| Plan Review Notes For Permit 06061761 |
| Permit Number |
06061761 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-09-07 00:00:00 | *****RESPONSES/CORRECTIONS TO FIRE PLAN | | | REVIEW OF 07/10/2006***** | | | | | | | | | | | | | | | | | | 1.) OK | | | | | | 2.) OK | | | | | | 3.) OK. THE BUBBLED ITEMS ON REVISED | | | A2.0 WOULD SEEM TO INDICATE THAT TWO | | | EMERGENCY LIGHTS HAVE BEEN ADDED; | | | HOWEVER BY MAKING A COMPARISON TO THE | | | OLD SHEETS ONLY ONE EMERGENCY LIGHT WAS | | | ADDED (BUBBLED). | | | | | | 4.) OK | | | | | | 5.) COMMENT STILL NOT ADDRESSED. THE | | | BUBBLED ITEMS ON REVISED A2.0 ARE | | | EMERGENCY LIGHTS WHICH ARE NOT PART OF | | | THE FIRE ALARM SYSTEM. PLEASE INDICATE | | | ANY EXISTING OR NEW FIRE ALARM STROBES | | | WITHIN THE TENANT SPACE. | | | | | | 6.) OK; HOWEVER IT IS RECOMMENDED THAT | | | IN ADDITION TO THE FIRE EXTINGUISHER | | | LOCATED IN THE STOREROOM (SEE CS-2), A | | | CERTIFIED AND TAGGED 2A10BC FIRE | | | EXTINGUISHER BE LOCATED IN THE SALES | | | AREA 3' TO 5' ABOVE THE FLOOR IN AN | | | OBVIOUS AND ACCESSIBLE LOCATION. | | | | | | 7.) OK | | | | | | | | | | | | | | | | | | LT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 | | | | | | |
|