2006-09-07 00:00:00*****RESPONSES/CORRECTIONS TO FIRE PLAN
 REVIEW OF 07/10/2006*****
  
  
  
  
  
 1.) OK
  
 2.) OK
  
 3.) OK. THE BUBBLED ITEMS ON REVISED
 A2.0 WOULD SEEM TO INDICATE THAT TWO
 EMERGENCY LIGHTS HAVE BEEN ADDED;
 HOWEVER BY MAKING A COMPARISON TO THE
 OLD SHEETS ONLY ONE EMERGENCY LIGHT WAS
 ADDED (BUBBLED).
  
 4.) OK
  
 5.) COMMENT STILL NOT ADDRESSED. THE
 BUBBLED ITEMS ON REVISED A2.0 ARE
 EMERGENCY LIGHTS WHICH ARE NOT PART OF
 THE FIRE ALARM SYSTEM. PLEASE INDICATE
 ANY EXISTING OR NEW FIRE ALARM STROBES
 WITHIN THE TENANT SPACE.
  
 6.) OK; HOWEVER IT IS RECOMMENDED THAT
 IN ADDITION TO THE FIRE EXTINGUISHER
 LOCATED IN THE STOREROOM (SEE CS-2), A
 CERTIFIED AND TAGGED 2A10BC FIRE
 EXTINGUISHER BE LOCATED IN THE SALES
 AREA 3' TO 5' ABOVE THE FLOOR IN AN
 OBVIOUS AND ACCESSIBLE LOCATION.
  
 7.) OK
  
  
  
  
  
 LT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW