| Date |
Text |
| 2006-09-21 00:00:00 | ****** UNSAT 3RD REVIEW ******* |
| | |
| | ** PLEASE SEE SOME NOTES FROM PREVIOUS |
| | REVIEW STILL NEED TO BE ADDRESSED. |
| | PLEASE SEE NOTES BELOW AS THEY ARE TAKEN |
| | DIRECTLY FROM PREVIOUS REVIEW. |
| | PLEASE SEE NEW NOTES BELOW PREVIOUS |
| | NOTES. |
| | |
| | |
| | 1) NOTE: OK. |
| | PLEASE SURE TO REPLACE ANY SHEETS AS |
| | NEEDED BASED ON THIS REVIEW OF NOTES. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE KNOW, ONCE ALL REVIEWS |
| | ARE DONE AND BEFORE RSUBMITTING PLANS |
| | ALL OLD/VOIDED SHEETS SHALL BE |
| | COMPLETELY REMOVED FROM SETS AND ONLY |
| | THE NEW REVISED SHEETS SHALL BE INSERTED |
| | INTO TWO COMPLETE SETS FOR REVIEW AND |
| | STAMPING. ONLY ONE SET OF THE OLD/VOIDED |
| | REMOVED SHEETS SHOULD BE SUBMITTED AS |
| | REFERENCE. |
| | 106.1 ADMIN SECT FBC. |
| | |
| | 2) NOTE: NO, 3RD REQUEST, PLEASE SEE |
| | SOME NUMBER OF "F97-000003792" IS NOW |
| | BEING PLACED ON PLANS FOR THE |
| | CERTIFICATE OF AUTHORIZATION NUMBER AS |
| | REQUIRED. PLEASE SEE THIS NUMER IS NO |
| | SUCH NUMBER AS LISTED WITH THE STATE OF |
| | FLORIDA'S DEPARTMENT OF BUSINESS AND |
| | PROFESSIONAL REGULATION. PLEASE KNOW, |
| | EVEN ENTERING IN JUST 3792 , COMES UP AS |
| | A "NULL AND VOID" FOR AN INTERIOR |
| | DESIGNER. PLEASE SEE A SERCH FOR ANY |
| | NAME LISTED UNDER "LITTLE" CAME UP WITH |
| | A COMPANY LOCATED IN NORTH CAROLINA, |
| | WHICH IS "INC". THESE SHEETS IN WHICH I |
| | HAVE PRINTED OUT FROM THE STATE ARE |
| | BEING ATTACHED TO MY COMMENTS. |
| | PLEASE STILL SEE THE MISSING "PRINTED" |
| | LICENSE NUMBER FOR THE ARCHITECT ON |
| | TITLE BLOCKS WHICH GOES ALONG WITH THE |
| | PINTED NAME WHICH WAS DONE. |
| | ENGINEERING FIRM WAS CORRECTED. |
| | |
| | ** PREVIOUS REVIEW NOTE, REVIEW #2** |
| | |
| | NO, PLEASE SEE TITLE BLOCKS FOR |
| | ARCHITECTURAL FIRM IS STILL MISSING THE |
| | REQUIRED FIRM LICENSE NUMBER WHICH IS |
| | ALSO KNOWN AS THE "CERITIFICATE OF |
| | AUTHORIZATION NUMBER". |
| | PLEASE ALSO SEE THE MISSING 'PRINTED |
| | NAME AND LICENSE NUMBER FOR THE |
| | ARCHITECT. 61G1-16.004, FS 481.219 |
| | |
| | ** THIS IS REQUIRED FOR ALL TRADES AND |
| | FOR ALL SHEETS WHETHER OR NOT COMMENT IS |
| | MADE BY OTHER REVIEWER(S). |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE MISSING INFORMATION |
| | REQUIRED ON TITLE BLOCKS FOR |
| | ARCHITECTURAL FIRM AS REQUIRED UNDER |
| | FLORIDA ADMINISTRATIVE CODE 61G1-16.004 |
| | AND FLORIDA STATUES 481.219 |
| | PLEASE SEE MISSING CERTIFICATE OF |
| | AUTHORIZATION NUMBER, PRINTED NAME AND |
| | PRINTED LICENSE NUMBER FOR SAID |
| | ARCHITECT ALSO. |
| | PLEASE KNOW, THIS IS REQUIRED ON ALL |
| | PLANS AND FOR ALL SHEETS CONTAINING THIS |
| | TITLE BLOCK WHETHER OR NOT COMMENT IS |
| | MADE BY OTHER REVIEWER(S). |
| | |
| | 3) NOTE: OK. |
| | |
| | 4) NOTE:NO, PLEASE SEE SOME NEC |
| | ARTICLES IN NOTES ON E-4 ARE STILL BEING |
| | SHOWN FROM THE 1996 CODE. |
| | THIS COULD BE REDLINED, HOWEVER PLEASE |
| | CORRECT OR REMOVE. THIS IS BEING |
| | REDLINED WHERE ON PLANS. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | OK, HOWEVER PLEASE SEE SOME |
| | CODE ARTICLE NUMBERS AS SHOWN IN NOTES |
| | ETC ARE NOT FROM THE CURRENT NEC, 2002. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE THAT ALL THE CURRENT |
| | CODES ARE REFLECTED AS ADOPTED BY THE |
| | STATE OF FLORIDA. PLEASE SEE THE |
| | FOLLOWING SHALL BE INDICATED ON PLANS. |
| | PLEASE ALSO SEE SOME CODES REFLECTED ON |
| | PLANS ARE FROM THE "1996" NEC. |
| | PLEASE REF; 2002 NFPA-70, 2002 NFPA-72, |
| | 2003 NFPA-101, AND 2004 FBC. |
| | |
| | 5) NOTE: OK, HOWEVER NOW THE MAIN |
| | DISCONNECT FROM LANDLOARD GUTTER IS |
| | BEING SHOWN IN FRONT OF THE METER. |
| | (LINESIDE). PLEASE SEE THESE NEED |
| | REVERSING. |
| | |
| | ** PREVIOUS REVIEW NOTE, REVIEW #2** |
| | NO, PLEASE SEE THE RESPONSE FOR |
| | THE SERVICE IS NOTED, HOWEVER PLEASE |
| | KNOW THIS IS A NEW TENAT SPACE BEING |
| | DERIVED FROM THE EXISTING MAIN SERVICE |
| | TO THE BUILDING. THE INFORMATION FOR THE |
| | EXISTING METER AND MAIN ETC IS "NOT" ON |
| | PREVIOUS PLANS AS THIS IS A NEW SPACE |
| | BEING CREATED. |
| | PLEASE COMPLETE RISER INCLUDING |
| | INFORMATION FOR NEW METER WITH "FLOATING |
| | NEUTRAL", SIZE, AND MAINETC. |
| | PLEASE KNOW, THE RISER AS SHOWN SHOWS |
| | SERVICE TO THIS SPACE AS BEING |
| | UN-METERED FROM THE LAND LORDS MAIN |
| | PANEL, YET THIS IS NOT HOW SERVICE IS AT |
| | BUILDING OR HOW NEW SERVICE IS PROVIDED. |
| | PLEASE SEE MISSING METERING FOR SPACE |
| | ETC. |
| | PLEASE SEE OTHER COMMENTS BELOW WITH |
| | RESPECT TO LOADS AND AIC RATINGS. |
| | 230.70,230.72, 240.4,310.16 ETC. |
| | |
| | ** PREVIOUS REVIEW NOTE REVIEW #1 ** |
| | PLEASE SEE THE PERMIT FOR |
| | CREATING THIS TENANT SPACE SHOWS THE HV |
| | 277/480V ELECTRICAL PANEL BEING |
| | INSTALLED BY THEM.?? |
| | IN EITHER CASE, AFTER COORDINATION ON |
| | DESIGNERS BEHALF, IF THIS SCOPE OF WORK |
| | IS GOING TO INCLUDE THE INSTALATION OF |
| | PANEL INTO TENANT SPACE. PLEASE IDENTIFY |
| | THE EXISTING LOAD ON THE 1200A MAIN |
| | SHOWN ALONG WITH NEW LOAD OF THIS |
| | TENANT. |
| | PLEASE INCLUDE THE CONDUCTORS FROM |
| | GUTTER TO METER, METER TO MAIN ETC. |
| | IF THE PANEL "H" WHICH IS SHOWN ON THESE |
| | PLANS OR PANEL "A" WHICH IS SHOWN ON THE |
| | OTHER IS GOING TO BE INSTALLED UNDER |
| | THIS PERMIT PLEASE REVISE. |
| | PLEASE INDICATE BY NOTE THAT A |
| | "FLOATING NEUTRAL" SHALL BE INSTALLED. |
| | 250.6,250.24B,310.16,240.4, 215.5, ETC |
| | |
| | 6) NOTE: OK. |
| | |
| | |
| | 7) NOTE: OK. |
| | |
| | 8) NOTE: OK. |
| | |
| | 9) NOTE: OK. |
| | |
| | 10) NOTE: OK. |
| | |
| | 11) NOTE: OK. |
| | |
| | 12) NOTE: OK. |
| | |
| | 13) NOTE: NO, COMPLIANCE HAS NOT BEEN |
| | MET AS OF YET. PLEASE SEE THE |
| | ENERG/LIGHTING CALCULATIONS ARE NOW |
| | BEING SUBMITTED FOR REVIEW FOR THE FIRST |
| | TIME. PLEASE SEE THE ITEMS FOR CONTROLS |
| | ETC ARE NOT CHECKED ON COMPLIANCE CHECK |
| | LIST. PLEASE SEE THE NUMBER OF FIXTURES |
| | ON PLANS EXCEED THAT OF THE NUMBER OF |
| | FIXTURES IN CALCULATIONS. PLEASE ALSO |
| | SEE FBC TABLES FOR SPACE BY SPACE |
| | ALLOWANCES. |
| | ** CONTROLS AND OVER-RIDES SEEM TO BE |
| | OK. |
| | |
| | |
| | **PREVIOUS REVIEW NOTE REVIEW #2** |
| | NO, PLEASE SEE A CONTACTOR IS |
| | BEING SHOWN, HOWEVER COMPLIANCE FOR THE |
| | 2004 FBC CHAPTER 13 STILL NEEDS TO BE |
| | SHOWN. PLEASE SEE MISSIGN OVER-RIDES |
| | LOCATED IN AREAS IN EGRESS/INGRESS INTO |
| | SPACE, LOCATIONS SO THE OCCUPANT CAN SEE |
| | ALL LIGHTING BEING CONTROLLED/OVER-RIDEN |
| | ETC. |
| | PLEASE SEE NO INFORMATION WAS SUBMITTED |
| | FOR THE OVER-RIDE DEVICES, ALL OR |
| | DEVICES SHALL AUTOMATICALLY SHUT OFF AS |
| | PRE-DETERMINED BY THE CODE. TIMES WERE |
| | GIVEN ON PREVIOUS REVIEW. |
| | PLEASE SEE MISSING LIGHTING DENSITIES |
| | ETC. |
| | NO CALCULATIONS WERE SUBMITTED FOR NEW |
| | SPACE. |
| | PLEASE SEE 13-415.1.ABC.1.1,.1.2,.1.3, |
| | 13-415.1.AB.1,13-415.2.ABC.1, TABLES FOR |
| | LPD'S, 415.2.C1, 415.2.B.1 ETC. |
| | PLEASE KNOW, ALL CODES WERE NOTE GIVEN, |
| | HOWEVER REFERENCE TO THE 2004 FBC |
| | CHAPTER 13 WAS GIVEN. |
| | PLEASE KNOW, THE LC PANELBEING SHOWN |
| | IS OK, HOWEVER SEE OTHER ITEMS AS NOTED. |
| | PLEASE KNOW, COULD NOT LOCATE THE TIME |
| | SCHEDULING. |
| | |
| | **PREVIOUS REVIEW NOTE REVIEW #1** |
| | PLEASE SEE FBC CHAPTER 13, |
| | 13-415.1.ABC.1.1, .1.2 AND .1.3. |
| | PLEASE SHOW THE TIME SCHEDULING, THE |
| | LOCATION OF THE REQUIRED OVER RIDES |
| | DEVICES, AND THE TYPE OF PROPOSED OVER |
| | RIDE DEVICES. |
| | PLEASE KNOW, IF A TIMER TYPE, A MAX OF |
| | 4HRS SHALL BE INDICATED. IF AN OCC |
| | SENSORS, MOTION TYPE DEVICE ETC IS BEING |
| | SHOWN , A MAX TIME OF 30 MINS SHALL BE |
| | INDICATED. |
| | |
| | 14) NOTE: OK. |
| | |
| | 15) NOTE: OK. |
| | |
| | *** NEW NOTES ** |
| | |
| | 1) NOTE: OK. |
| | |
| | 2) NOTE: OK, AS THE INFORMATIONWAS |
| | SUBMITTED, HOWEVER NOT CORRECT AS THIS |
| | TIME. |
| | |
| | ** PREVIOUS NOTE ** |
| | PLEASE SEE FS 553.80(2)(B) WITH |
| | RESPECT TO THE DESIGN PROFESSIONAL AND |
| | REPEAT COMMENTS FOR CODE COMPLIANCE. |
| | THIS IS ONLY A NOTICE GIVEN AT THIS |
| | TIME. |
| | |
| | |
| | PLEASE SEE COMMENTS FROM OTHER TRADES |
| | WHICH MAY HAVE AN AFFECT ON ELECTRICAL |
| | PLANS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTRUCTION SERVICES DEPT. |
| | 561-805-6717 |