2006-07-13 00:00:00DENIED;
 1.PAGE CS-2 PLUMBING FIXTURE
 REQUIREMENTS REFERS TO FBC-2004 CHAPTER
 29. CHAPTER 29 REFERS YOU TO FBC-2004
 PLUMBING CODE. SEE TABLE 403.1 MINIMUM
 NUMBER OF REQUIRED PLUMBING FIXTURES,
 OCCUPANCY "B" ONE DRINKING FOUNTAIN IS
 REQUIRED. DRINKING FOUNTAIN IS REQUIRED
 TO BE PART OF THE PLUMBING SYSTEM,
 410.1.
 2.TRAP PRIMER REQUIRED FOR FLOOR DRAIN
 PLEASE ADD NOTE TO PLANS.
 3.WASTE AND VENT RISER DIAGRAM; LAVATORY
 VENT WILL VENT THE BATHROOM GROUP. VENTS
 NOT NEEDED ON TOILET AND FLOOR DRAIN.
 SEE PLUMBING CHAPTER 9 VENTING SEC.
 909.1, WET VENT.