| Plan Review Notes For Permit 06061761 |
| Permit Number |
06061761 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-07-13 00:00:00 | DENIED; | | | 1.PAGE CS-2 PLUMBING FIXTURE | | | REQUIREMENTS REFERS TO FBC-2004 CHAPTER | | | 29. CHAPTER 29 REFERS YOU TO FBC-2004 | | | PLUMBING CODE. SEE TABLE 403.1 MINIMUM | | | NUMBER OF REQUIRED PLUMBING FIXTURES, | | | OCCUPANCY "B" ONE DRINKING FOUNTAIN IS | | | REQUIRED. DRINKING FOUNTAIN IS REQUIRED | | | TO BE PART OF THE PLUMBING SYSTEM, | | | 410.1. | | | 2.TRAP PRIMER REQUIRED FOR FLOOR DRAIN | | | PLEASE ADD NOTE TO PLANS. | | | 3.WASTE AND VENT RISER DIAGRAM; LAVATORY | | | VENT WILL VENT THE BATHROOM GROUP. VENTS | | | NOT NEEDED ON TOILET AND FLOOR DRAIN. | | | SEE PLUMBING CHAPTER 9 VENTING SEC. | | | 909.1, WET VENT. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|