ** PREVIOUS REVIEW NOTE REVIEW #1 **
 PLEASE SEE THE PERMIT FOR
 CREATING THIS TENANT SPACE SHOWS THE HV
 277/480V ELECTRICAL PANEL BEING
 INSTALLED BY THEM.??
 IN EITHER CASE, AFTER COORDINATION ON
 DESIGNERS BEHALF, IF THIS SCOPE OF WORK
 IS GOING TO INCLUDE THE INSTALATION OF
 PANEL INTO TENANT SPACE. PLEASE IDENTIFY
 THE EXISTING LOAD ON THE 1200A MAIN
 SHOWN ALONG WITH NEW LOAD OF THIS
 TENANT.
 PLEASE INCLUDE THE CONDUCTORS FROM
 GUTTER TO METER, METER TO MAIN ETC.
 IF THE PANEL "H" WHICH IS SHOWN ON THESE
 PLANS OR PANEL "A" WHICH IS SHOWN ON THE
 OTHER IS GOING TO BE INSTALLED UNDER
 THIS PERMIT PLEASE REVISE.
 PLEASE INDICATE BY NOTE THAT A
 "FLOATING NEUTRAL" SHALL BE INSTALLED.
 250.6,250.24B,310.16,240.4, 215.5, ETC
  
 6) NOTE: OK.
  
  
 7) NOTE: OK.
  
 8) NOTE: OK.
  
 9) NOTE: OK.
  
 10) NOTE: OK.
  
 11) NOTE: OK.
  
 12) NOTE: OK.
  
 13) NOTE: NO, COMPLIANCE HAS NOT BEEN
 MET AS OF YET. PLEASE SEE THE
 ENERG/LIGHTING CALCULATIONS ARE NOW
 BEING SUBMITTED FOR REVIEW FOR THE FIRST
 TIME. PLEASE SEE THE ITEMS FOR CONTROLS
 ETC ARE NOT CHECKED ON COMPLIANCE CHECK
 LIST. PLEASE SEE THE NUMBER OF FIXTURES
 ON PLANS EXCEED THAT OF THE NUMBER OF
 FIXTURES IN CALCULATIONS. PLEASE ALSO
 SEE FBC TABLES FOR SPACE BY SPACE
 ALLOWANCES.
 ** CONTROLS AND OVER-RIDES SEEM TO BE
 OK.
  
  
 **PREVIOUS REVIEW NOTE REVIEW #2**
 NO, PLEASE SEE A CONTACTOR IS
 BEING SHOWN, HOWEVER COMPLIANCE FOR THE
 2004 FBC CHAPTER 13 STILL NEEDS TO BE
 SHOWN. PLEASE SEE MISSIGN OVER-RIDES
 LOCATED IN AREAS IN EGRESS/INGRESS INTO
 SPACE, LOCATIONS SO THE OCCUPANT CAN SEE
 ALL LIGHTING BEING CONTROLLED/OVER-RIDEN
 ETC.
 PLEASE SEE NO INFORMATION WAS SUBMITTED
 FOR THE OVER-RIDE DEVICES, ALL OR
 DEVICES SHALL AUTOMATICALLY SHUT OFF AS
 PRE-DETERMINED BY THE CODE. TIMES WERE
 GIVEN ON PREVIOUS REVIEW.
 PLEASE SEE MISSING LIGHTING DENSITIES
 ETC.
 NO CALCULATIONS WERE SUBMITTED FOR NEW
 SPACE.
 PLEASE SEE 13-415.1.ABC.1.1,.1.2,.1.3,
 13-415.1.AB.1,13-415.2.ABC.1, TABLES FOR
 LPD'S, 415.2.C1, 415.2.B.1 ETC.
 PLEASE KNOW, ALL CODES WERE NOTE GIVEN,
 HOWEVER REFERENCE TO THE 2004 FBC
 CHAPTER 13 WAS GIVEN.
 PLEASE KNOW, THE LC PANELBEING SHOWN
 IS OK, HOWEVER SEE OTHER ITEMS AS NOTED.
 PLEASE KNOW, COULD NOT LOCATE THE TIME
 SCHEDULING.
  
 **PREVIOUS REVIEW NOTE REVIEW #1**
 PLEASE SEE FBC CHAPTER 13,
 13-415.1.ABC.1.1, .1.2 AND .1.3.
 PLEASE SHOW THE TIME SCHEDULING, THE
 LOCATION OF THE REQUIRED OVER RIDES
 DEVICES, AND THE TYPE OF PROPOSED OVER
 RIDE DEVICES.
 PLEASE KNOW, IF A TIMER TYPE, A MAX OF
 4HRS SHALL BE INDICATED. IF AN OCC
 SENSORS, MOTION TYPE DEVICE ETC IS BEING
 SHOWN , A MAX TIME OF 30 MINS SHALL BE
 INDICATED.
  
 14) NOTE: OK.
  
 15) NOTE: OK.
  
 *** NEW NOTES **
  
 1) NOTE: OK.
  
 2) NOTE: OK, AS THE INFORMATIONWAS
 SUBMITTED, HOWEVER NOT CORRECT AS THIS
 TIME.
  
 ** PREVIOUS NOTE **
 PLEASE SEE FS 553.80(2)(B) WITH
 RESPECT TO THE DESIGN PROFESSIONAL AND
 REPEAT COMMENTS FOR CODE COMPLIANCE.
 THIS IS ONLY A NOTICE GIVEN AT THIS
 TIME.
  
  
 PLEASE SEE COMMENTS FROM OTHER TRADES
 WHICH MAY HAVE AN AFFECT ON ELECTRICAL
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTRUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  